Flame, Gas, and Systems Product Catalog September 1, 2008 to August 31, 2009 Detector Electronics Corporation 6901 West 110th Street Minneapolis, MN 55438 USA ph: 952.941.5665 or 800.765.3473 fax: 952.829.8750 www.det-tronics.com detronics@detronics.
Product Catalog September 1, 2008 to August 31, 2009 © 2008 Detector Electronics Corporation. All rights reserved. DET-TRONICS and DET-TRONICS logo, ProtectIR, xWatch, and Eagle Quantum Premier are registered trademarks or trademarks of Detector Electronics Corporation in the United States, other countries or both. Other company, product, or service names may be trademarks or service marks of others.
TABLE OF CONTENTS FLAME X3301 Protect•ir® Multispectrum Infrared Flame Detector.....................................................................A.1 X3301 Model Matrix....................................................................................................................................................................................... A.2 X3301 Protect•ir Multispectrum Infrared Flame Detector ...................................................................................................
TABLE OF CONTENTS FLAME CONTINUED… X7050 xWatch™ Explosion-Proof Surveillance Camera .......................................................................... F.1 X7050 Model Matrix....................................................................................................................................................................................... F.2 X7050 xWatch Camera ..........................................................................................................................
TABLE OF CONTENTS FLAME CONTINUED… Output Devices for R7XXX Controllers...................................................................................................K.10 R1425 Rack Mount Detonator Module for the R7404 Controller................................................................................................................. K.10 R6007 Auxiliary Relay Output Assembly...........................................................................................................................
TABLE OF CONTENTS GAS PointWatch Eclipse® PIRECL Infrared Hydrocarbon Gas Detector..........................................................A.1 ® PointWatch Eclipse Model Matrix ................................................................................................................................................................ A.2 Typical PIRECL Customer Proposal ........................................................................................................................................
TABLE OF CONTENTS GAS CONTINUED… PIRVOL Infrared Hydrocarbon Gas Process Monitor .............................................................................A.25 PIRVOL Model Matrix.................................................................................................................................................................................. A.26 PIRVOL Model Listings ............................................................................................................................
TABLE OF CONTENTS GAS CONTINIUED… C706X Calibration Gas Kits ....................................................................................................................C.11 Toxic Calibration Gas Kits ...........................................................................................................................................................................C.12 Toxic Calibration Gas Kit Replacement Parts ..................................................................................
TABLE OF CONTENTS SYSTEMS Eagle Quantum Premier® System .............................................................................................................A.1 Eagle Quantum Premier® Controller • EQ3001 .........................................................................................B.1 EQ3001 Controller Model Matrix ................................................................................................................................................................... B.
TABLE OF CONTENTS SYSTEMS CONTINIUED… Heat Detectors (Explosion-Proof)...........................................................................................................C.17 Smoke Detectors and Heat Detectors (General Use)............................................................................C.17 Manual Call Stations ...............................................................................................................................C.18 EQ3720RM Relay Module ..........................
TABLE OF CONTENTS RERERENCES Abbreviations ............................................................................................................................................A.1 Product Life Cycle Definitions ..................................................................................................................A.3 Ordering Information .................................................................................................................................A.4 Ordering Information..
TABLE OF CONTENTS FLAME X3301 Protect•ir® Multispectrum Infrared Flame Detector.....................................................................A.1 X3301 Model Matrix....................................................................................................................................................................................... A.2 X3301 Protect•ir Multispectrum Infrared Flame Detector ...................................................................................................
TABLE OF CONTENTS FLAME CONTINUED… X7050 xWatch™ Explosion-Proof Surveillance Camera .......................................................................... F.1 X7050 Model Matrix....................................................................................................................................................................................... F.2 X7050 xWatch Camera ..........................................................................................................................
TABLE OF CONTENTS FLAME CONTINUED… Output Devices for R7XXX Controllers...................................................................................................K.10 R1425 Rack Mount Detonator Module for the R7404 Controller................................................................................................................. K.10 R6007 Auxiliary Relay Output Assembly...........................................................................................................................
MULTISPECTRUM INFRARED X3301 Protect•ir® Multispectrum Infrared Flame Detector X3301 Protect•ir Multispectrum Infrared Flame Detector (Spec Sheet: 90-1143, 90-1144, 90-1190) establishes the benchmark in multiple-fuel fire detection performance and false alarm rejection. The detector utilizes advanced signal processing algorithms supported by an embedded 32-bit microprocessor to provide continuous protection in the presence of false alarm sources and environments with infrared radiation present.
MULTISPECTRUM INFRARED X3301 Model Matrix MODEL DESCRIPTION X3301 Multispectrum IR Flame Detector TYPE MATERIAL A Aluminum S Stainless Steel (316) TYPE THREAD TYPE 3M 3 Port, Metric M25 3N 3 Port, 3/4" NPT 4M 4 Port, Metric M25 4N 4 Port, 3/4" NPT TYPE OUTPUTS 11 Relay 13 Relay and 4-20 mA 14 Eagle Quantum Premier (EQP) 15 Relay and Pulse 16 Addressable Module Only (third-party type) 21 Relay - Automotive 22 EQP - Automotive 23 HART, Relay, and 4-20 mA 33 Relay and 4-20 mA / NTSC (xWatch) 34 Eagle Quantum P
MULTISPECTRUM INFRARED X3301 Protect•ir Multispectrum Infrared Flame Detector Model Part Number * X3301A4N11W1 X3301A4M11W1 X3301S4N11W1 X3301S4M11W1 008100-XXX 008101-XXX 008102-XXX 008103-XXX AL AL 316 SS 316 SS 3/4 NPT M25 3/4 NPT M25 Relay Relay Relay Relay X3301A4N11W2 X3301A4M11W2 X3301S4N11W2 X3301S4M11W2 008104-XXX 008105-XXX 008106-XXX 008107-XXX AL AL 316 SS 316 SS 3/4 NPT M25 3/4 NPT M25 Relay Relay Relay Relay X3301A4N13W1 X3301A4M13W1 X3301S4N13W1 X3301S4M13W1 008108-XXX 008109-XXX
MULTISPECTRUM INFRARED X3301 Protect•ir Multispectrum Infrared Flame Detector – EQP Model Part Number Material Threads Output EEx de X3301A4N14W1 X3301A4M14W1 X3301S4N14W1 X3301S4M14W1 008124-001 008125-001 008126-001 008127-001 AL AL 316 SS 316 SS 3/4 NPT M25 3/4 NPT M25 EQP EQP EQP EQP X X X X X3301A4N14W2 X3301A4M14W2 X3301S4N14W2 X3301S4M14W2 008128-001 008129-001 008130-001 008131-001 AL AL 316 SS 316 SS 3/4 NPT M25 3/4 NPT M25 EQP EQP EQP EQP X3301A4N14W1 X3301A4M14W1 X3301S4N14W1 X330
MULTISPECTRUM INFRARED X3301 Protect•ir Multispectrum Infrared Flame Detector - China X X X X CCCF China X X X X Ship Weight 6 lb (2.75 kg) 6 lb (2.75 kg) 10 lb (4.54 kg) 10 lb (4.54 kg) Relay/4-20 mA Relay/4-20 mA Relay/4-20 mA Relay/4-20 mA X X X X X X X X 6 lb (2.75 kg) 6 lb (2.75 kg) 10 lb (4.54 kg) 10 lb (4.54 kg) 3/4 NPT M25 3/4 NPT M25 EQP EQP EQP EQP X X X X X X X X 6 lb (2.75 kg) 6 lb (2.75 kg) 10 lb (4.54 kg) 10 lb (4.54 kg) 3/4 NPT M25 Automotive Automotive X X X X 6 lb (2.
MULTISPECTRUM INFRARED X3301 Protect•ir Multispectrum Infrared Flame Detector / xWatch Camera X3301A3N33A2 X3301A3M33A2 X3301S3N33A2 X3301S3M33A2 009500-XXX 009501-XXX 009502-XXX 009503-XXX AL AL SS SS 3/4 NPT M25 3/4 NPT M25 Relay/4-20 Relay/4-20 Relay/4-20 Relay/4-20 NTSC NTSC NTSC NTSC X X X X X X X X Ship Weight 9 lb (4.1 kg) 9 lb (4.1 kg) 14 lb (6.4 kg) 14 lb (6.
MULTISPECTRUM INFRARED Table A1 - X3301 Software Part Number Configuration Matrix Dash Sensitivity Alarm Relay De-energized -001 Medium Non-latching De-energized -002 Very High Non-latching De-energized -004 Low Non-latching De-energized -005* Medium Non-latching De-energized -006 Medium Latching De-energized -007 Very High Latching De-energized -009 Low Latching De-energized -034 Medium Non-Latching De-energized -035 Very High Non-Latching Aux Relay Energized Non-latching Energized Non-latching Energized
MULTISPECTRUM INFRARED NOTES 9/01/2008 52-1002-5 Multispectrum Infrared Flame A.
MULTISPECTRUM INFRARED X3302 Multispectrum Infrared Flame Detector X3302 Multispectrum Infrared Flame Detector (Spec Sheet: 90-1185) provides a solid cone of vision for hydrogen fire detection coupled with superior false alarm rejection. The detector utilizes advanced signal processing algorithms supported by an embedded 32-bit microprocessor to provide continuous protection in the presence of false alarm sources and environments with infrared radiation present.
