CHAPTER 6: SETPOINTS CONFIGURATION SETPOINTS
MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL 6–3
6.2 Configuration setpoints
The configuration setpoints contains data on motor configuration as well as system setup,
inputs, outputs, communications, CTs, and VTs. The following sub-pages are available.
• Motor (setpoints related to motor configuration).
• CT-VT (setpoints related to CT and VT configuration).
• Inputs (setpoints related to digital input configuration)
• Outputs (setpoints related to digital output configuration)
• Comms (setpoints related to communications configuration)
• System (setpoints related to MM300 system configuration, such as the faceplate LEDs)
• Events (setpoints related to the event recorder)
• Counters (setpoints related to the digital counters)
6.2.1 Motor setpoints
The MM300 starter function is responsible for executing the motor startup sequence,
including the pre-contactor start warning. The MM300 provides six pre-defined starters.
• Full-voltage non-reversing
• Full-voltage reversing
• Two-speed
• Wye-delta open transition
•Inverter
•Soft start
NOTE
NOTE:
By selecting a pre-defined starter, inputs and outputs are automatically assigned.
Select the Home > Setpoints > Config > Motor page to edit the motor data settings.
Figure 2: Motor data settings page
6.2.1.1 Common motor setpoints
Several motor setpoints are dependent on the chosen starter type. The setpoints shown
below are common to all starter types.