Specifications

20
X3300 Pulse Output Response Characteristics
Medium Sensitivity
Ave. Response Time, Sec.
Fuel Size
Distance
Connection to Connection to
Ft. (M)
R7404 Controller R7494 Controller
On Axis (0°) Off Axis (45°) On Axis (0°) Off Axis (45°)
Heptane 36 Sq. In. 40 4.5 10.6 5.3 11.4
(0.023 Sq. M.) (12)
OPTICAL FAULT:
The detector generated an optical fault in the presence of contamination on any single or combination of lens
surfaces verifying that the detector performs an optical integrity (o
i
) test for each sensor. Upon removal of the
contaminant the detector fault was cleared and the detector was verified to detect a fire.