MULTISPECTRUM INFRARED X3302 Model Matrix MODEL DESCRIPTION X3302 Multispectrum IR Flame Detector TYPE MATERIAL A Aluminum S Stainless Steel (316) TYPE THREAD TYPE 3M 3 Port, Metric M25 3N 3 Port, 3/4" NPT 4M 4 Port, Metric M25 4N 4 Port, 3/4" NPT OUTPUTS TYPE 13 Relay and 4-20 mA 14 Eagle Quantum Premier (EQP) 15 Relay and Pulse 16 Addressable Module Only (third-party type) 23 HART, Relay, and 4-20 mA 33 Relay and 4-20 mA / NTSC (xWatch) 34 Eagle Quantum Premier / NTSC (xWatch) 43 Relay and 4-20 mA / PAL (
MULTISPECTRUM INFRARED X3302 Multispectrum Infrared Flame Detector Model Part Number* Material Threads Output X3302A4N13W1 X3302A4M13W1 X3302S4N13W1 X3302S4M13W1 009008-XXX 009009-XXX 009010-XXX 009011-XXX AL AL 316 SS 316 SS 3/4 NPT M25 3/4 NPT M25 Relay/4-20 mA Relay/4-20 mA Relay/4-20 mA Relay/4-20 mA X3302A4N13W2 X3302A4M13W2 X3302S4N13W2 X3302S4M13W2 009012-XXX 009013-XXX 009014-XXX 009015-XXX AL AL 316 SS 316 SS 3/4 NPT M25 3/4 NPT M25 Relay/4-20 mA Relay/4-20 mA Relay/4-20 mA Relay/4-20
MULTISPECTRUM INFRARED X3302 Multispectrum Infrared Flame Detector / xWatch Camera Output Video EEx d FM/CSA 3/4" NPT M25 3/4" NPT M25 Relay/4-20 Relay/4-20 Relay/4-20 Relay/4-20 NTSC NTSC NTSC NTSC X X X X X X X X Ship Weight 9 lb (4.1 kg) 9 lb (4.1 kg) 14 lb (6.4 kg) 14 lb (6.4 kg) AL AL SS SS 3/4" NPT M25 3/4" NPT M25 Relay/4-20 Relay/4-20 Relay/4-20 Relay/4-20 PAL PAL PAL PAL X X X X X X X X 9 lb (4.1 kg) 9 lb (4.1 kg) 14 lb (6.4 kg) 14 lb (6.
SINGLE FREQUENCY INFRARED X9800 IR Flame Detector The X9800 IR Flame Detector (Spec Sheet: 90-1160) meets the most stringent requirements worldwide with advanced detection capabilities and immunity to extraneous sources, combined with a superior mechanical design. The detector is equipped with dual signal processing (high speed operation) and automatic/magnetic manual oi test capability. The detector has Division and Zone explosion-proof ratings and is suitable for use in indoor and outdoor applications.
SINGLE FREQUENCY INFRARED X9800 Model Matrix MODEL DESCRIPTION X9800 Single Frequency IR Flame Detector TYPE MATERIAL A Aluminum S Stainless Steel (316) TYPE THREAD TYPE 3M 3 Port, Metric M25 3N 3 Port, 3/4" NPT 4M 4 Port, Metric M25 4N 4 Port, 3/4" NPT TYPE OUTPUTS 11 Relay 13 Relay and 4-20 mA 14 Eagle Quantum Premier 15 Relay and Pulse 16 Addressable Module Only (third-party type) 33 Relay and 4-20 mA / NTSC (xWatch) 34 Eagle Quantum Premier / NTSC (xWatch) 43 Relay and 4-20 mA / PAL (xWatch) 44 Eagle Qu
SINGLE FREQUENCY INFRARED X9800 Single Frequency IR Flame Detector Model Part Number * Material Threads Output EEx de EEx d X9800A4N11W1 X9800A4M11W1 X9800S4N11W1 X9800S4M11W1 008700-XXX 008701-XXX 008702-XXX 008703-XXX AL AL 316 SS 316 SS 3/4 NPT M25 3/4 NPT M25 Relay Relay Relay Relay X9800A4N11W2 X9800A4M11W2 X9800S4N11W2 X9800S4M11W2 008704-XXX 008705-XXX 008706-XXX 008707-XXX AL AL 316 SS 316 SS 3/4 NPT M25 3/4 NPT M25 Relay Relay Relay Relay X9800A4N13W1 X9800A4M13W1 X9800S4N13W1 X9800
SINGLE FREQUENCY INFRARED X9800 Single Frequency IR Flame Detector - Russia Model Part Number* Material Threads Output EEx de EEx d X9800A4M11R1 X9800S4M11R1 X9800A4M11R2 X9800S4M11R2 VNIIPO/ VNIIFTRI Russia X X X X Ship Weight 008740-XXX AL M25 Relay X 6 lb (2.75 kg) 008741-XXX X 10 lb (4.54 kg) 316 SS M25 Relay 008742-XXX AL M25 Relay X 6 lb (2.75 kg) 316 SS M25 Relay X 10 lb (4.54 kg) 008743-XXX X9800A4M13R1 008744-XXX AL M25 Relay/4-20 mA X X 6 lb (2.75 kg) X9800S4M13R1 008745-XXX X X 10 lb (4.
SINGLE FREQUENCY INFRARED Table B1 - X9800 Software Part Number Configuration Matrix Dash IR Sensitivity Alarm Output IR Qualification Alarm Relay Aux Output Function Aux Output IR Qualification Aux Relay Fault Relay -001 High TDSA De-Energized Non-latching Follows Alarm TDSA Energized Non-latching Energized Non-latching -002 High TDSA or Quick De-Energized Non-latching Follows Alarm TDSA or Quick Energized Non-latching Energized Non-latching -003 Very High TDSA or Quick De-Energi
SINGLE FREQUENCY INFRARED NOTES 9/01/2008 52-1002-5 Single Frequency Infrared Flame B.
ULTRAVIOLET/INFRARED X5200 UVIR Flame Detector X5200 UVIR Flame Detector (Spec Sheet: 90-1156) meets the most stringent requirements worldwide with advanced high speed detection capabilities and immunity to extraneous sources, combined with a superior mechanical design. The combination of Arc rejection on the UV sensor and TDSA/Quick on the IR sensor make this detector the highest false alarm immune UVIR available.
ULTRAVIOLET/INFRARED X5200 Model Matrix MODEL X5200 DESCRIPTION UVIR Flame Detector X5200M+ UVIR Flame Detector with Molybdenum Tube TYPE MATERIAL A Aluminum S Stainless Steel (316) TYPE THREAD TYPE 3M 3 Port, Metric M25 3N 3 Port, 3/4" NPT 4M 4 Port, Metric M25 4N 4 Port, 3/4" NPT TYPE OUTPUTS 11 Relay 13 Relay and 4-20 mA 14 Eagle Quantum Premier 24 Eagle Quantum 15 Relay and Pulse 16 Addressable Module Only (third-party type) 33 Relay and 4-20 mA / NTSC (xWatch) 34 Eagle Quantum Premier / NTSC (xWatch
ULTRAVIOLET/INFRARED X5200 UVIR Flame Detector Model Part Number * Material Threads Output EEx de EEx d X5200A4N11W1 X5200A4M11W1 X5200S4N11W1 X5200S4M11W1 008500-XXX 008501-XXX 008502-XXX 008503-XXX AL AL 316 SS 316 SS 3/4 NPT M25 3/4 NPT M25 Relay Relay Relay Relay X5200A4N11W2 X5200A4M11W2 X5200S4N11W2 X5200S4M11W2 008504-XXX 008505-XXX 008506-XXX 008507-XXX AL AL 316 SS 316 SS 3/4 NPT M25 3/4 NPT M25 Relay Relay Relay Relay X5200A4N13W1 X5200A4M13W1 X5200S4N13W1 X5200S4M13W1 008508-XXX 0
ULTRAVIOLET/INFRARED X5200 UVIR Flame Detector - China Model Part Number Material Threads Output X5200A4N11Y2 X5200A4M11Y2 X5200S4N11Y2 X5200S4M11Y2 008580-001 008581-001 008582-001 008583-001 AL AL 316 SS 316 SS 3/4 NPT M25 3/4 NPT M25 Relay Relay Relay Relay X5200A4N13Y2 X5200A4M13Y2 X5200S4N13Y2 X5200S4M13Y2 008584-001 008585-001 008586-001 008587-001 AL AL 316 SS 316 SS 3/4 NPT M25 3/4 NPT M25 Relay/4-20 mA Relay/4-20 mA Relay/4-20 mA Relay/4-20 mA X X X X CCCF China X X X X 6 lb (2.
ULTRAVIOLET/INFRARED X5200M UVIR Flame Detector - Moly Model Part Number Material Threads Output EEx de EEx d X5200MA4N13W1 X5200MA4M13W1 X5200MS4N13W1 X5200MS4M13W1 008540-013 008541-013 008542-013 008543-013 AL AL 316 SS 316 SS 3/4 NPT M25 3/4 NPT M25 Relay/4-20 mA Relay/4-20 mA Relay/4-20 mA Relay/4-20 mA X5200MA4N13W2 X5200MA4M13W2 X5200MS4N13W2 X5200MS4M13W2 008544-013 008545-013 008546-013 008547-013 AL AL 316 SS 316 SS 3/4 NPT M25 3/4 NPT M25 Relay/4-20 mA Relay/4-20 mA Relay/4-20 mA Re
ULTRAVIOLET/INFRARED Table C1 - X5200 Software Part Number Configuration Matrix Dash UV Sensitivity Arc Rejection IR Sensitivity Alarm Output IR Qualifications -001 High High High TDSA Only -002 High Very High High TDSA or Quick -003 High Off Very High TDSA or Quick -004 High High Very High TDSA Only -005 Medium High High TDSA or Quick -006 High High Low TDSA Only -007 High High High TDSA Only -008 High Very High High TDSA or Quick -009 High Off Very High TDS
ULTRAVIOLET X2200 UV Flame Detector X2200 UV Flame Detector (Spec Sheet: 90-1157) meets the most stringent requirements worldwide with advanced signal processing and immunity to extraneous sources, combined with high speed capability. The detector is equipped with both automatic and manual oi test capability. The detector has Division and Zone explosion-proof ratings and is suitable for use in a variety of applications.
