RMC100 Startup Appendix C: An Example
63
deltamotion.com
Check the deadband. This system has a very small deadband, approx 5
millivolts, so we will not worry about it.
Set the gains and feed forwards to zero and issue a Set Parameters (P)
command.
Double-click the Axis 0 Auto Stop word (in the Parameters field).
Set the Overdrive, Integrator Windup and Overdrive bits to Status
only.
Set the proportional gain to a small value, such as 5. Issue a Set
Parameters (P) command.
Set the Plot Time for Axis 0 to 4.
Now make a move. The tuning process will consist of repeatedly making
moves. To easily make repeated moves, use Stored Commands:
To edit and view the Stored Commands, click Stored Command
Editor on the Stored Commands menu. The following window
appears:
For example, ALT-1 on axis 1 will issue a Go cmd to 4000 at a speed
of 10 in/sec, with acceleration rates of 100 in/(sec*sec). These are
common values for moving hydraulic systems. These values are
editable from this window.
To use the stored commands, click on any Axis 0 field, then press e.g.
ALT-1 to move to 4 in. and ALT-5 to move to 20 in. The command
will be issued to the axis where the cursor is located.
Using the Stored Commands, a move is made in this example from 2 in. to
8 in. The move will take less time than what the Plot Time is set to so that
the entire move can be viewed.
Press the Insert key. This opens the Plot window with the last move. It
looks like this: