6–20 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
CONFIGURATION SETPOINTS CHAPTER 6: SETPOINTS
6.2.6 System
Figure 17: System setpoint page
The following setpoints are available.
LED Colour Invert
Range: Red/Green, Green/Red
Default: Green/Red
When set Red/Green, the colour of Running LED is red, and the colour of the Stopped LED
is green. When set Green/Red the colour of the Running LED is green, and the colour of
the Stopped LED is red.
Tripped LED Flasher
Range: ON/YES, OFF/NO
Default: OFF/NO
This setpoint determines whether the Tripped LED flashes or is steadily illuminated when
there is a trip or lockout condition.
Self-Test Action
Range: Trip, Alarm
Default: Trip
This setpoint defines whether a self-test failure will cause a trip or an alarm.
For relay self-test, the MM300 runs a series of self-tests, including data and program
memory integrity and program execution watchdogs. If any of these tests fail, a self-test
trip or alarm is generated depending on the value of the setpoint.
Reset Lockout Using Reset Key
Range: Disabled/Enabled
Default: Disabled
If set to "enabled," the GCP/BCP reset key will perform a non-lockout and lockout reset.
NOTE
NOTE:
When a Lockout Reset is used to reset a Thermal Overload, the Thermal Capacity % will
be reset to zero.
Change Mode When Running
Range: Disabled/Enabled
Default: Enabled
If set to "enabled," the Auto/Manual mode can be changed while the motor is running.
Set Date
Set to program today’s date.