ULTRAVIOLET X2200 Model Matrix MODEL DESCRIPTION X2200 UV Flame Detector UV Flame Detector X2200M+ w/Molybdenum Tube TYPE MATERIAL A Aluminum S Stainless Steel (316) TYPE THREAD TYPE 3M 3 Port, Metric M25 3N 3 Port, 3/4" NPT 4M 4 Port, Metric M25 4N 4 Port, 3/4" NPT TYPE OUTPUTS 11 Relay 13 Relay and 4-20 mA 14 Eagle Quantum Premier 24 Eagle Quantum 15 Relay and Pulse 16 Addressable Module Only (third-party type) 33 Relay and 4-20 mA / NTSC (xWatch) 34 Eagle Quantum Premier / NTSC (xWatch) 43 Relay and 4-20
ULTRAVIOLET X2200 UV Flame Detector Model Part Num ber * Material Threads Output X2200A4N11W1 X2200A4M11W 1 X2200S4N11W1 X2200S4M11W 1 008300-XXX 008301-XXX 008302-XXX 008303-XXX AL AL 316 SS 316 SS 3/4 NPT M25 3/4 NPT M25 Relay Relay Relay Relay X2200A4N11W2 X2200A4M11W 2 X2200S4N11W2 X2200S4M11W 2 008304-XXX 008305-XXX 008306-XXX 008307-XXX AL AL 316 SS 316 SS 3/4 NPT M25 3/4 NPT M25 Relay Relay Relay Relay X2200A4N13W1 X2200A4M13W 1 X2200S4N13W1 X2200S4M13W 1 008308-XXX 008309-XXX 008310-
ULTRAVIOLET X2200 UV Flame Detector - Russia Model Part Number * Material Threads Output EEx de EEx d X2200A4M11R1 X2200S4M11R1 X2200A4M11R2 X2200S4M11R2 VNIIPO/ VNIIFTRI Russia X X X X Ship Weight 008364-XXX AL M25 Relay X 6 lb (2.75 kg) 316 SS M25 Relay X 10 lb (4.54 kg) 008365-XXX 008366-XXX AL M25 Relay X 6 lb (2.75 kg) 316 SS M25 Relay X 10 lb (4.54 kg) 008367-XXX X2200A4M13R1 008368-XXX AL M25 Relay/4-20 mA X X 6 lb (2.75 kg) X2200S4M13R1 316 SS M25 Relay/4-20 mA X X 10 lb (4.
ULTRAVIOLET X2200 UV Flame Detector / xWatch Camera X2200A3N33A2 X2200A3M33A2 X2200S3N33A2 X2200S3M33A2 009564-XXX 009565-XXX 009566-XXX 009567-XXX AL AL SS SS 3/4 NPT M25 3/4 NPT M25 Relay/4-20 Relay/4-20 Relay/4-20 Relay/4-20 NTSC NTSC NTSC NTSC X X X X X X X X Ship Weight 9 lb (4.1 kg) 9 lb (4.1 kg) 14 lb (6.4 kg) 14 lb (6.
ULTRAVIOLET Table D1 - X2200 Software Part Number Configuration Matrix Dash UV Sensitivity Arc Rejection -001 High High -002 High Very High -003 High Off -005 Medium High -006 High High -007 High High -008 High Very High -009 High Off -010 Medium High 011 High High -013* High Off -014* High Off -015 Very High Low -016 Very High Low Alarm Relay De-Energized Non-latching De-Energized Non-latching De-Energized Non-latching De-Energized Non-latching De-Energized Non
X-SERIES FLAME DETECTOR ACCESSORIES X-Series Flame Detector Accessories X-Series Flame Detector Sensor Modules Model Part Number * Material EEx de EE xd X3301 Sensor Mod X3301 Sensor Mod X3301 Sensor Mod X3301 Sensor Mod 007752-XXX 007753-XXX 007754-XXX 007755-XXX AL AL 316 SS 316 SS X X3301 Sensor Mod X3301 Sensor Mod X3301 Sensor Mod X3301 Sensor Mod 007752-005** 007753-005** 007754-005** 007755-005** AL AL 316 SS 316 SS X X3302 Sensor Mod X3302 Sensor Mod X3302 Sensor Mod X3302 Sensor Mod 008
X-SERIES FLAME DETECTOR ACCESSORIES X-Series Flame Detector Misc. Accessories Model and/or Description Part Number Material Ship Weight Converter RS485 to RS232 000511-029 <1 lb (<0.45 kg) W6300B1002 Inspector Connector (Inspector Monitor software included) 007819-001 <1 lb (<0.45 kg) Inspector Monitor CD 009207-001 <1 lb (<0.45 kg) Model 375 HART Communicator 103346-007 7.5 lb (3.4 kg) Magnet Magnet and Adapter for Extension Pole Magnet and Extension Pole 102740-002 008082-001 007739-001 <1 lb (<0.
X7050 X7050 xWatch™ Explosion-Proof Surveillance Camera X7050 xWatch Explosion-Proof Surveillance Camera (Spec Sheet 90-1193) An explosionproof surveillance camera providing high-resolution color images of activity in the monitored area, which allows the capture and recording of fires and other activities on video. When a detector goes into alarm, the operator can immediately view the monitored area in real time and accurately assess the risk and location of the fire.
X7050 X7050 Model Matrix MODEL DESCRIPTION X7050 xWatch Explosion Proof CCTV TYPE MATERIAL A Aluminum S Stainless Steel TYPE THREAD TYPE 1E 1/2" NPT 1F M20 TYPE VIDEO OUTPUT 50 NTSC 51 PAL TYPE APPROVALS W FM/CSA/ATEX/CE TYPE CLASSIFICATION 2 Division/Zone Ex d X7050 xWatch Camera Model X7050A1E50W2 X7050A1F50W2 X7050S1E50W2 X7050S1F50W2 X7050A1E51W2 X7050A1F51W2 X7050S1E51W2 X7050S1F51W2 Part Number Material 009580-001 AL 009581-001 AL 009582-001 SS 009583-001 SS 009584-001 009585-001 009586-001 009587-0
C7050 C7050 Detector C7050 Detector (Manual: 95-8214) combined with the EQ2200UVHT (95-8570) on an EQP (or as a replacement on an older EQ system) provides fast, reliable flame detection in a wide variety of applications. The detector has the Automatic Optical Integrity (oi) feature, providing a continuous check of detector optical surfaces, detector sensitivity, and electronic circuitry of the detector/controller system. Not recommended for applications where welding or lightning may be present.
C7050 C7050B Model Matrix MODEL DESCRIPTION C7050B Controller Based UV Flame Detector TYPE MATERIAL A Aluminum S Stainless Steel (316) TYPE 6 1 Port TYPE THREAD TYPE E 1/2" NPT F M20 TYPE OUTPUTS 4 Pulse (Standard) TYPE TUBE MODULE OPTION A DE1888A2 (Standard) K DE1888K2 (High Temp) M DE1888M2 (Remote Surveillance, Hydrogen Fires) N DE1888N2 (High Sensitivity, Special App) T DE1888T2 (Electrostatic App) V DE1888V2 (Internal Reflection) W DE1888W2 (Remote Surveillance, Reduced Sensitivity) X DE1888N (High Se
DUAL SPECTRUM INFRARED Det-Tronics PM-5MPX Dual Spectrum® Flame Detector Det-Tronics PM-5MPX Dual Spectrum® Flame Detector (Spec Sheet: 90-1182) is optimized for the rigorous semiconductor fabrication industry, which is beset with many hazards that result in stringent and application-specific requirements for fire protection safety systems.
DUAL SPECTRUM INFRARED Det-Tronics PM-9SBE Dual Spectrum® Det-Tronics PM-9SBE Dual Spectrum® (Spec Sheet: 90-1136) is a fiber optically coupled infrared flame detector that is designed to provide maximum reliability with minimum maintenance in installations that are difficult to monitor using conventional detectors. The device consists of an optical assembly and an electronic assembly connected by a fiber optic cable.
HIGH-SPEED INFRARED C7093/R7094 High-Speed Infrared Flame Detection System The C7093/R7094 High-Speed Infrared Flame Detection System (Spec Sheet: 90-1028) responds in less than 5 milliseconds to a high-intensity flash fire. Designed specifically for applications such as munitions manufacturing, the C7093/R7094 can trigger high-speed extinguishing systems. x x x x DETECTOR R7094 Controller ACCESSORIES C7093 CONTROLLERS x x x x x x KEY: Flame I.
HIGH-SPEED INFRARED C7093 High-Speed Infrared Fire Detector Model Part Number C7093D6025 C7093E8010 004083-006 004083-102* Enclosure Material 316 SS 316 SS Conduit Entry 1/2 in 1/2 in Cable Ship Weight Length 10 ft 2.75 lb (1.24 kg) 10 ft 2.75 lb (1.24 kg) * Alliant Tech Model (no optical test) R7094 High-Speed Infrared Detection Controller Model Part Number Mounting Ship Weight R7094A2001 003703-001 Rack 4.4 lb (2.
SMOKE DETECTORS U5005 and U5006 Smoke Detectors U5005 Smoke Detector (Spec Sheet: 90-1101) is a sensitive, yet rugged, state-of-the-art protection device that is designed for classified areas in hazardous industrial and commercial locations. The detector is designed to operate effectively with both slow smoldering and fastburning fires. Includes an external alarm indicating LED and one set of normally open relay contacts for alarm and one set of normally closed relay contacts for power supervision.
SMOKE DETECTORS U5005 Smoke Detector Model Part Number U5005A1001 004784-007 Housing J-box Conduit CSA Ship Weight Material Material Entry AL AL 25 mm* X 2 lb (0.91 kg) * Shipped with 3/4" adapter. U5006 Duct Mount Smoke Detector Model Part Number Housing Material U5006A1001 004785-004 Fiberglass J-box Conduit Material Entry AL 25 mm * Sample Ship CSA Tube Weight Specify 13 lb X 1,3,6, or 10 ft (5.9 kg) * Shipped with 3/4" adapter.
