User Manual

26 95-85769.2
Low Sensitivity
False Alarm Source
Distance
feet (m)
Fire Source
Distance
feet (m)
Average Response
Time (seconds)**
Sunlight, direct, unmodulated*
Hydrogen @ 100 SLPM 25 (7.6)
3.5
Sunlight, direct, modulated*
Hydrogen @ 200 SLPM
10 (3.0)
3.5
Sunlight, reflected, unmodulated*
Hydrogen @ 100 SLPM 25 (7.6)
2.5
Sunlight, reflected, modulated*
Hydrogen @ 100 SLPM 15 (4.6)
2.5
Arc welding, steady, #7014 5 (1.5) Hydrogen @ 100 SLPM 25 (7.6)
3
Arc welding, modulated, #7014 5 (1.5) Hydrogen @ 100 SLPM
17.5 (5.3)
2.5
70 w sodium vapor, unmodulated 3 (0.9) Hydrogen @ 100 SLPM
25 (7.6)
3
70 w sodium vapor, modulated 3 (0.9) Hydrogen @ 100 SLPM
25 (7.6)
2
250 w vapor lamp, unmodulated 3 (0.9) Hydrogen @ 100 SLPM
25 (7.6)
3
250 w vapor lamp, modulated 3 (0.9) Hydrogen @ 100 SLPM
17.5 (5.3)
2
300 w incandescent lamp, unmodulated 3 (0.9) Hydrogen @ 100 SLPM
25 (7.6)
3
300 w incandescent lamp, modulated 3 (0.9) Hydrogen @ 100 SLPM
15 (4.6)
2
500 w shielded quartz halogen lamp, unmodulated 5 (1.5) Hydrogen @ 100 SLPM
25 (7.6)
3.5
500 w shielded quartz halogen lamp, modulated 5 (1.5) Hydrogen @ 100 SLPM
10 (3.0)
2.5
1500 w electric radiant heater, unmodulated 3 (0.9) Hydrogen @ 100 SLPM
25 (7.6)
2
1500 w electric radiant heater, modulated 3 (0.9) Hydrogen @ 100 SLPM
10 (3.0)
2
Two 34 w fluorescent lamps, unmodulated 2 (0.6) Hydrogen @ 100 SLPM
25 (7.6)
3
Two 34 w fluorescent lamps, modulated 2 (0.6) Hydrogen @ 100 SLPM
25 (7.6)
3.5
* Outdoor test conditions.
** Add 2 seconds for EQP model.
FM Approval and Performance Report – Continued