Specifications

FlameB.6Ultraviolet/Infrared

8/01/2011 52-1002-8.1
Table B1 – X5200 Software Part Number Conguration Matrix
Dash
UV
Sensitivity
Arc
Rejection
IR
Sensitivity
Alarm Output IR
Qualications
Alarm Relay
Aux Output
Function
Aux Output IR
Qualications
Aux Relay Fault Relay
-001 High High High TDSA Only
De-Energized
Non-latching
Follows Alarm TDSA
Energized
Non-latching
Energized
Non-latching
-002 High Very High High TDSA or Quick
De-Energized
Non-latching
Follows Alarm TDSA or Quick
Energized
Non-latching
Energized
Non-latching
-003 High Off Very High TDSA or Quick
De-Energized
Non-latching
UV or IR TDSA
Energized
Non-latching
Energized
Non-latching
-004 High High Very High TDSA Only
De-Energized
Non-latching
Pre-Alarm TDSA
Energized
Non-latching
Energized
Non-latching
-005 Medium High High TDSA or Quick
De-Energized
Non-latching
UV or IR TDSA
Energized
Non-latching
Energized
Non-latching
-006 High High Low TDSA Only
De-Energized
Non-latching
Pre-Alarm TDSA
Energized
Non-latching
Energized
Non-latching
-007 High High High TDSA Only
De-Energized
Latching
Follows Alarm TDSA
De-energized
Latching
Energized
Non-latching
-008 High Very High High TDSA or Quick
De-Energized
Latching
Follows Alarm TDSA or Quick
De-energized
Latching
Energized
Non-latching
-009 High Off Very High TDSA or Quick
De-Energized
Latching
UV or IR TDSA
De-energized
Latching
Energized
Non-latching
-010 High High Very High TDSA Only
De-Energized
Latching
Pre-Alarm TDSA
De-energized
Latching
Energized
Non-latching
-011 Medium High High TDSA or Quick
De-Energized
Latching
UV or IR TDSA
De-energized
Latching
Energized
Non-latching
-012 High High Low TDSA Only
De-Energized
Latching
Pre-Alarm TDSA
De-energized
Latching
Energized
Non-latching
-013* High Off High TDSA or Quick
De-Energized
Non-Latching
Follows Alarm TDSA or Quick
Energized
Non-Latching
Energized
Non-latching
-014* High Off High TDSA or Quick
De-Energized
Latching
Follows Alarm TDSA or Quick
De-energized
Latching
Energized
Non-latching
-015 Very High Low Very High TDSA or Quick
De-Energized
Non-Latching
Follows Alarm TDSA or Quick
Energized
Non-Latching
Energized
Non-latching
-016 Very High Low Very High TDSA or Quick
De-Energized
Latching
Follows Alarm TDSA or Quick
De-energized
Latching
Energized
Non-latching
-019 Very High Off Very High TDSA or Quick
De-Energized
Non-Latching
UV or IR TDSA
Energized
Non-Latching
Energized
Non-latching
-021 Very High Off Very High TDSA or Quick
De-Energized
Latching
Follows Alarm TDSA or Quick
De-energized
Latching
Energized
Non-latching
*Available only on the X5200M model.
ARC = Arc Rejection. An algorithm that prevents false alarms from transient UV sources.
TDSA = “Time Domain Signal Analysis” signal processing algorithm for superior IR false alarm rejection.
Quick = Signal processing for explosive IR events.
Application Recommendations
These are typical industry application settings.
They may not be applicable to all installations. Contact factory for application guidance.
General Duty 001
Offshore 001
Compressor 002
High Speed 003
Hangar 004
Automotive 005
Turbine 006
NOTE: Latching relays cannot be used in voted systems.