User Manual
RMC70/150 and RMCTools User Manual
Tolerance At 10 V:
Currently unavailable
Resolution
16 bits
Output Isolation
Not isolated
Overload protection
One-second short-circuit duration
Overvoltage protection
Outputs are protected by clamp diodes
Fault Input
Input Characteristics
12-24 VDC, sinking or sourcing
Logic Polarity
True High
Input "High" Range
7 to 26.4 VDC (polarity independent)
3mA maximum
Input "Low" Range
0 to 3.5 VDC (polarity independent)
<1 mA
Maximum Propagation
Delay
100 µs
Enable Output
Output Type
Solid State Relay
Logic Polarity
User Selectable to Active Open or Active Closed
Isolation
500 VAC
Rated Voltage
12-24 V, max 30 V (DC or peak AC voltage)
Maximum Current
75 mA
Maximum Propagation
Delay
1.5 ms
Closed
Low Impedance (50 Ω maximum)
Open
High Impedance (<1 µA leakage current at 250 V)
See the Fault Input and Enable Output topics for usage details.
LEDs
Axis LED
This LED represents the input and control status for the axis. This bi-color (red/green)
LED has the following states:
State
Description
Steady
Off
No power or this input is not assigned to an axis.
Steady
Green
The axis is either in closed loop control or is a reference axis. The axis is
not halted.
Flashing
Green
The input is in open loop and the axis is not halted (not possible for
reference axes).
Flashing
Red
A Closed Loop Halt or External Halt has occurred because an error bit is set
(not possible for reference axes). The LED will not turn red due to a halt
caused by halt command.
Steady
Red
An Open Loop Halt or Direct Output Halt has occurred because an error bit
is set (for reference axes, any halt has occurred). The LED will not turn red
due to a halt caused by halt command.
En/F LED
This LED represents the status of the Enable Output and Fault Input
for the axis. This bi-
color (red/green) LED will have the following states:
634 Delta Computer Systems, Inc.