Specifications
DevicesC.7Systems 8/01/201152-1002-8.1
EQ3740IPM Intelligent Protection Module
EQ3740IPM Intelligent Protection Module (Spec Sheet: 90-1184). The IPM is designed
to provide continuous and automated local area fire protection, while monitoring system
operation through continuous supervision of its inputs/outputs (I/O) and Local Operating
Network/Signaling Line Circuit (LON/SLC) connection to the EQP controller. In addition, the
module contains a unique “embedded logic program” that if enabled during configuration,
allows the IPM to perform local area protection in a “back-up mode” without controller
interaction. The IPM utilizes eight pre-configured I/O channels to perform its monitoring,
supervision, and mitigation functions.
• Provides a pre-packaged single hazard protection solution to the Det-Tronics Eagle Quantum
Premier system
• Class 1 Div. 2 locations combined with Zone 2 rated devices Type N
• Eight independent, supervised I/O channels
• Individual channels have the pre-assigned functions necessary to deliver a single hazard
protection solution
• Supports two conventional “two-wire” smoke/heat zones with up to 15 devices per zone, and
the ability to reset latched zones. Does not require the use of “relay bases”
• Individual points are supervised in accordance with NFPA requirements for alarm/supervisory/
other input styles, notification/releasing outputs
• Panel or DIN rail mounting
• Meets the requirements of NFPA 72
ACCESSORIES
KEY:
= Required
= Option
= Choice Required
DETECTORS
CONTROLLER
Abort
Manual
Release
Supervisory
Device
Zone 1
Smoke and
Heat
EQ3740
Intelligent
Protection
Module
Release -1 Release -2
EQ30XX
Controller
Mounting Option
(Panel or DIN
Rail)
Bell
Zone 2
Smoke and
Heat
LON Communication Loop