10 Wiring and Installation
Pin
Function
Int/Clk +
SSI + Clock
Int/Clk -
SSI - Clock
Cmn
Common
Ret/Dat +
SSI + Data
Ret/Dat -
SSI - Data
Case
RMC70 Chassis
Max Cable Length
SSI Clock Rate
Maximum Cable Length*
100 kHz
2100 ft (640 m)
150 kHz
1360 ft (415 m)
250 kHz
770 ft (235 m)
375 kHz
475 ft (145 m)
* The cable lengths are approximate, and may be affected by the type of wire and
transducer.
Wiring Instructions
Connect both the +Clock and -Clock between the MA module and transducer for the
clock signal.
Connect both the +Data and -Data between the MA module and transducer for the
data signal.
Connect the transducer DC ground to Cmn. Each axis has two Cmn pins. Either of the
2 pins may be used. The Cmn must be connected to the transducer, or the signals will
not be read correctly!
The transducer power supply is not provided by the RMC. The user must supply a
power supply. The power supply common may be connected to the same common that
is connected to the RMC70 CPU Cmn.
Diagram