ACCESSORIES Test Lamps W8066 Portable UV Test Lamp (Spec Sheet: 90-1055) is used for on-site testing of all UV detector types. It replaces W866. Consists of a UV lamp powered by a replaceable 9 volt battery and is contained in a plastic enclosure. Intrinsically safe. W867C Portable UV/IR Test Lamp (Spec Sheet: 90-1055) is used for on-site testing of UV, single frequency IR, or UVIR detectors.
ACCESSORIES W8066 Portable UV Test Lamp Model Part Number FM CSA Ship Weight W8066A1001 Replacement Bulb Screw-on cap, red for Lens Window, Fused Silica Seal, Pushbutton Boot 004483-001 002405-002 004520-003 004648-001 102219-001 X X 1.5 lb (0.7 kg) <1 lb (<0.45 kg) 1.5 lb (0.7 kg) 1.5 lb (0.7 kg) 1.5 lb (0.
ACCESSORIES Laser Aimer, Laser Holder, W6300 Detector Inspector Laser Aimer/Cone of Vision Tester is for use with the Q1201A and Q1201C Laser Holder in sighting and testing the area of flame detection coverage. Battery-powered laser projects a red beam of light and has a rotary switch for turning the device on and off. When used with its holder, the laser beam identifies the center and edges of the detector's COV. Includes battery.
ACCESSORIES Laser Description Part Number For Use With Ship Weight Laser Aimer Battery, 3V Lithium 006097-001 102871-001 Q1201A, B, and C 1 lb (0.46 kg) <1 lb (<0.46 kg) Q1201 Laser Holder/Aimer Model Part Number For Use With Ship Weight Q1201A1001 006066-001 C7050, C7052, U 7602 X3300, X3301, X3302, X2200, X5200, X9800 2 lb (0.95 kg) Q1201C1001 007255-001 2 lb (0.
ACCESSORIES Detector Hardware Q1113A Universal Air Shield Assembly (Manual: 95-8321). Use on UV, IR, and UV/IR detectors (C7050A, B and H, C7051, C7052, C7098, U7600, U7602 and U7698) in areas with high levels of airborne contamination. Consists of Delrin (solvent-resistant plastic) air shield housing with bronze sintered air diffuser. Quick connect air line fitting accepts 1/4 inch O.D. nylon tubing for instrument grade air supply of 5 to 15 psi at 3 or more cubic feet per minute.
ACCESSORIES Q1113 Universal Air Shield Assembly Model Part Number Air Connection Air Supply Air Requirement Ship Weight Q1113A1001 004273-002 1/4 in OD nylon tubing 5-15 psi 3 cfm minimum 1 lb (0.45 kg) Air Requirement Ship Weight 5-15 psi 3 cfm minimum 2 lb (0.9 kg) 5-15 psi 3 cfm minimum 1 lb (0.
ACCESSORIES Detector Mounting Hardware Q9001B Aluminum swivel for positioning the C7050 and X7050. Q9001H Stainless steel swivel for positioning the C7050 and X7050. Q9033A Aluminum swivel for X3301, X3302, X2200, X5200, and X9800. Note: For use with aluminum body detectors only. Q9033B Stainless steel swivel for X3301, X3302, X2200, X5200, and X9800. (DNV approved with X3301) Flame K.
ACCESSORIES Detector Mounting Hardware–Swivels Model Q9001B1175 Q9001H8001 Q9033A1000 Q9033B1000 9/01/2008 Part Number 002099-003 004404-002 007290-002 007290-001 52-1002-5 For Use With Al C7050 and X7050 SS C7050 and X7050 AL X2200, X5200, X9800, X3301,X3302 SS X2200, X5200, X9800, X3301,X3302 Ship Weight 0.5 lb (0.23 kg) 1 lb (0.45 kg) 6 lb (2.75 kg) 14 lb (6.4 kg) Accessories Flame K.
ACCESSORIES Power Supplies 000507-005 and 000507-006 24 Vdc Power Supplies (Spec Sheet: 90-1035). Open frame construction and designed to operate on 120/240 Vac 50/60 Hz to handle the power requirements of IR detection systems, UV/IR detection systems, and larger UV detection systems that typically need higher levels of current than rack-mounted voltage converters can deliver. Use in Q1020 Wall mount enclosures (sold separately) or in other enclosures containing Det-Tronics fire detection equipment.
ACCESSORIES Output Devices for R7XXX Controllers R1425 Rack Mount Detonator Module (Spec Sheet: 90-1021) for high-speed extinguishing systems. Features two independent capacitive-discharge detonator firing circuits monitored for opens. Use with the R7404 controller. Mounts in Q4004 Cage Assembly (sold separately). Operates on 12 or 24 Vdc. R1425 Rack Mount Detonator Module for the R7404 Controller Model Part Number Description Ship Weight R1425A2024 002791-001 3 lb (1.
CONTROLLERS R74XX Controllers The R7404 Controller (Spec Sheet: 90-1014) provide fast, reliable flame detection in a wide variety of applications. The microprocessor-based controller simultaneously monitors up to 16 C7050 ultraviolet detectors in up to eight different zones. The detector has the Automatic Optical Integrity (oi) feature, providing a continuous check of detector optical surfaces, detector sensitivity, and electronic circuitry of the detector/controller system. Selectable time delay.
CONTROLLERS R7404 UV Fire Detection Controller Model R7404B7001 R7404B7003* R7404B7004 R7404C5020 Part Number Channels 002257-001 002257-006 002257-007 002257-005** 8 8 8 8 Backplate STAR High FM CSA Ship Weight Connector Logic Speed X X X X 4.4 lb (2.0 kg) X X X X 4.4 lb (2.0 kg) X X 4.4 lb (2.0 kg) X X X X 4.4 lb (2.0 kg) *Star logic controllers are recommended for outdoor applications. **Consult Factory - for replacement only, replace with R7404B7001.
SPARE PARTS Spare and Replacement Parts U7698E Spare Parts Part Number Replaces 005994-003 Description 005994-001 Electronics Module Electronics Module 005994-002 w/ 4-20 mA output Electronics Module N/A with time and date stamp Electronics Module N/A with time and date stamp - High Speed N/A oi ring for IR detectors Viton O-ring for UV N/A and IR sensor housings N/A Viton O-ring (U7698E rear housings) 005994-004 005994-006 005994-007 003525-001 107427-004 107427-040 - Required per Housing - 0.
SPARE PARTS Circuit Board Parts for J-boxes Part Number For Use With SP005203-002 SP005203-003 SP005203-004 SP005203-005 SP005203-006 U7652B U7652C3 U7652C4 U7652B U7652B Description Replaces 005203-001 With auxiliary relay With 4-20 mA Form C fault relay Time date stamping Ship Weight 0.5 lb (0.23 kg) 0.5 lb (0.23 kg) 0.5 lb (0.23 kg) 0.5 lb (0.23 kg) 0.5 lb (0.
SPARE PARTS IR Sensor Modules Part Number DE3207-001 DE3895-001 DE3895-002 DE3895-003 DE3895-004 DE4161-001 DE4161-002 DE4161-003 DE4960-001 DE4960-003 DE4933-001 DE4933-003 DE5400-001* DE5400-004 DE5500-003 DE5600-001 DE5600-002 DE6000-001 Part Number 003207-001 003895-001 003895-002 003895-003 003895-004 004161-001 004161-002 004161-003 004960-001 004960-003 004933-001 004933-003 005400-001* 005400-004 005500-003 005600-001 005600-002 006000-001 Controller C7052B, C7052C3 C7052J4 C7052J4 C7052K1 C7052K1
SPARE PARTS Backplate Terminal Connectors Use With Part Number Replaces Ship Weight R1425 R6006 R6017 R7094 R7404, R7409, R7484, R7494 W4220 002805-001 002296-001 003356-001 003715-001 002242-001 002224-001 003551-001, 003957-001 - 1 lb (0.45 kg) 1 lb (0.45 kg) 1 lb (0.45 kg) 1 lb (0.45 kg) 1 lb (0.45 kg) 1 lb (0.45 kg) Miscellaneous Detector Parts for Regular Maintenance Part Number Description Use With Ship Weight 001680-001 - 0.5 lb (0.26 kg) - 0.5 lb (0.26 kg) - 0.5 lb (0.26 kg) 0.
TABLE OF CONTENTS GAS PointWatch Eclipse® PIRECL Infrared Hydrocarbon Gas Detector ..........................................................A.1 PointWatch Eclipse® Model Matrix ................................................................................................................................................................ A.2 Typical PIRECL Customer Proposal ........................................................................................................................................
TABLE OF CONTENTS GAS CONTINIUED… PIRVOL Infrared Hydrocarbon Gas Process Monitor ..............................................................................A.25 PIRVOL Model Matrix.................................................................................................................................................................................. A.26 PIRVOL Model Listings ..........................................................................................................................
TABLE OF CONTENTS GAS CONTINUED… C706X Calibration Gas Kits......................................................................................................................C.11 Toxic Calibration Gas Kits ...........................................................................................................................................................................C.12 Toxic Calibration Gas Kit Replacement Parts ...................................................................................
INFRARED PointWatch Eclipse® PIRECL Infrared Hydrocarbon Gas Detector ® The PointWatch Eclipse PIRECL Hydrocarbon Detector (Spec Sheet: 90-1138) is our most rugged stainless steel, point infrared gas detector providing detection of flammable hydrocarbon gases in the LFL range. Standard signal outputs include isolated 4 to 20 mA output, HART communication protocol, and RS-485 serial communication supporting Modbus. An Eagle Quantum Premier version is also available.
