Specifications


DevicesC.1Systems 8/01/201152-1002-8.1
EQ3750 Addressable Smoke and Heat (ASH) Module
The EQP Addressable Smoke and Heat (ASH) Module (Instruction Manual: 95-8654) is designed
to expand the input and output capability of the Det-Tronics Eagle Quantum Premier
®
system.
The ASH is an interface device designed to provide continuous and automated fire protection.
It ensures system operation through continuous supervision of system inputs/outputs and Local
Operating Network/Signaling Line Circuit (LON/SLC) monitoring in the controller.
The ASH is located directly on the LON of the EQP system, with a loop of up to 64 addressable
devices tied into the ASH. This allows the EQP controller to annunciate a fire alarm from either its
own LON based I/O or from the ASH connected addressable smoke and heat detection loops.
System status can be determined using the troubleshooting procedures, Eagle Quantum Safety
System Software (S³), and the status indicators on the module.
• Expands the capabilities of the Det-Tronics Eagle Quantum Premier
®
system
• Class 1 Div. 2 locations combined with Zone 2 rated devices Type N
• Provides power and communications to 64 addressable devices
• Uses Apollo Discovery smoke and heat detectors
• ASH alarm and fault status are logged in the EQP controller
• LEDs for easy annunciation of power, faults and an active device on the loop
• Monitors single addressable devices
• Provides remote I/O capabilities via LON/SLC
• DIN rail mounting
• Plug-in wiring connectors
• RFI and EMI hardened
• Smoke detetors are globally approved (see product data sheets)
KEY:
= Required
= Option
= Choice Required
INPUTS
CONTROLLER
Detectors (Heat,
Smoke, CO,
Multi-sensor)
Manual Call
Points
Mini-module
I/O units
EQ3750
Addressable
Smoke & Heat
(ASH) Module
Sounders/
Beacon
EQ30XX
Controller
Horns
LON Communication Loop
OUTPUTS
Discovery Signal Loop