Instructions 95-8552 UV Flame Detector with Pulse Output X2200 5.
Table of Contents Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . 16 Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . .
INSTRUCTIONS UV Flame Detector with Pulse Output X2200 Important Be sure to read and understand the entire instruction manual before installing or operating the flame detection system. Any deviation from the recommendations in this manual may impair system performance and compromise safety. ATTENTION The X2200 includes the Automatic Optical Integrity (oi ®) feature — a calibrated performance test that is automatically performed once per minute to verify complete detector operation capabilities.
Magnetic oi / Manual oi Outputs Relays CAUTION These tests require disabling of all extinguishing devices to avoid release resulting from a successful test. The detector is furnished with fire and fault relays. The relays are rated 5 amperes at 30 Vdc. The Fire Alarm relay has redundant terminals and normally open / normally closed contacts, normally de-energized operation, and latching or non-latching operation. The detector incorporates both magnetic oi and manual oi test capabilities.
important Magnetic o i can be per formed with the controller’s (R7404/R7494) keylock switch in either the Normal or Test position. In Normal, the controller goes into alarm and activates its outputs. If no controller alarm output is desired, place the keylock switch in the Test position before touching the magnet to the outside of the detector. Manual oi operates only with the keylock switch in the Test position.
General APPLICATION INformation FACTORS INHIBITING DETECTOR RESPONSE Response Characteristics Glass and Plexiglas windows significantly attenuate UV radiation and must not be located between the detector and a potential flame source. If the window cannot be eliminated or the detector location changed, contact Detector Electronics for recommendations regarding window materials that will not attenuate UV radiation.
IMportant Safety Notes Table 2 UV Absorbing Gases and Vapors Warning Do not open the detector assembly in a hazardous area when power is applied. The detector contains limited serviceable components and should never be opened. Doing so could disturb critical optical alignment and calibration parameters, possibly causing serious damage. This type of damage could be undetected and could result in failure to see a fire and/or false alarm.
INSTALLATION note The recommended lubricant for threads and O-rings is a silicone free grease (part number 005003-001) available from Detector Electronics. Under no circumstances should a lubricant containing silicone be used. CENTER AXIS OF DETECTOR FIELD OF VIEW INCORRECT Detector Positioning Detectors should be positioned to provide the best unobstructed view of the area to be protected. The following factors should also be taken into consideration: • Identify all high risk fire ignition sources.
Protection Against Moisture Damage The “B” (pulse output) and “D” (oi driver) leads from each detector should be shielded from the “B” and “D” leads of all other detectors in order to prevent false alarms resulting from crosstalk between zones. It is recommended that the “A” and “C” leads also be shielded to provide maximum immunity to EMI/RFI. (See Figures 6 to 10.
4X ø0.42 (1.1) 3.0 (7.6) 4.0 (10.2) 13.1 (33.4) NOTE: THIS ILLUSTRATION SHOWS THE DETECTOR MOUNTED AT THE 10° MINIMUM. THESE DIMENSIONS WILL CHANGE BASED ON THE DETECTOR’S MOUNTING ANGLE. 3.0 (7.6) 4.0 (10.2) 10.6 (27.0) E2069 Figure 3—Q9033 Mounting Bracket Dimensions in Inches (cm) (Refer to Figure 1 for Correct Detector Orientation) Figures 11 and 12 provide examples of typical installations with an X2200 wired to a fire alarm panel. 2.
NOTE: DO NOT CONNECT THE X2200 "A" LEAD (#2/12) TO TERMINAL J1-3 (290 VDC).
NOTE: DO NOT CONNECT THE X2200 "A" LEAD (#2/12) TO TERMINAL J1-3 (290 VDC).
X2200 #2 #1 #19 #22 #2 #1 #19 #22 DETECTOR 1 X2200 #2 #1 #19 #22 #2 #1 #19 #22 J1-5 J1-13 DETECTOR 2 X2200 #2 #1 #19 #22 #2 #1 #19 #22 J1-6 J1-14 DETECTOR 3 X2200 #2 #1 #19 #22 #2 #1 #19 #22 J1-7 J1-15 DETECTOR 4 X2200 #2 #1 #19 #22 #2 #1 #19 #22 J1-8 J1-16 +24 VDC ZONE OUTPUT 1 33 – 2 CIRCUIT GROUND ZONE OUTPUT 2 34 3 +24 VDC ZONE OUTPUT 3 35 4 B1 - INPUT SIGNAL ZONE OUTPUT 4 36 5 B2 - INPUT SIGNAL ZONE OUTPUT 5 37 6 B3 - INPUT SIGNAL ZONE OUTPUT 6 38 7 B4 -
R7495 CONTROLLER (NOT FM APPROVED) X2200 #2 #1 #19 #22 #2 #1 #19 #22 24 VDC J1 + 1 +24 VDC – 2 GROUND 3 DETECTOR 1 X2200 #2 #1 #19 #22 #2 #1 #19 #22 J2-44 J2-36 4 J2 5 31 32 DETECTOR 2 X2200 #2 #1 #19 #22 #2 #1 #19 #22 33 34 J2-45 J2-37 DETECTOR 3 X2200 #2 #1 #19 #22 #2 #1 #19 #22 J2-46 J2-38 DETECTOR 4 X2200 #2 #1 #19 #22 #2 #1 #19 #22 J2-47 J2-39 DETECTOR 5 X2200 #2 #1 #19 #22 #2 #1 #19 #22 J2-48 J2-40 35 D1 36 D2 37 D3 38 D4 39 D5 40 D6 41 D7 42 D
NOTE: DO NOT CONNECT THE X2200 "A" LEAD (#2/12) TO TERMINAL J2-34 (290 VDC).