INFRARED ® PointWatch Eclipse Model Matrix MODEL DESCRIPTION PIRECL Point Infrared Eclipse Gas Detector TYPE THREAD TYPE 3/4" NPT A M25 B TYPE OUTPUT AND MEASUREMENT OPTIONS 4-20 mA with HART Protocol and RS-485: 0-100% LFL Full Scale Range 1 Eagle Quantum Premier Compatible Only: 0-100% LFL Full Scale Range 4 TYPE ALARM AND FAULT RELAY OUTPUT OPTION A No Relay Option Board installed B Relay Option Board installed (Not compatible with EQP) Ex d only TYPE WEATHER PROTECTION Standard External Black Plastic W
INFRARED ® PointWatch Eclipse Models Model PIRECLA1A1W1 PIRECLA1A2W1 PIRECLA1B1W2 PIRECLA1B2W2 PIRECLA1A5W1 PIRECLA1B5W2 PIRECLA1A3W1 PIRECLA1B3W2 PIRECLB1A3W1 PIRECLB1A1W1 PIRECLB1A2W1 PIRECLB1B1W2 PIRECLB1A5W1 PIRECLB1B5W2 PIRECLB1B2W2 Part number 007168-001 007168-003 007168-005 007168-007 007168-022 007168-023 007168-010 007168-038 007168-040 007168-002 007168-004 007168-006 007168-024 007168-025 007168-027 Entry thread type 3/4 NPT 3/4 NPT 3/4 NPT 3/4 NPT 3/4 NPT 3/4 NPT 3/4 NPT 3/4 NPT M25 M25 M25
INFRARED ® PointWatch Eclipse Models – Russia Model PIRECLB1A1R1 PIRECLB1A1R2 PIRECLB1A2R1 PIRECLB1A2R2 PIRECLB1B1R2 PIRECLB1B2R2 Part number 007168-902 007168-905 007168-904 007168-907 007168-906 007168-908 Entry thread type M25 M25 M25 M25 M25 M25 Output 4-20 mA 4-20 mA 4-20 mA 4-20 mA 4-20 mA 4-20 mA PIRECLB4A1R2 PIRECLB4A2R2 007168-913 007168-915 M25 M25 EQP EQP Relays Weather protection No w/ hydrophobic No w/ hydrophobic No no hydrophobic No no hydrophobic Yes w/ hydrophobic Yes no hydrophobi
INFRARED PIRECL Accessories, Duct Mount, and Sample Draw The Model 375 HART Field Communicator is available from Detector Electronics Corporation under agreement with Fisher-Rosemount Systems, Inc. The 375 Field Communicator enables connection to the PIRECL via the onboard HART port connection.
INFRARED Miscellaneous PIRECL Accessories 375 HART Communicator Part Number 103346-007 Description 375 HART communic ator, CENELEC approved Ship Weight 7.5 lb (3.
INFRARED PointWatch® PIR9400 IR Hydrocarbon Gas Detector PointWatch® PIR9400 Infrared Hydrocarbon Detector (Spec Sheet: 90-1074). For the detection of combustible hydrocarbon gases. Provides reliable operation in high concentrations of background hydrocarbon gases and has low maintenance costs. It is immune to poisoning. Five year warranty. x x x x x x x x x Gas A.
INFRARED ® PointWatch PIR9400 Model Matrix MODEL DESCRIPTION PIR9400 Pointwatch Gas Detector T YPE DETECTOR BODY MATERIAL A Aluminum S Stainless Steel TYPE THREAD TYPE 2 Metric M20 3 3/4" NPT TYPE WEAT HER BAFFLE MATERIAL A Aluminum Polyphthalamide Plastic P TYPE HYDROPHOBIC FILTER Factory-Fitted Hydrophobic filter 1 No hydrophobic filter 2 TYPE LEAD WIRE LENGTH A 22 inch B 44 inch TYPE APPROVALS W FM/CSA/ATEX/CE R Russia B CEPEL (Brazil) 9/01/2008 52-1002-5 Infrared Gas A.
INFRARED ® PointWatch PIR9400 Models and Typical Proposals PointWatch ® PIR9400 IR Detectors Body Matl AL AL Baffle Type AL AL Hydro filter yes yes Approvals Ship Weight 3/4 NPT M20 Wires length 22" 22" FM/CSA/CEN/CE/ATEX FM/CSA/CEN/CE/ATEX 2.0 lb (0.95 kg) 2.0 lb (0.95 kg) 006300-003 006300-004 3/4 NPT M20 22" 22" SS SS Plastic Plastic no no FM/CSA/CEN/CE/ATEX FM/CSA/CEN/CE/ATEX 4.0 lb (1.8 kg) 4.0 lb (1.
INFRARED NOTES 9/01/2008 52-1002-5 Infrared Gas A.
INFRARED U9500H Infiniti® HC–PointWatch® Transmitter U9500H Infiniti® HC–PointWatch® Transmitter (Spec Sheet: 90-1099). For use with a single Det® Tronics PointWatch Eclipse or PIR9400 Infrared Hydrocarbon gas detector.
INFRARED ® U9500H Infiniti Model Matrix MODEL U9500 DESCRIPTION Infiniti Gas Transmitter TYPE GAS H60 IR Combustible TYPE OUTPUT 01 or 02 4-20 mA 04 Relay and 4-20 mA ® U9500H Infiniti PIR9400 Transmitters (U9500 junction box must be ordered separately) Model U9500H6002 U9500H6004 U9500H6002-R U9500H6004-R Part Relays Number 006265-003 006265-009 X 006265-903 006265-909 X Junction Boxes for U9500 Infiniti FM/CSA/ ATEX/CE X X RUS Ship Weight 1 lb (0.46 1 lb (0.46 1 lb (0.46 1 lb (0.
INFRARED Model PIRTB Series PointWatch® Termination Box x x x x x x Gas A.
INFRARED PIRTB Junction Box Model Matrix (for use with Point Infrared Gas Detectors) MODEL PIRTB DESCRIPTION ® PointWatch Termination Box TYPE MATERIAL A Aluminum S Stainless Steel TYPE # OF OPEN PORTS 5 5 Port TYPE THREAD TYPE L Metric M25 N 3/4" NPT TYPE APPROVAL AGENCY W FM/CSA/ATEX/CE TYPE COVER TYPE 1 Short without window 3 Tall straight with window TYPE CABLE ENTRIES Ports 2 thru 6 open V PIRTB Series Termination Boxes Model Part Number Material Conduit Entry FM/CSA/ ATEX/CE Cover Ports Ship
INFRARED PIR9400 PointWatch® Accessories The PointWatch® Direct Duct Mount kit (Manual 95-8525) enables direct mounting of PointWatch® PIR9400 Infrared Hydrocarbon gas detector into air-handling ductwork. Each assembly contains: PointWatch®–modified w/shortened weatherbaffles mounting plate, adapters, and fittings to apply test gas to PointWatch® without duct removal.
INFRARED ® PointWatch Direct Duct Mount Assembly Part Number Conduit Entry 006575-001 006575-002 006575-003 006575-004 006575-903* 006575-904* 3/4 in 3/4 in 20 mm 20 mm 20 mm 20 mm Material Ship Weight AL SS AL SS AL SS 5.5 7.5 5.5 7.5 5.5 7.5 lb lb lb lb lb lb (2.5 kg) (3.4 kg) (2.5 kg) (3.4 kg) (2.5 kg) (3.4 kg) All assemblies above include matching PIR9400 detector. Not recommended for use in high-temperature or dirty applications.
INFRARED Model MIR MSHA Approved IR Gas Detector Model MIR - MSHA Approved IR Gas Detector (Spec Sheet: 90-1196) is a diffusion based point-type infrared (IR) gas detector that provides continuous monitoring for hydrocarbon gases in underground mining applications. The gas detection system is approved by MSHA as permissible for use in gassy mines (Approval No. 18-A070003-0).
INFRARED MIR Mining IR Gas Detector Model Matrix MODEL DESCRIPTION MIR Mining IR Gas Detector TYPE COMBINATION 1 Sensor and Transmitter (TX) 2 Sensor and Termination Box 3 Transmitter (TX) Only TYPE BODY MATERIAL A Aluminum TYPE PORT CONFIGURATION 205 Port 2 Open, Port 5 Sensor (Combination 1 and 2) 603 Port 6 Open, Port 3 Sensor (Combination 1) 200 Port 2 Open (Combination 3) 600 Port 6 Open (Combination 3) 260 Ports 2 and 6 Open (Combination 3) TYPE WEATHER BAFFLE MATERIAL N N/A A Plastic w/ 90 micron fil
INFRARED PIRDUCT IR Gas Monitor The Model PIRDUCT DuctWatch™ (Spec Sheet: 90-1188) is an infrared (IR) based flammable gas monitoring solution designed for combustion turbine enclosure monitoring and similar air handling ductwork applications. The DuctWatch is easy to install and commission, and does not require expensive extractive sampling system hardware.
INFRARED PIRDUCT Model Matrix MODEL DESCRIPTION PIRDUCT Point Infrared DuctWatch Gas Monitor TYPE Thread Type A 3/4" NPT B M25 TYPE SIGNAL OUTPUT 1 4-20 mA TYPE APPROVALS W FM/CSA/ATEX/CE TYPE WIRING TERMINATION JUNCTION BOX 1 Factory-fit with PIRTBA5NW3V (std 4-20 mA), AL, 3/4"NPT cable entry 2 Factory-fit with PIRTBA5LW3V (std 4-20 mA), AL, M25 cable entry 3 Factory-fit with EQ2253DCU (EQP sys only), AL, 3/4"NPT cable entry 4 Factory-fit with EQ2207DCU (EQP sys only), AL, M25 cable entry 5 No factory-fit
INFRARED PointWatch® PIR9400, PointWatch Eclipse® and PIRDUCT Calibration Kits ® High accuracy compressed gas calibration kits provided for field calibration of all PointWatch IR detectors. Each kit includes: x x x Two 3.6 ft3 (103 liters) cylinders of specified gas Special regulator pressure indicator, 3-foot tube Sturdy plastic carrying case The Windshield Calibration Bag enables calibration to be performed in high wind conditions.
