Manual

Chromalox Instruments and Controls
A-51643 Rev. 6 10/06/03 17
REGISTER ADDRESS
REGISTER DESCRIPTION
$0000
COMMUNICATIONS ACCESS CODE
$0005
KEYPAD LOCKOUT
$0007
ALARM ACKNOWLEDGE
$0008
LEVEL 1 PASSWORD (write not allowed while in setup mode)
$0009
LEVEL 2 PASSWORD (write not allowed while in setup mode)
$0010
MANUAL SETPOINT
$0040
TIMER SETPOINT
$0192
RUN/HOLD/STOP
$0194
SEGMENT ADVANCE
4.5 Monitoring and Acknowledgement of Alarms, Events, and Cycle Complete, Discrete
Inputs, and Discrete Outputs
Two input registers allow monitoring of the alarm ($0094) and event ($0095) functions associated with
relay outputs 1-4. The corresponding input register represents a binary pattern that indicates the state of
each function. Bits 0-3 of the holding register value represent item 1-4 respectively. A bit value of 0
indicates off, while a bit value of 1 indicates on. Example: A read of holding register $0098 returns a
value of $0006. This would indicate that alarms 2 and 3 are active.
The cycle complete status is monitored by reading input register $0096. A value of 0 indicates the cycle
is active, while a value of 1 indicates the cycle is complete.
Reading the discrete input addresses-$0000 - $00003 monitors the hardware states of the external inputs
Event 1-4. For details on the return values see 5.2.2 [02] Read Input Discretes. Since these inputs are
active low switch inputs, a returned value of 1 (or on) means the input is active (electrically pulled low).
Reading the discrete output addresses-$0000 - $00003 monitors the hardware states of relays 1-4. For
details on the return values see 5.2.1 [01] Read Outputs.
The audible annunciator can be monitored via input register $0097. A value of 0 indicates the audible
annunciator is off, while a value of 1 indicates on. Acknowledgement of alarms and cycle complete
audible annunciation is handled through the alarm acknowledge holding register ($0007). Writing any
non-zero value to this register will acknowledge the alarm. This register emulates the pressing of the
Page/Reset key during an audible alarm condition.