8 Command Reference
Note:
See the Position-Pressure and Position-Force Control topic for information on setting up a
position-pressure or position-force axis.
Entering Pressure or Force Limit Mode
This procedure is can be used to enter Pressure/Force Limit mode.
1. Make sure the Target Pressure/Force has been set to the desired value. For example,
the Ramp Pressure/Force (Linear) (42) command can be used to set the Target
Pressure/Force to the desired value.
2. Send the Set Pressure/Force Limit Mode (40) command to enable Pressure/Force
Limit.
3. Move the axis as desired. When the motion begins to affect the pressure, the RMC will
limit the motion such that the Actual Pressure/Force does not exceed the Target
Pressure/Force.
Note:
Pressure/Force Limit mode may affect normal closed-loop motion even when the
pressure is very low. Therefore, if possible, do not enter Pressure/Force Limit until
you need to.
Changing the Target Pressure/Force
Once the axis is in pressure or force control, you can issue any of the following
pressure/force commands to change the pressure/force. For example, you can ramp the
pressure up or down, or perform a sinusoidal profile, or follow a spline. For details on
each command, see the respective help topics.
Ramp Pressure/Force (Linear) (42)
Ramp Pressure/Force (S-Curve) (41)
Stop Pressure/Force (43)
Sine Start (Prs/Frc) (76)
Sine Stop (Prs/Frc) (77)
Change Target Parameter (Prs/Frc) (81)
Curve Start (Prs/Frc) (87)
Curve Start Advanced (Prs/Frc) (89)
DO NOT issue the pressure/force commands that enter pressure/force control, because
this will exit pressure/force limit:
Hold Current Pressure/Force (19)
Enter Pressure/Force Control (Auto) (44)
Enter Pressure/Force Control (Time) (45)
Enter Pressure/Force Control (Rate) (46)
Exiting Pressure/Force Limit
An axis will exit pressure/force limit mode if any of the following occurs:
The Set Pressure/Force Limit Mode (40) command is sent with the
Pressure/Force Limit command parameter set to 0 (Disabled).
A Direct Output (9) command is sent to the axis.
An Open Loop Halt or Direct Output Halt occurs on the axis.
The Fault Controller (8) command is issued to the RMC.
For more details, see the Pressure/Force Limit
topic.
Status Bits
deltamotion.com 801