INFRARED PIR9400, PIRECL, and PIRDUCT Calibration Kits Part Number Gas %LFL % Vol Ship Weight 006468-006 006468-002 006468-003 006468-007* 006468-014 006468-914 006468-001 006468-906 006468-015 006468-915 006468-004 006468-005 Butane Ethane Ethylene Methane Methane Methane Methane Methane Propane Propane Propane Propylene 50% 50% 50% 7.5% 50% 50% 50% 50% 50% 50% 50% 50% 0.8 1.5 1.35 0.375 2.2 2.2 2.5 2.5 0.85 0.85 1.1 1 11.5 lb (5.23 kg) 11.5 lb (5.23 kg) 11.5 lb (5.23 kg) 11.5 lb (5.23 kg) 11.
INFRARED Open Path Eclipse OPECL Infrared Gas Detection System The Open Path Eclipse Infrared Gas Detection System (Spec Sheet: 90-1159) is a stainless steel, IR beam-type hydrocarbon gas detection system.
INFRARED Open Path Eclipse Model Matrix MODEL DESCRIPTION OPECL Open-Path Eclipse Infrared Gas Detector TYPE MATERIAL S Stainless Steel TYPE CONDUIT ENTRY THREAD TYPE 2M 2 Port, Metric M25 2N 2 Port, 3/4" NPT TYPE OUTPUT 00 None (Transmitter Only) 14 Eagle Quantum Premier (EQP) (Receiver or Kit) 18 4-20 mA, RS485, HART (Receiver or Kit) 25 4-20 mA, RS485, HART w/Optional Relay Board (Receiver or Kit) - Ex d only TYPE APPROVAL AGENCY W FM/CSA/ATEX/CE TYPE CLASSIFICATION Division/Zone Ex de 1 Division/Zone Ex
INFRARED PIRVOL Infrared Hydrocarbon Gas Process Monitor PIRVOL Infrared Hydrocarbon Gas Process Monitor (Spec Sheet: 90-1137) is a point-type, infrared gas process monitor designed for use in extractive vapor sampling applications. All PIRVOL models provide a continuous 4-20 milliampere signal output that is proportional to a 0-90% by volume hydrocarbon vapor concentration. Each unit is provided with a sealed, aluminum vapor sampling enclosure fitted with brass compression tubing fittings (0.25 inch o.d.
INFRARED PIRVOL Model Matrix MODEL DESCRIPTION PIRVOL Point Infrared Volumetric Gas Process Monitor TYPE Application LT Light Hydrocarbon HV Heavy Hydrocarbon VR Vapor Recovery TYPE Material A Aluminum S Stainless Steel TYPE T hread Type 2 M20 3 3/4" NPT TYPE Sampling Cup A with Sampling Cup B without Sampling Cup (for replacement only) TYPE APPROVALS C CSA PIRVOL Model Listings PIRVOL Light Hydrocarbon Measurement Models Model Part Number Description PIRVOLLTA3AC 009884-001 AL, 3/4" NPT, with cup PIRVOLLT
CATALYTIC Combustible Gas Sensor (CGS) Combustible Gas Sensor (CGS) (Spec Sheet: 90-1041). Stainless steel catalytic sensor that provides an accurate measurement of combustible gas concentration in the % LFL range. Requires Model 505, U9500A or DCUEX transmitter. x x x x x x x Gas B.
CATALYTIC Combustible Gas Sensor for DCUEX, Models 505, 500, and K-Series (constant voltage) Transmitters Model Part Number CGSS1A6V2R1X 006824-002 CGSS1A3V2R1X 006824-006 CGSS1C6V2R1X CGSS1C6V2R1R 006824-004 006824-904 Replaces old catalytic sensor p/n 225006-002, 226931-001, 223106-002 225006-005, 226931-003, 226999-010, 226999-010, 225957-001, 226530-001, 226531-001, 226931-002, 226999-002, 226999-004, 226530-004, 226531-002, 226931-004 226999-013, 226999-018, 226999-019 226999-013, 226999-018,
CATALYTIC U9500A Infiniti Combustible Transmitters (sensor and junction box ordered separately) U9500A Infiniti Combustible Transmitters (Manual: 95-8444). For use with CGS, the Infiniti provides an analog signal output and onboard readout of detected gas level. A number of optional features are also available. x x x x x x x x x Gas B.
CATALYTIC U9500 Infiniti Model Matrix MODEL U9500 DESCRIPTION Infiniti Gas Transmitter TYPE GAS A10 Catalytic Combustible TYPE OUTPUT 01 or 02 4-20 mA 04 Relay and 4-20 mA U9500A Infiniti® Combustible Gas Transmitter (junction box and sensor must be ordered separately) Model Part Number Relays U9500A1001 U9500A1004 U 9500A1001-R U 9500A1004-R 006265-001 006265-007 006265-901 006265-907 X X FM/CSA/ Russian Ship Weight ATEX/CE X 1 lb (0.46 kg) X 1 lb (0.46 kg) X 1 lb (0.46 kg) X 1 lb (0.
CATALYTIC Model 505 Combustible Transmitter (includes junction box, sensor ordered separately) Model 505 Combustible Transmitter (Spec Sheet: 90-1114). Designed for use with CGS sensor, the 505 provides an analog signal output representing detected gas concentration. The 505 is always used with a gas controller, PLC or similar analog input signal receiver.
CATALYTIC Model 505 Model Matrix Model 505 Description Catalytic Combustible Gas Transmitter Type Enclosure Material A Aluminum S Stainless Steel Type Conduit Entries and Orientation 2-ports, ST-straight-through config (180 degree orientation) 2 2-ports, L-configuration (90 degree orientation) 3 3-ports, T-configuration 4 5-ports 5 Type Thread Type 3/4" NPT A Metric M20/M25 C Type Output 4-20 mA 2 Type Signal Loop Impedance 0-125 ohms (replaces K series) A B 100-500 ohms (replaces Model 500) Type Classific
CATALYTIC Combustible Gas Calibration Kits Combustible Gas Calibration Kits (Spec Sheet: 90-1059) for combustible gas sensors. Kits include sturdy plastic carrying case containing: x x x Gas B.7 Two 3.
CATALYTIC Combustible Gas Calibration Kits Model Listing and Typical Proposals Calibration Kits for Catalytic Sensor Part Number 225130-002 225130-902* 225130-003 225130-005 225130-006 225130-007 225130-008 225130-014 225130-914* 225130-001 225130-901* 225130-015 225130-915* 225130-004 225130-009 Gas LFL Ethane 50% Ethane 50% Ethylene 50% Hydrogen 50% Methane 20% Methane 25% Methane 35% Methane 50% Methane 50% Methane 50% Methane 50% Propane 50% Propane 50% Propane 50% Empty kit–no cal gas % Vol Ship
CATALYTIC Model STB Series Sensor Termination Box and Separation Kit Model STB Series Sensor Termination Box and Separation Kit includes a junction box, proper connector board required hardware.
CATALYTIC STB Model Matrix Model STB Description Sensor Termination Box Type Compatibility 1 Model 505 Catalytic Transmitter 2 Model U9500A Catalytic Transmitter 3 Model C706x electrochmical gas sensor/transmitter 4 10 terminal 5 12 terminal Type Material A Aluminum S Stainless Steel Type # of Ports, thread type 2M 2 PORT, M20/M25 at 90 degree orientation 2N 2 PORT, 3/4" NPT at 90 degree orientation 2S 2 PORT, M20 at 180 degrees vertical 2U 2 PORT, 3/4" NPT at 180 degree vertical 2X 2 PORT, M20 at 90 degre
CATALYTIC Duct Mount and Sample Draw Assemblies for CGS Direct Duct Mount Assembly (Spec Sheet: 90-1046). For mounting combustible sensors to air handling duct work. The Direct Duct Mount CGS assembly enables combustible gas detection in air handling, heating, ventilating, and air conditioning ducts. Designed for flat surface mounting only.
CATALYTIC CGS Accessories: Rain Shields, Splash Guards, Dust Covers, Remote Calibration Cups Rain Shields (Spec Sheet: 90-1046) protect combustible sensors from rain and snow. Splash Guards (Spec Sheet: 90-1046) protect combustible sensors from ingress due to rain or splashing water. Dust Covers (Spec Sheet: 90-1046) protect sensors against dust, oil, and high wind environments. Porex and stainless steel filters available.
TOXICS NTM Nanotechnology MOS H2S Gas Sensor Model NTM Nanotechnology MOS H2S Gas Sensor (Spec Sheet: 90-1195). Stainless steel, nanotechnology MOS sensor that provides an accurate measurement of Hydrogen Sulfide (H2S) gas. 4-20 mA output Approved as a stand alone sensor Performance approved to ANSI/ISA 92.0.
TOXICS NTM Model Structure MODEL DESCRIPTION NTM Nanotechnology MOS H2S Gas Sensor TYPE THREAD TYPE 3/4 NPT 1A TYPE MEASUREMENT OPTIONS 0-100 ppm 10 TYPE APPROVALS FM F NTM Gas Sensor Model NTM1A10F Part Number 009910-001 Thread 3/4 NPT ppm 0-100% Ship Weight 1 lb (0.45 kg) ® U9500B Infiniti Transmitter Model Part Number Relay U9500B2002 U9500B2004 006265-002 006265-008 X FM/CSA ATEX/CE X X Ship Weight 1 lb (0.46 kg) 1 lb (0.
TOXICS C706X Sensor/Transmitter C706X Sensor/Transmitter (Spec Sheet: 90-1079) housing. Two-wire, stainless steel or aluminum toxic gas detector with 3/4” NPT or 20 mm threads. Purchase EC cell separately for monitoring H2S, O2, CL2, CO and SO2 toxic gases.
