Specifications
OPTICAL FAULT:
The detector generated an optical fault in the presence of contamination on any single or combination of lens
surfaces verifying that the detector performs an optical integrity (o
i
) test for each sensor. Upon removal of the
contaminant the detector fault was cleared and the detector was verified to detect a fire.
RESPONSE CHARACTERISTICS IN THE PRESENCE OF FALSE ALARM SOURCES:
17
95-8502
False Alarm Source Distance Fire Source Distance Average Response Time
(feet) (feet) (seconds)
Sunlight, direct, modulated, reflected — 6-inch propane 6 < 4
Vibration N/A 6-inch propane 6 < 10
Radio frequency interference 1 6-inch propane 12 < 1
Arc welding 40 1 x 1 foot gasoline 40 3.1
6 kw heater, modulated 100 1 x 1 foot gasoline 100 1.9
6 kw heater, unmodulated 10 1 x 1 foot gasoline 100 5.3
250 w vapor lamp, modulated 3 1 x 1 foot gasoline 100 2.7
300 w incandescent lamp, modulated 3 1 x 1 foot gasoline 100 3.6
500 w unshielded quartz halogen lamp, modulated 8 1 x 1 foot gasoline 100 2.7
1500 w electric radiant heater, modulated 10 1 x 1 foot gasoline 100 4.2
Two 34 w fluorescent lamps, modulated 3 1 x 1 foot gasoline 100 1.7
Very High Sensitivity
False Alarm Source Distance Fire Source Distance Average Response Time
(feet) (feet) (seconds)
Sunlight, direct, modulated, reflected — 6-inch propane 6 < 4
Vibration* N/A N/A N/A N/A
Radio frequency interference 1 6-inch propane 6 < 1
Arc welding 10 1 x 1 foot gasoline 10 0.2
6 kw heater, modulated 100 1 x 1 foot gasoline 100 5.0
6 kw heater, unmodulated 10 1 x 1 foot gasoline 100 10.7
250 w vapor lamp, modulated 3 1 x 1 foot gasoline 100 7.1
300 w incandescent lamp, modulated 3 1 x 1 foot gasoline 100 9.6
500 w unshielded quartz halogen lamp, modulated 8 1 x 1 foot gasoline 100 6.3
1500 w electric radiant heater, modulated 10 1 x 1 foot gasoline 90 6.4
Two 34 w fluorescent lamps, modulated 3 1 x 1 foot gasoline 100 4.6
Medium Sensitivity
* Fire was verified with very high sensitivity only.