User Manual
28 95-85769.2
0°
15°
45°
15°
30°
30°
DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45° FROM HORIZONTAL.
0°
15°
30°
45°
15°
30°
45°
50 (15.2)
45 (13.7)
40 (12.2)
35 (10.7)
30 (9.1)
25 (7.6)
20 (6.1)
15 (4.6)
10 (3)
5 (1.5)
5 (1.5)
10 (3)
15 (4.6)
20 (6.1)
25 (7.6)
30 (9.1)
35 (10.7)
40 (12.2)
45 (13.7)
50 (15.2)
Field of View at Indicated Distance in Feet (m) for Hydrogen at
Medium Sensitivity (30 inch plume, with 100 SLPM ow rate)
0°
15°
15°
30°
45°
30°
45°
35 (10.7)
30 (9.1)
25 (7.6)
20 (6.1)
15 (4.6)
10 (3)
5 (1.5)
5 (1.5)
10 (3)
15 (4.6)
20 (6.1)
25 (7.6)
30 (9.1)
35 (10.7)
0°
15°
45°
15°
30°
30°
DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45° FROM HORIZONTAL.
Field of View at Indicated Distance in Feet (m) for
Methanol at Medium Sensitivity (1 x 1 ft)
0°
15°
15°
30°
45°
30°
45°
17.5 (5.3)
15 (4.6)
10 (3)
5 (1.5)
5 (1.5)
10 (3)
15 (4.6)
17.5 (5.3)
0
°
15
°
45
°
15
°
30
°
30
°
DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45° FROM HORIZONTAL.
FM Approval and Performance Report – Continued
0°
15°
30°
45°
15°
30°
45°
0°
15°
45°
15°
30°
30°
DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45° FROM HORIZONTAL.
25 (7.6)
20 (6.1)
15 (4.6)
10 (3)
5 (1.5)
5 (1.5)
10 (3)
15 (4.6)
20 (6.1)
25 (7.6)
Field of View at Indicated Distance in Feet for Hydrogen at
Low Sensitivity (30 inch plume, with 100 SLPM ow rate)
NOTE
FM Approvals minimum requirements are response distance measurements at 0° (on axis) and the limits of
the eld of view. These high resolution eld of view diagrams show the measured response distances at all the
indicated angles in the horizontal plane.
Field of View at Indicated Distance in Feet for
Methanol at Low Sensitivity (1 x 1 ft)