Specifications
23
95-8517
FIELD OF VIEW:
Fuel Size Distance Horizontal Avg. Horiz. Response Time Vertical Avg. Vert. Response Time
(feet) (degrees) (seconds) (degrees) (seconds)
Gasoline 1 x 1 foot 150 +45 11.9 +45 8.5
–45 9.5 –30 6.0
Gasoline 1 x 1 foot 100 +45 3.5 +45 4.2
–45 4.0 –30 3.2
Diesel** 1 x 1 foot 100 +45 2.2 +45 2.1
–45 4.4 –30 2.8
Methanol 1 x 1 foot 110 +45 8.5 +45 9.5
–45 9.2 –30 4.3
Methane 30 inch plume 100 +45 1.9 +45 3.5
–45 4.3 –30 2.0
JP-5** 2 x 2 feet 180* +45 13.3 +45 10.4
–45 17.3 –30 5.0
JP-5** 2 x 2 feet 90 +45 2.9 +45 1.4
–45 4.1 –30 2.5
Office 18” x 16” x 10” 80 +45 6.4 +45 8.2
Paper 0.5 lb.
–45 9.8 –30 6.0
Corrugated
18” x 36” 80 +45 15.6 +45 14.7
Panel –45 12.2 –30 10.6
Very High Sensitivity
* Outdoor test condition.
** 10 second flame pre-burn from ignition.
Fuel Size Distance Horizontal Avg. Horiz. Response Time Vertical Avg. Vert. Response Time
(feet) (degrees) (seconds) (degrees) (seconds)
Gasoline 1 x 1 foot 75 +45 9.5 +45 6.4
–45 9.5 –30 5.4
Gasoline 1 x 1 foot 50 +45 3.8 +45 4.1
–45 3.8 –30 3.1
Diesel** 1 x 1 foot 60 +45 4.5 +45 5.5
–45 6.8 –30 2.1
Methanol 1 x 1 foot 45 +45 9.0 +45 9.8
–45 9.7 –30 6.6
Methane 30 inch plume 45 +45 4.4 +45 2.0
–45 0.9 –30 0.5
Methane 30 inch plume 40 +45 1.7 +45 3.4
–45 0.4 –30 1.4
JP-5** 2 x 2 feet 90 +45 2.9 +45 3.4
–45 8.1 –30 2.5
Medium Sensitivity
* Outdoor test condition.
** 10 second flame pre-burn from ignition.