TOXICS C706X Electrochemical Sensor Housings (sensor cell sold separately) Model Part Number C7064C4012* C 7064E4012 C7064C5014* C 7064E5012 C 7064E6031 C 7064E6012 C 7064E5014 004539-004 004539-009 004539-014 004539-102 004539-103 004539-104 004539-105 C7067E7012* C7067E7031* 005931-001 005931-002 C 7066E6012 C 7066E6031 C 7066E7012 C 7066E7031 C 7066E8012 C 7066E8031 005736-001 005736-002 005736-003 005736-004 005736-005 005736-006 C 7068E8012 C 7068E8031 006398-001 006398-002 Toxic Gas Hydroge
TOXICS Electrochemical Sensor Cells for use with Model C706x housings Electrochemical sensor cells are provided for use with the C706X gas detector housings. Be sure to use the proper electrochemical sensor cell with the proper model C706x housing. NOTE: Carbon monoxide sensors are available in three ranges–be sure to use proper CO cell with the matching C7066 housing. All sensors are shipped in a sealed bag. Store in a cool, dry place until installation/commissioning is required. Gas C.
TOXICS Electrochemical Sensor Cell Part Number Toxic Gas Measurement Range (PPM) FM/CSA/ ATEX/CE 005434-003 005434-004 005434-002 005932-001 005744-001 005744-002 005744-003 006400-001 005724-001 Hydrogen Sulfide Hydrogen Sulfide Hydrogen Sulfide Chlorine Carbon Monoxide Carbon Monoxide Carbon Monoxide Sulfur Dioxide Oxygen 0-20 0-50 0-100 0-10 0-100 0-500 0-1000 0-100 0-25% v/v X X X Shipping weight for sensor cells is 2 oz. (0.
TOXICS U9500 Infiniti® Transmitter ® U9500 Infiniti Transmitter (Spec Sheet: 90-1099). For use with a single C706x electrochemical toxic gas detector.
TOXICS U9500 Model Matrix MODEL U9500 DESCRIPTION Infiniti Gas Transmitter TYPE GAS B20 H2S C30 Oxygen D40 Chlorine E50 CO F60 SO2 G60 NO2 TYPE OUTPUT 01 or 02 4-20 mA 04 Relay and 4-20 mA ® U9500 Infiniti Toxic Transmitter (junction boxes must be ordered separately) Used with sensor type: Relay U9500B2002 U9500B2004 Part Number 006265-002 006265-008 C7064E-Hydrogen Sulfide C7064E-Hydrogen Sulfide X U9500D4002 U9500D4004 006265-004 006265-010 C7067E-Chlorine C7067E-Chlorine X 1 lb (0.
TOXICS Model STB Series Sensor Termination Box and Separation Kit Model STB Series Sensor Termination Box and Separation Kit includes a junction box, proper connector board required hardware to enable proper mounting and wiring of C706x series detectors.
TOXICS STB Model Matrix Model STB Description Sensor Termination Box Type Compatibility 1 Model 505 Catalytic Transmitter 2 Model U9500A Catalytic Transmitter 3 Model C706x electrochmical gas sensor/transmitter 4 10 terminal 5 12 terminal Type Material A Aluminum S Stainless Steel Type # of Ports, thread type 2M 2 PORT, M20/M25 at 90 degree orientation 2N 2 PORT, 3/4" NPT at 90 degree orientation 2S 2 PORT, M20 at 180 degrees vertical 2U 2 PORT, 3/4" NPT at 180 degree vertical 2X 2 PORT, M20 at 90 degree o
TOXICS C706X Calibration Gas Kits Toxic Calibration Gas Kit consists of a sturdy carrying case containing: 3 Two 3.
TOXICS Toxic Calibration Gas Kits Part Number Concentration Gas Use With 227115-003 227115-004 227115-005 227115-013 227115-001 227115-002 227115-014 227115-015 227115-901 227115-915 227115-011 227115-006 227115-012 50 ppm 250 ppm 500 ppm 5 ppm 50 ppm 20 ppm 10 ppm 25 ppm 50 ppm 25 ppm 10 ppm 20.
TOXICS Duct Mount and Sample Draw Adapters for Toxic Gas Detectors C706X Series Duct Mount Adapter x Enables monitoring of toxic gases within air handling systems while maintaining easy sensor access Recommended for use on positive pressure ductwork with homogenous air mix conditions (nonstratified) Use of flexible cabling recommended to enable sensor removal x x Model Q812 Duct Mount Enclosure Series (Manual: 95-8459) Provides detection in environments involving air handling, heating, ventilating, or ai
TOXICS NOTES 9/01/2008 52-1002-5 Toxics Gas C.
DISPLAYS AND CONTROLLERS FlexVu™ UD10 Universal Display FlexVu™ UD10 Universal Display (Spec Sheet 90-1200) is recommended for applications where a gas detector with digital read-out of detected gas levels and analog, content, and/or Modbus RS485 signal outputs are required. The FlexVu™ UD10 Universal Display Unit is designed for use with DetTronics gas sensor/transmitters such as PIR9400, PIRECL, OPECL, C706x, Model 505/CGS, or NTMOS.
DISPLAYS AND CONTROLLERS FlexVu™ UD10 Model Matrix MODEL DESCRIPTION UD10 Universal Display Unit TYPE MATERIAL A Aluminum S Stainless Steel (316) TYPE THREAD TYPE 5M 5 Port, Metric M25 5N 5 Port, 3/4" NPT TYPE OUTPUTS 14 LON/EQP 25 Relay, 4-20mA, RS485, HART TYPE APPROVAL C CSA W FM/CSA/ATEX/CE TYPE CLASSIFICATION (Div/Zone) 2 Ex d (Flameproof) FlexVu™ UD10 Universal Display Model Part Number Material UD10A5M25W2 UD10A5N25W2 UD10S5M25W2 UD10S5N25W2 UD10A5N25C2 UD10S5N25C2 009621-001 009621-002 009621-
DISPLAYS AND CONTROLLERS R8471 Series Single Channel Rack-Mounted Gas Controllers Features include: Analog 4-20 mA signal input receiver Digital and bar graph displays indicate detected gas level Individual low, high, auxiliary, and fault alarm outputs are field programmable Standard model offers open collector outputs only Premium model offers 4-20 mA output and 4 relay output package All support remote calibration capability Compatible with Det-Tronics gas detector’s transmitters Two controller height opt
DISPLAYS AND CONTROLLERS R8471 Single Channel Rack-Mounted Gas Controllers for use with Q4004 mounting cages (4U height) Model Part Number R8471A1002 005479-001 R8471A1004 005479-002 R8471B2002 005479-003 R8471B2004 005479-004 R8471B2006 005479-031 R8471B2008 005479-032 R8471B2010 005479-029 R8471B2012 005479-030 R8471C3006 005479-025 R8471C3008 005479-026 R8471D6002 005479-009 R8471D6004 005479-010 R8471E5002 005479-007 R8471E5004 005479-008 R8471E5102 005479-013 R8471E5104 005479-014 R8471E5506 005479-0
DISPLAYS AND CONTROLLERS Mounting Cages: Q4003 and Q4004 Q4004 Universal Mounting Cage for use with 4U-height (7”) R8471 gas controllers. Also supports R74xx and R60xx flame detection cards. Same size as previous Q4001 rack used with R73xx controllers. Infrared, Combustible, or Toxic Gas Detector with analog 4-20 mA output UD10 Universal Display ACCESSORIES MOUNTING CAGE DISPLAY/ CONTROLLERS DETECTOR Q4003 Universal Mounting Cage for use with 3U-height (5.2”) R8471 gas controllers. KEY: Gas D.
DISPLAYS AND CONTROLLERS R8471 Mounting Cages Model Part Number Capacity (m ax # of R8471 controllers) Height Config Height Q4004A2019 Q4004E2027 Q4004B2011 Q4004C2009 Q4004D2007 Q4004A2050 4U Blank Plate 005269-001 005269-002 005269-003 005269-004 005269-005 005269-006 005496-001 16 12 8 6 4 2 covers 1 slot width 4U 4U 4U 4U 4U 4U 4U 7.0 in 7.0 in 7.0 in 7.0 in 7.0 in 7.0 in 7.0 in 9.3 7.6 5.9 5.1 4.2 3.1 0.2 lb (4.2 kg) lb (3.5 kg) lb (2.7 kg) lb (2.3 kg) lb (1.9 kg) lb (1.4 kg) lb (0.
DISPLAYS AND CONTROLLERS Q2050 Series Wall Mount Enclosures The Q205x series (Spec Sheet 90-1075) are factory-built and tested NEMA 4X fiberglass enclosures with preinstalled R8471 gas controllers. DETECTOR CONTROLLERS R8471x Series Gas Controller None required ACCESSORIES Infrared, Combustible, or Toxic Gas Detector with analog 4-20 mA output KEY: Gas D.
DISPLAYS AND CONTROLLERS Q2050 Series Wall Mount Enclosures Model Series Relay Power Outputs Supply Q2050 X X X X Q2051 X X Q2052 X X X X X X X X X X X X X X X X Q2053 X X Q2054 X X X X X # of Ctrlrs 1 1 2 2 3 3 4 4 1 1 2 2 1 1 2 2 3 3 4 4 5 5 6 6 5 5 6 6 Height 15.5 in (381 mm) 15.5 in (381 mm) 15.5 in (381 mm) 15.5 in (381 mm) 15.5 in (381 mm) 15.5 in (381 mm) 15.5 in (381 mm) 15.5 in (381 mm) 15.5 in (381 mm) 15.5 in (381 mm) 15.5 in (381 mm) 15.5 in (381 mm) 19.5 in (495 mm) 19.5 in (495 mm) 19.
DISPLAYS AND CONTROLLERS Q1020A Wall Mount Enclosure The Q1020 (Manual 95-8350) is a three-compartment, painted metal enclosure with preinstalled 19 inch Q4004 mounting cage and termination strip factory-wired and tested for easy installation. Additional equipment such as power supply or extra items (external relays, sounders, lights, etc.) may limit maximum controller capacity. Consult factory with specific requirements.
DISPLAYS AND CONTROLLERS Q1020A Wall Mount Enclosures Model Part Number Dimensions Q1020A1001 000803-001 13" x 24" x 21" Q1020A2001 000803-002 26" x 24" x 21" 9/01/2008 52-1002-5 Use With up to (16) R8471 gas controllers up to (32) R8471 gas controllers Ship Weight 80 lb (36 kg) 160 lb (72 kg) Displays and Controllers Gas D.
