User Manual

RMC70/150 and RMCTools User Manual
supply needs and connector pin-outs or cable color codes, consult your transducer
manufacturer's documentation.
Note:
The analog input Cmn pin must be connected! A disconnected Cmn pin can cause noise and
inaccurate readings.
Voltage Input, 4- or 5-wire
To minimize electrical interference:
-In and Cmn must be connected. This connected should be made as close to the
transducer as possible.
Use individually shielded twisted-pair wire.
Typically, the cable shield should be connected to earth on one end only.
If the transducer has only one common, connect the power supply and the RMC Cmn
to it. For best results, make this connection at the transducer.
Voltage Input, 3-wire