Specifications

FlameB.1 Ultraviolet/Infrared

8/01/201152-1002-8.1
X5200 UVIR Flame Detector
X5200 UVIR Flame Detector (Spec Sheet: 90-1156) meets the most stringent requirements
worldwide with advanced high speed detection capabilities and immunity to extraneous
sources, combined with a superior mechanical design. The combination of Arc rejection
on the UV sensor and TDSA/Quick on the IR sensor make this detector the highest false
alarm immune UVIR available. The mounting arrangement allows the UV and IR sensors to
monitor the same hazardous location with a 90-degree cone of vision. When both sensors
simultaneously detect the presence of a flame, an alarm signal is generated. The detector
has Division and Zone explosion-proof ratings and is suitable for use in indoor and outdoor
applications.
The standard output configuration includes fire, fault, and auxiliary relays and RS-485
Modbus. Optional 4-20 mA or Eagle Quantum Premier output is also available. A model
with pulse output is available for easy retrofitting into existing Det-Tronics controller based
systems. A multi-color LED on the detector faceplate indicates detector status condition.
The X5200 housing is available in aluminum or stainless steel, with NEMA 4X and IP66/IP67
rating. Typical applications include: Hangars, munitions, petrochemical applications, and
turbines.
• Eagle Quantum Premier and Eagle Quantum compatible models available
• A new level of false alarm rejection
• Responds to a fire in the presence of modulated blackbody radiation (i.e., heaters, ovens,
turbines) without false alarm
• High-speed capability
• Optional HART output and AMS aware
• Microprocessor-controlled heated optics for increased resistance to moisture and ice
• Automatic, manual, or magnetic optical integrity (o
i
) testing
• Pulse output for compatibility with controller-based systems (optional)
• IECEx, FM, CSA, ATEX/CE
• EN 54 part 10 certified by VdS, LPCB
• Meets Construction Product Directive
• Integral wiring compartment for ease of installation
• Class A wiring per NFPA 72
• EMI, RFI, EMC Directive Compliant
• Built-in data logging / event monitoring
• Meets NFPA 33 Response requirement for under 0.5 second (when model selected)
• Models available with integral explosion proof camera option (xWatch)
CONTROLLERSACCESSORIES
DETECTOR
KEY: = Required
= Option
= Choice Required
X5200
Flame B.1
LON Output Pulse Output
Eagle Quantum
Premier
®
Systems B.1
R74XX
Controllers
Flame L.1
Q1201C Laser
Aimer / Cone of
Vision Tester
Flame K.2
Q1116 Air Shield
Q1118 Flange/Air
Q2000 Weather Shield
Flame K.3
Mounting
Hardware
Q9033
Flame K.5
HART 475
Communicator
Flame E.2