Hardware manual

AH500 Hardware Manual
3-97
3.10.2 Profiles
AHRTU-DNET-5A
1. Profile
x10
1
x10
0
Node Address
DR 1
DR 0
IN 1
IN 0
1
2
3
4
7
6
8
9
11
10
5
Number Name Description
1 Model name Model name of the module
2 Seven-segment display Display
3 Address knobs Setting the address
4 Function switch Setting the functions
5 DeviceNet connector
DeviceNet is used to interconnect control devices for data
exchange.
6 MS LED indicator Indicating the status of the module
7 NS LED indicator Indicating the status of the network
8 Label Nameplate
9 Set screw Fixing the module
10 Connector Connecting the module and a backplane
11 Projection Fixing the module
2. Address knob
s
It is used to set the node address of AHRTU-DNET-5A on a DeviceNet network. (Node addresses
range from 0 to 63.)
Setting Description
0…63 Available nodes on a DeviceNet network
64…99 Unavailable nodes on a DeviceNet network
Example: If users want to set the communication address of AHRTU-DNET-5A to 26, they can turn the
knob corresponding to x10
1
to 2, and turn the knob corresponding to x10
0
to 6.
Points for attention:
When the power supply is cut off, the node address is set. After the setting of the node address is
complete, AHRTU-DNET-5A can be supplied with power.
If AHRTU-DNET-5A is running, changing the node address is unavailable.