5-2 Revision October 2006, 2006PDD23000013
VFD-E type
Baud Rate 9600 P09-01=1
RTU 8, N, 2 P09-03=3
Freq. Source P02-00=3
Command Source P02-01=3
After these settings completed, connecting CME-PD01 and VFD-E series via communication
cable mentioned earlier, CME-PD01 is then energized. Two LEDs will be firstly in orange
because CME-PD01 is initialized and test itself. SP LED will be then in steady green since that
the connection is established between CME-PD01 and VFD-E series.
5.3 Cyclical Data of CME-PD01 via PROFIBUS-DP
CME-PD01 is controlled via cyclical PROFIBUS-DP channel. This channel can be used to
access the parameters of VFD-E series.
5.3.1 Useful Data Structure as Defined in PROFIDrive Profile 2.0
The structure of useful data for the cyclical channel is defined in the PROFIDrive Profile,
version 2.0. Please refer to the Parameter Process data Object (PPO).
PKW PZD
PKE IND PWE
PZD1
STW
ZSW
PZD2
HSW
HIW
PZD3 PZD4 PZD5 PZD6 PZD7 PZD8 PZD9
PZD
10
1st
word
2nd
word
3rd
word
4th
word
1st
word
2nd
word
3rd
word
4th
word
5th
word
6th
word
7th
word
8th
word
9th
word
10th
word
PPO1
PPO2
PPO3
PPO4
PPO5
PKW: Parameter ID/value STW: Control word
PZD: Process data ZSW: Status word
PKE: Parameter ID HSW: Main setpoint
IND: Sub-index HIW: Main actual value
PWE: Parameter value