Chapter 6 Parameters Setting in GSD file| CME-PD01
Revision October 2006, 2006PDD23000013 6-5
Ext_User_Prm_Data_Ref(10) = 6
Ext_User_Prm_Data_Ref(12) = 7
Ext_User_Prm_Data_Ref(14) = 8
Ext_User_Prm_Data_Ref(16) = 9
Ext_User_Prm_Data_Ref(18) = 10
Ext_User_Prm_Data_Ref(20) = 11
Ext_User_Prm_Data_Ref(22) = 12
Ext_User_Prm_Data_Ref(24) = 13
File END: ==========================================================
NOTE
The required GSD file is available and can be downloaded from the DELTA web site
http://www.delta.com.tw, or you can copy this text to a text editor such as NOTEPAD, and save
it as a GSD file named “DELT08DB.GSD”. Please make sure the extension file name is “.GSD”,
NOT “.GSD.TXT”.
6.2 Parameters Settings
The parameters in GSD file are used for the configuration of the PROFIBUS network. The
parameters description are shown in the following table:
Item Name Type Description Default
1 Data Input 1 UINT
This is a MODBUS address. The 1st word of
cyclic output data PZD will be sent to this
address.
0x2000
2 Data Input 2 UINT
This is a MODBUS address. The 2nd word of
cyclic output data PZD will be sent to this
address.
0x2001
3 Data Input 3 UINT
This is a MODBUS address. The 3rd word of
cyclic output data PZD will be sent to this
address if selecting module "4 PKW, 4 PZD".
0x0000
4 Data Input 4 UINT
This is a MODBUS address. The 4th word of
cyclic output data PZD will be sent to this
address if selecting module "4 PKW, 4 PZD".
0x0000
5 Data Output 1 UINT
This is a MODBUS address. CME-PD01 will
monitor this address, and copy the return data
to the 1st word of cyclic input data PZD.
0x2101
6 Data Output 2 UINT
This is a MODBUS address. CME-PD01 will
monitor this address, and copy the return data
to the 2nd word of cyclic input data PZD.
0x2102
7 Data Output 3 UINT
This is a MODBUS address. CME-PD01 will
monitor this address, and copy the return data
to the 3rd word of cyclic input data PZD if
selecting module "4 PKW, 4 PZD".
0x2103