X2200 DETECTOR FIRE ALARM PANEL 9 19 8 7 6 5 ALARM 4 3 + 24 VDC 2 – 1 PULSE OUT 18 COM FIRE2 SPARE 29 SPARE 28 17 N.O. FIRE2 27 16 N.C. FIRE2 26 END OF LINE DEVICE 4 15 COM FAULT1 N.O. FAULT1 24 VDC + 14 RS-485 A 24 13 RS-485 B 23 MAN Oi 22 12 24 VDC – 25 24 VDC – 11 21 oi TEST 3 WIRING NOTES: A2162 1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND THE CONTACTS ARE CLOSED.
STARTUP PROCEDURE EOL Resistors To ensure that the insulating material of the wiring terminal block will not be affected by the heat generated by EOL resistors, observe the following guidelines when installing the resistors. When installation of the equipment is complete, apply power and allow 20 to 30 minutes for the detector’s heated optics to reach equilibrium. Then perform one or more of the following tests: 1. Required EOL resistor power rating must be 5 watts minimum.
TROUBLESHOOTING 3. Press the SELECT button until the desired zone is displayed on the ZONE indicator on the controller front panel. Warning The sensor module (“front” half of the detector) contains no user serviceable components and should never be opened. The terminal compartment is the only part of the enclosure that should be opened by the user in the field. 4. Press and hold the TEST button. The DETECTOR/ ZONE display indicates the counts per second (cps) received from the detector.
MAINTENANCE GRASP VISOR AND REMOVE oi PLATE IMPORTANT Pe r i o d i c fl a m e p a t h i n s p e c t i o n s a re n o t recommended, since the product is not intended to be serviced and provides proper ingress protection to eliminate potential deterioration of the flamepaths. Warning The sensor module (“front” half of the detector) contains no user serviceable components and should never be opened. The terminal compartment is the only part of the enclosure that should be opened by the user in the field.
FEATURES • POWER UP TIME— Fault indication clears after 0.5 second; device is ready to indicate an alarm condition after 30 seconds. Responds to a fire in the presence of modulated blackbody radiation (i.e. heaters, ovens, turbines) without false alarm. • High speed capability. • Built-in data logging / event monitoring, up to 1500 events (up to 1000 general, 500 alarms). • Pulse output for compatibility with controller based systems. • Automatic, manual or magnetic optical integrity (oi) testing.
M ENCLOSURE MATERIAL— Copper-free aluminum (painted) or 316 stainless steel. NOTE Operational performance verified from -40°C to +75°C. Vibration— Conformance per FM 3260: 2000, MIL-STD 810C (Curve AW), NOTE An optional third party addressable module can only be used within the Ex d flameproof model unless the addressable module is component certified as Ex e for use within the Ex d e increased safety model. DIMENSIONS— See Figure 16.
replacement parts ORDERING INFORMATION The detector is not designed to be repaired in the field. If a problem should develop, refer to the Troubleshooting section. If it is determined that the problem is caused by an electronic defect, the device must be returned to the factory for repair. When ordering, please specify: X2200 UV Flame Detector with Pulse Output Refer to the X2200 Model Matrix for details. Q9033 mount is required: DEVICE REPAIR AND RETURN Q9033A for aluminum detectors only.
X2200 MODEL MATRIX MODEL X2200 X2200M DESCRIPTION UV Flame Detector UV Flame Detector with Molybdenum Tube TYPE MATERIAL A Aluminum S Stainless Steel (316) TYPE THREAD TYPE 4M 4 PORT, METRIC M25 4N 4 PORT, 3/4" NPT TYPE 15 OUTPUTS Relay and Pulse TYPE W APPROVAL AGENCY FM/CSA/ATEX/CE/IECEx TYPE CLASSIFICATION* 1 Division/Zone Ex d e 2 Division/Zone Ex d *Detectors are always Class I, Div. 1.
