User Manual
10 Wiring and Installation
Pin
Function
Int/Clk +
SSI + Clock
Int/Clk -
SSI - Clock
Cmn
Common
Ret/Dat +
SSI + Data
Ret/Dat -
SSI - Data
Case
RMC70 Chassis
Max Cable Length
SSI Clock Rate
Maximum Cable Length*
100 kHz
2100 ft (640 m)
150 kHz
1360 ft (415 m)
250 kHz
770 ft (235 m)
375 kHz
475 ft (145 m)
* The cable lengths are approximate, and may be affected by the type of wire and
transducer.
Wiring Instructions
• Connect both the +Clock and -Clock between the MA module and transducer for the
clock signal.
• Connect both the +Data and -Data between the MA module and transducer for the
data signal.
• Connect the transducer DC ground to Cmn. Each axis has two Cmn pins. Either of the
2 pins may be used. The Cmn must be connected to the transducer, or the signals will
not be read correctly!
• The transducer power supply is not provided by the RMC. The user must supply a
power supply. The power supply common may be connected to the same common that
is connected to the RMC70 CPU Cmn.
Diagram
deltamotion.com 1135