Instruction Manual
- 6 -
32000
)(10
16000
V
Offset
OffsetGainX
VY
Y=Voltage output, X=Digital input
Equation for current output Mode1: 0.625μA = 20mA/32,000
32000
)(20
16000
mA
Offset
OffsetGainX
mAY
Y=Current output, X=Digital input
Equation for current output Mode2: 0.5μA = 16mA/32,000
Adopt the equation of current output mode 1, substitute Gain for 19,200(12mA) and
Offset for 6,400(4mA)
32000
)(20
6400
16000
640019200 mAX
mAY
Y=Current output, X=Digital input
Voltage output – mode 0:
Digital input
10V
5V
-5V
+32000
-10V
-32000
+16000
0
Gain
Offset
Voltage
output
-32768
+32767
Mode 0 (CR#2 ~ CR#5) -10V ~ +10V,Gain = 5V (16,000),Offset = 0V (0)
Range of digital data -32,000 ~ +32,000
Max./Min. range of digital data -32,768 ~ +32,767
Current output – mode 1:
Digital input
+32000+16000
20mA
10mA
0
Offset
Current
output
+32767
Gain
Mode 1 (CR#2 ~ CR#5) 0mA ~ +20mA,Gain = 10mA (16,000),Offset = 0mA (0)
Range of digital data 0 ~ +32,000
Max./Min. range of digital data 0 ~ +32,767
Current output – mode 2: