User Manual

22 95-85769.2
FM Approval and Performance Report – Continued
RESPONSE CHARACTERISTICS
Very High Sensitivity
Fuel Size/Flow Rate
Distance
feet (m)
Average Response
Time (seconds)**
Hydrogen 30 inch plume/100 SLPM* 100 (30.5) 3
Methanol 1 x 1 foot 70 (21.3) 5
* Standard Liters Per Minute (Standard conditions defined as +25°C and 14.696 PSIA).
** Add 2 seconds for EQP model.
High Sensitivity
Fuel Size/Flow Rate
Distance
feet (m)
Average Response
Time (seconds)**
Hydrogen 30 inch plume/100 SLPM* 75 (22.9) 3
Methanol 1 x 1 foot 52.5 (16.0) 2
* Standard Liters Per Minute (Standard conditions defined as +25°C and 14.696 PSIA).
** Add 2 seconds for EQP model.
Medium Sensitivity
Fuel Size/Flow Rate
Distance
feet (m)
Average Response
Time (seconds)**
Hydrogen 30 inch plume/100 SLPM* 50 (15.2) 4
Methanol 1 x 1 foot 35 (10.7) 4
* Standard Liters Per Minute (Standard conditions defined as +25°C and 14.696 PSIA).
** Add 2 seconds for EQP model.
Low Sensitivity
Fuel Size/Flow Rate
Distance
feet (m)
Average Response
Time (seconds)**
Hydrogen 30 inch plume / 100 SLPM* 25 (7.6) 3
Methanol 1 x 1 foot 17.5 (5.3) 3
* Standard Liters Per Minute (Standard conditions defined as +25°C and 14.696 PSIA).