APPENDIX A FM Approval and Performance Report THE FOLLOWING ITEMS, FUNCTIONS AND OPTIONS DESCRIBE THE FM APPROVAL: • Explosion-proof for Class I, Div. 1, Groups B, C and D (T5) Hazardous (Classified) Locations per FM 3615. • Dust-ignition proof for Class II/III, Div. 1, Groups E, F and G (T5) Hazardous (Classified) Locations per FM 3615. • Nonincendive for Class I, Div. 2, Groups A, B, C and D (T3) Hazardous (Classified) Locations per FM 3611. • Nonincendive for Class II, Div.
FM Approval and Performance Report – Continued RESPONSE CHARACTERISTICS IN THE PRESENCE OF FALSE ALARM SOURCES Very High Sensitivity (Standard Mode) False Alarm Source Distance feet (m) Fire Source Distance feet (m) Typical Response Time (seconds) — 6-inch propane 10 (3) < 30 Sunlight, direct, modulated, reflected 6 kw heater, modulated & unmodulated 10 (3) 1 x 1 foot n-Heptane 75 (22.9) 1 250 w vapor lamp, modulated & unmodulated 3 (0.9) 1 x 1 foot n-Heptane 75 (22.
FM Approval and Performance Report – Continued FIELD of view Very High Sensitivity Fuel Size Distance feet (m) Horizontal (degrees) Typical Response Time (seconds) Vertical (degrees) Typical Response (seconds) Mode n-Heptane 1 x 1 foot 42.5 (13) +45 –45 2 2 +45 –30 2 2 Low Arc Methane 32 inch plume 50 (15.
FM Approval and Performance Report – Continued MODEL X2200M The X2200M uses a sensor that has a broader spectrum than the standard sensor. It is designed to detect fires with unusual chemistry such as black powder. Consult factory for usage recommendations. X2200M RESPONSE CHARACTERISTICS High Sensitivity Fuel Size Distance feet (m) Typical Response Time (seconds) Mode Black Powder 40 grams 10 (3) 0.
FM Approval and Performance Report – Continued X2200M FIELD of view High Sensitivity (Standard Mode) Fuel Size Distance feet (m) Horizontal (degrees) Typical Response Time (seconds) Vertical (degrees) Typical Response (seconds) Black Powder 40 grams 5 (1.5) +45 –45 0.1 0.1 +45 –30 0.1 0.1 5.
APPENDIX B CSA Approval PRODUCTS CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations Class I, Division 1, Groups B, C, and D (T5); Class II, Division 1, Groups E, F, and G (T5); Class I, Division 2, Groups A, B, C, and D (T3); Class II, Division 2, Groups F and G (T3); Class III; Enclosure Type 4X; Ultraviolet Flame Detector/Controller X2200 series, rated 18-30 Vdc, 2.5 Watts to 7.6 Watts. Relay contacts rated 5 Amps @ 30 Vdc. 5.
APPENDIX C ATEX / CE Approval EC-TYPE EXAMINATION CERTIFICATE DEMKO 02 ATEX 132195X Increased Safety Model Flameproof Model II 2 G Ex d e IIC T5–T6 Gb T6 (Tamb –50°C to +60°C) T5 (Tamb –50°C to +75°C) IP66. II 2 G Ex d IIC T5–T6 Gb T6 (Tamb –55°C to +60°C) T5 (Tamb –55°C to +75°C) IP66. 0539 FM ® APPROVED 0539 FM ® APPROVED Compliance with: EN 60079-0: 2009 EN 60079-1: 2007 EN 60079-7: 2007 EN / IEC 60529: 2001.
APPENDIX D IECEx Approval IECEx Certificate of Conformity DEMKO IECEx ULD 06.0018X Ex d e IIC T5-T6 Gb Ex d IIC T4-T6 Gb T6 (Tamb =–50°C to +60°C) or T6 (Tamb =–55°C to +60°C) T5 (Tamb =–50°C to +75°C) T5 (Tamb =–55°C to +75°C) IP66. IP66. Compliance with: IEC 60079-0: 2007 IEC 60079-1: 2007 IEC 60079-7: 2006 EN / IEC 60529: 2001. Installation instructions The field wiring connections in the terminal compartment are suitably certified and accepts wiring diameter from 14 AWG (2.
APPENDIX E VdS Schadenverhütung GmbH Approval VdS Performance per EN54-10, Certificate of Approval G-203083. EC-Certificate of Conformity 08 0786 – CPD – 20777 EN54-10 Flame detectors - Point detectors. SUBJECT MATTER OF THE APPROVAL UV Flame Detector Type X2200 for use in Automatic Fire Detection and Fire Alarm Systems. BASIS OF APPROVAL DIN EN 54, Part 10 (05/02) - Flame Detectors.
95-8552 Detector Electronics Corporation 6901 West 110th Street Minneapolis, MN 55438 USA X3301 Multispectrum IR Flame Detector PointWatch Eclipse® IR Combustible Gas Detector FlexVu® Universal Display w/ GT3000 Toxic Gas Detector Eagle Quantum Premier® Safety System T: 952.941.5665 or 800.765.3473 F: 952.829.8750 W: http://www.det-tronics.com E: det-tronics@det-tronics.