A-51643 Rev. 6 10/06/03 13
774
306
Sunday Run Mode
Auto Start Sun[Mode]
1 or 2 (Note 1)
0=Off, 1=Manual, 2=Timer, 3-10=Profile 1-8
775
307
Sunday Run Time
Auto Start Sun[Time]
1 or 2 (Note 1)
00h00m to 23h59m
776
308
Monday Run Mode
Auto Start Mon[Mode]
1 or 2 (Note 1)
0=Off, 1=Manual, 2=Timer, 3-10=Profile 1-8
777
309
Monday Run Time
Auto Start Mon[Time]
1 or 2 (Note 1)
00h00m to 23h59m
778
30A
Tuesday Run Mode
Auto Start Tue[Mode]
1 or 2 (Note 1)
0=Off, 1=Manual, 2=Timer, 3-10=Profile 1-8
779
30B
Tuesday Run Time
Auto Start Tue[Time]
1 or 2 (Note 1)
00h00m to 23h59m
780
30C
Wednesday Run Mode
Auto Start Wed[Mode]
1 or 2 (Note 1)
0=Off, 1=Manual, 2=Timer, 3-10=Profile 1-8
781
30D
Wednesday Run Time
Auto Start Wed[Time]
1 or 2 (Note 1)
00h00m to 23h59m
782
30E
Thursday Run Mode
Auto Start Thu[Mode]
1 or 2 (Note 1)
0=Off, 1=Manual, 2=Timer, 3-10=Profile 1-8
783
30F
Thursday Run Time
Auto Start Thu[Time]
1 or 2 (Note 1)
00h00m to 23h59m
784
310
Friday Run Mode
Auto Start Fri[Mode]
1 or 2 (Note 1)
0=Off, 1=Manual, 2=Timer, 3-10=Profile 1-8
785
311
Friday Run Time
Auto Start Fri[Time]
1 or 2 (Note 1)
00h00m to 23h59m
786
312
Saturday Run Mode
Auto Start Sat[Mode]
1 or 2 (Note 1)
0=Off, 1=Manual, 2=Timer, 3-10=Profile 1-8
787
313
Saturday Run Time
Auto Start Sat[Time]
1 or 2 (Note 1)
00h00m to 23h59m
788 -- 1023
314 -- 3FF
Illegal, Available to application
Relay Outputs Holding Registers
Relay Output 1
1024
400
Output 1 Type
Relay 1[Relay Type]
1 or 2 (Note 1)
0=Off, 1=Alarm, 2=Cycle, 3=Event
1025
401
Relay 1 Action
Relay 1[Relay Action]
1 or 2 (Note 1)
0=NDE, 1=NE, 2=NDEL, 3=NEL
1026
402
Alarm 1 Type
Relay 1[Alarm Type]
1 or 2 (Note 1)
0 = High, 1 = Low, 2 = +Dev, 3 = -Dev, 4 = +/-Dev
1027
403
Alarm 1 Setpoint
Relay 1[AlmHi/LoSP]
1 or 2 (Note 1)
read/written as xxxx deg. F.
1028
404
Alarm 1 Deviation Setpoint
Relay 1[AlmDevBand]
1 or 2 (Note 1)
read/written as xxxx deg. F.
1029
405
Alarm 1 Inhibit
Relay 1[AlmInhibit]
1 or 2 (Note 1)
0=Disabled, 1=Enabled
1030
406
Event 1 Type
Relay 1[Event Type]
1 or 2 (Note 1)
0=Time, 1=Temp
1031
407
Event 1 Setpoint
Relay 1[Event SP]
1 or 2 (Note 1)
read/written as xxxx deg. F.
Relay Output 2
1032 -- 1039
408 -- 40F
Output 2 Holding Registers (same as Output 1)
1 or 2 (Note 1)
Relay Output 3
1040 -- 1047
410 -- 417
Output 3 Holding Registers (same as Output 1)
1 or 2 (Note 1)
Relay Output 4
1048 -- 1055
418 -- 41F
Output 4 Holding Registers (same as Output 1)
1 or 2 (Note 1)
Test Mode Holding Registers
1056 -- 1062
420 -- 426
Reserved for factory use
1063 -- 1135
427 -- 46F
Illegal, Available to application
Communication Holding Registers
1136
470
Controller Address
Communication[Unit Addr]
1 or 2 (Note 1)
1-247
1137
471
Communications Mode
Communication[Enable]
1 or 2 (Note 1)
0=Disabled, 1=Enabled
1138
472
Baud Rate
Communication[BaudRate]
1 or 2 (Note 1)
0=2400, 1=4800, 2=9600, 3=19.2K, 4=38.4K
1139
473
Parity
Communication[Parity]
1 or 2 (Note 1)
0=None, 1=Odd, 2=Even
1140
474
Reserved, Available to application
0
0
Real Time Clock Holding Registers
1141
475
Week Day
Clock[Day]
1 or 2 (Note 1)
1=Sunday, 2=Monday, . . . 7=Saturday
1142
476
Time
Clock[hh:mm]
1 or 2 (Note 1)
00h00m to 23h59m
1143
477
Enter
Clock[UP to Reset CLK]
1 or 2 (Note 1)
0 = No action, >0 = Set Clock
1144 -- 1151
478 -- 47F
Illegal, Reserved for standard reg.
Calibration Holding Registers