NOTE
Operational performance veried from –40°C to +75°C.
NOTE
An optional third party addressable module can only be used within the Ex d ameproof model unless the
addressable module is component certied as Ex e for use within the Ex d e increased safety model.
NOTE
Refer to “EOL Resistors” section for installation details. All cable entry devices and blanking elements shall be
certied to “E-generation” or “ATEX” standards, in type of explosion protection increased safety “e” or ameproof
enclosure “d” (as applicable), suitable for the conditions of use and correctly installed. They shall maintain the
degree of ingress protection IP66/IP67 for the apparatus. Unused conduit entries shall be closed with suitable
blanking elements.
NOTE
For ATEX installations, the X3302 detector housing must be electrically connected to earth ground.
The following accessories are ATEX approved for use with the X3302 Flame Detector:
Part Number Description
007290-001
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
007290-002
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
011385-001
Q9033 Collar Attachment