Chapter 5 Parameters|VFD-S Series
Revision August 2006, SE08, SW V2.61 5-11
Pr. Explanation Settings
Factory
Setting
NOTE
A-07 PID Output Freq. Limit d0 to d110% d100
A-08 Feedback Signal Detection Time d0.0 to d650 seconds d0.0
A-09
Treatment of the Erroneous
Feedback Signals
d0: warn and RAMP to stop
d1: warn and COAST to stop
d0
A-10 Sleep Frequency d0.0 to d400Hz d0.0
A-11 Wakeup Frequency d0.0 to d400Hz d0.0
A-12 Sleep Period d0.0 to d650 seconds d0.0
A-13 PID User Defined d0.0 to d400 d0.0