Specifications

FlameD.6Ultraviolet

8/01/2011 52-1002-8.1
Table D1 – X2200 Software Part Number Conguration Matrix
Dash
UV
Sensitivity
Arc
Rejection
Alarm Relay
Aux Output
Function
Aux Relay Fault Relay
-001 High High
De-Energized
Non-latching
Follows Alarm
Energized
Non-latching
Energized
Non-latching
-002 High Very High
De-Energized
Non-latching
Follows Alarm
Energized
Non-latching
Energized
Non-latching
-003 High Off
De-Energized
Non-latching
Pre-Alarm
Energized
Non-latching
Energized
Non-latching
-005 Medium High
De-Energized
Non-latching
Follows Alarm
Energized
Non-latching
Energized
Non-latching
-006 High High
De-Energized
Non-latching
Pre-Alarm
Energized
Non-latching
Energized
Non-latching
-007 High High
De-Energized
Latching
Follows Alarm
De-energized
Latching
Energized
Non-latching
-008 High Very High
De-Energized
Latching
Follows Alarm
De-energized
Latching
Energized
Non-latching
-009 High Off
De-Energized
Latching
Pre-Alarm
De-energized
Latching
Energized
Non-latching
-010 Medium High
De-Energized
Latching
Follows Alarm
De-energized
Latching
Energized
Non-latching
011 High High
De-Energized
Latching
Pre-Alarm
De-energized
Latching
Energized
Non-latching
-013* High Off
De-Energized
Non-latching
Follows Alarm
Energized
Non-latching
Energized
Non-latching
-014* High Off
De-Energized
Latching
Follows Alarm
De-energized
Latching
Energized
Non-latching
-015 Very High Low
De-Energized
Non-latching
Follows Alarm
Energized
Non-latching
Energized
Non-latching
-016 Very High Low
De-Energized
Latching
Follows Alarm
De-energized
Latching
Energized
Non-latching
-017 Very High Off
De-Energized
Non-latching
Pre-Alarm
Energized
Non-latching
Energized
Non-latching
-018 Very High Off
De-Energized
Non-latching
Follows Alarm
Energized
Non-latching
Energized
Non-latching
-019 Very High Off
De-Energized
Non-latching
Pre-Alarm
De-Energized
Non -latching
Energized
Non-latching
*Available only on the X2200M model.
ARC = Arc Rejection. An algorithm that prevents false alarms from transient UV sources.
Application Recommendations
These are typical industry application settings.
They may not be applicable to all installations. Contact factory for application guidance.
General Duty 001
Offshore 001
Compressor 002
High Speed 003
Automotive 005
Turbine 006
NOTE: Latching relays cannot be used in voted systems.