DISPLAYS AND CONTROLLERS Power Supplies 000507-005 and 000507-006 24 Vdc Power Supplies (Spec Sheet: 90-1035) Ideally suited for Q1020 Wall Mount enclosures or other enclosures that contain Det-Tronics gas detection equipment.
DISPLAYS AND CONTROLLERS 24 Vdc Power Supplies 000507 Series Open Frame Power Supplies Part Number Max Am peres Ship Weight 000507-005 000507-006 3.6 12 6.5 lb (2.95 kg) 15 lbs (6.8 kg) 000604-012 Wall Mount Enclosure with 000507-006 Power Supply ins Part Number Housing Ship Weight 000604-012 Aluminum, NEMA 1 6.5 lb (2.95 kg) 9/01/2008 52-1002-5 Displays and Controllers Gas D.
DISPLAYS AND CONTROLLERS Panel Mount R8471 Controller Assembly Panel Mount R8471 Controller Assembly Each assembly consists of either one or two standard R8471 controllers modified for flat-panel mounting. Typical use includes installation within wall-mount enclosures such as the Q2050 series wall-mount fiberglass enclosure series.
DISPLAYS AND CONTROLLERS Panel Mount R8471 Controller Assemblies Part Number 006631-007 006631-008 006631-009 006631-010 006631-011 006631-012 006631-013 006632-001 006632-002 006632-003 006632-004 006632-005 Gas Type catalytic H2S (100 ppm full scale) PIR9400 chlorine oxygen H2S (20 ppm full scale) H2S (50 ppm full scale) 006632-006 006633-001 006633-002 006633-003 006633-004 006633-005 H2S (50 ppm full scale) 006633-006 007000-001 007000-002 007000-003 007000-004 007000-005 007000-006 007000-007 00700
TABLE OF CONTENTS SYSTEMS Eagle Quantum Premier® System .............................................................................................................A.1 Eagle Quantum Premier® Controller • EQ3001 .........................................................................................B.1 EQ3001 Controller Model Matrix ................................................................................................................................................................... B.
TABLE OF CONTENTS SYSTEMS CONTINIUED… Heat Detectors (Explosion-Proof)...........................................................................................................C.17 Smoke Detectors and Heat Detectors (General Use)............................................................................C.17 Manual Call Stations ...............................................................................................................................C.18 EQ3720RM Relay Module ..........................
OVERVIEW Eagle Quantum Premier® System The Eagle Quantum Premier System (EQP) (Spec Sheet 90-1150) combines “fire detection and extinguishing agent release” and “hazardous gas monitoring” in one complete package. The system is intended for use in hazardous locations and is designed to meet the requirements of approval agencies from around the world. The system consists of a controller and a number of addressable microprocessor-based field devices.
OVERVIEW Relay Module Water Flow, Pressure, etc.
OVERVIEW KEY: INPUT Supervised Inputs OUTPUT INPUT X3301 / X3302 Multispectrum IR Hydrogen Flame Detector INPUT X9800 Single Frequency IR Flame Detector INPUT INPUT X5200 UVIR Flame Detector INPUT X2200 UV Flame Detector INPUT INPUT C7050/UVHT UV Flame Detector EQ22XXIDC Initiating Device Circuit Supervised Outputs MISC Miscellaneous LON Devices INPUT EQ22XXDCUEX Digital Communications Unit EQ22XXIDCSC IDC Short Circuit INPUT Addressable devices are wired into the LON Communications Loop IN
OVERVIEW NOTES 9/01/2008 52-1002-5 Overview Systems A.
CONTROL ROOM Eagle Quantum Premier® Controller • EQ3001 Eagle Quantum Premier Controller • EQ3001 (Spec Sheet: 90-1148) The Eagle Quantum Premier™ Controller is a microprocessor-based module that performs all the communication and control functions for the system. The controller can be configured in a simplex or redundant mode of operation. It includes all the required operator interface controls for a fire alarm and releasing system.
CONTROL ROOM EQ3001 Controller Model Matrix MODEL DESCRIPTION EQ3001 Eagle Quantum Premier Controller TYPE MOUNTING OPTION D Din Rail P Panel TYPE COM Board 1 N None C Control Net TYPE COM Board 2 N None S Serial Expansion TYPE APPROVALS T SIL/FM/CSA/ATEX/CE W FM/CSA/ATEX/CE R VNIIPO/VNIIFTRI (RUSSIA) EQ3001 Controller Model Part Number Mounting Serial ControlNet Expansion Board EQ3001PNNW 007609-062 Panel EQ3001DNNW 007609-063 DIN EQ3001PCNW 007609-065 Panel EQ3001DCNW 007609-066 DIN EQ3001PNSW 007609
CONTROL ROOM Redundancy Parts Part Number 008981-001 008982-001 Description Ship Weight Controller to Controller High Speed Serial Cable (4 ft) LON Termination Module (2 required per LON) 1.0 lb (0.45 kg) 1.0 lb (0.45 kg) Controller Communication Cables Part Number 007633-001 007633-002 007633-003 Description 15 ft. (4.57 m) Controller RS-232 Cable (DB9 Female PC Connection) Controller RS-232 Cable (DB9 Female PC Connection) Controller RS-232 Cable (DB9 Female PC Connection) Length 30 ft. (9.
CONTROL ROOM NOTES 9/01/2008 52-1002-5 Control Room Systems B.
CONTROL ROOM Power Supplies Power Supply. Six power supply options are available: x x x x x x 10 Amp / 60HZ (EQ2110PS)* 30 Amp / 60HZ (EQ2130PS)* 75 Amp / 60HZ (EQ2175PS)* 10 Amp / 50HZ (EQ2111PS)* 30 Amp / 50HZ (EQ2131PS)* 75 Amp / 50HZ (EQ2176PS)* Contact the factory for additional options and current certifications *Requires the use of the DEC Power Supply Monitor, detailed below.
CONTROL ROOM Power Supply Model EQ2110PS* EQ2130PS* EQ2175PS* EQ2111PS* EQ2131PS* EQ2176PS* Part Number 000604-013 000604-014 000604-015 000604-034 000604-035 000604-036 Description EQ2110PS 10A 120VAC 60HZ EQ2130PS 30A 120/208/220 60HZ EQ2175PS 75A 120/208/220 60HZ EQ2111PS 10A 220/240VAC 50HZ EQ2131PS 30A 220/240VAC 50HZ EQ2176PS 75A 220/240VAC 50HZ Ship Weight 50 lb (25.0 kg) 115 lb (57.5 kg) 150 lb (75.0 kg) 50 lb (25.0 kg) 115 lb (57.5 kg) 150 lb (75.
CONTROL ROOM Operator Interface Safety System Software ® Safety System Software (S3). The Eagle Quantum Premier uses the safety system software to provide a user friendly, fully integrated, high performance package. The software provides convenient and accurate system configuration and status information including diagnostic and trouble shooting tools. An optional embedded OPC server provides additional flexibility.
CONTROL ROOM Operating Interface Safety System Software Part Number Description Safety System Software configuration/runtime package 60 007800-011* node version without OPC driver, USB key. Safety System Software configuration/runtime package 60 007800-012* node version with OPC driver, USB key. Safety System Software configuration/runtime package 250 007800-013* node version without OPC driver, USB key.
DEVICES EQ3730EDIO Enhanced Discrete Input/Output Module (EDIO) EQ3730EDIO Enhanced Discrete Input/Output Module (EDIO) • (Spec Sheet: 90-1189) The 8 Channel EDIO Module is specially designed to expand the input and output (I/O) capability of the Det-Tronics Eagle Quantum Premier® System. The unit is designed to provide continuous and automated fire/gas protection while ensuring system operation through continuous supervision of system I/O and signaling line circuit (SLC).
DEVICES EQ3730 EDIO Model Matrix MODEL DESCRIPTION EQ3730 8 Channel Enhanced Discrete Input/Output (EDIO) Module TYPE MOUNTING OPTION D DIN Rail P Panel TYPE APPROVAL AGENCY W FM/CSA/ATEX/CE T SIL/FM/CSA/ATEX/CE R VNIIPO/VNIIFTRI (RUSSIA) EQ3730 EDIO Module Model EQ3730PW EQ3730DW Part Number 009174-002 009174-003 Material AL AL FM/CSA/ ATEX/CE X X Ship Weight 1.0 lb (0.45 kg) 2.0 lb (0.90 kg) Material AL AL SIL/FM/CSA/ ATEX/CE X X Ship Weight 1.0 lb (0.45 kg) 2.0 lb (0.
DEVICES EQ3700DCIO Discrete Input/Output Module (DCIO) EQ3700DCIO Input/Output Module (DCIO) • (Spec Sheet: 90-1149) The 8 Channel DC I/O Module is specially designed to expand the Input and Output (I/O) capability of the Det-Tronics Eagle Quantum Premier® System. The unit is designed to provide continuous and automated fire/gas protection while ensuring system operation through continuous supervision of system I/O and signaling line circuit (SLC).
DEVICES 8 Channel DCIO Module Model Number Matrix MODEL DESCRIPTION EQ3700 8 Channel Discrete Input/Output (DCIO) Module TYPE MOUNTING OPTION D DIN Rail P Panel TYPE APPROVAL AGENCY W FM/CSA/ATEX/CE 8 Channel DCIO Module Model EQ3700PW EQ3700DW 9/01/2008 Part Number 007371-002 007371-003 52-1002-5 Material AL AL FM/CSA/ ATEX/CE X X Ship Weight 1.0 lb (0.45 kg) 2.0 lb (0.90 kg) Devices Systems C.
DEVICES EQ3740IPM Intelligent Protection Module EQ3740IPM Intelligent Protection Module (Spec Sheet: 90-1184). The IPM is designed to provide continuous and automated local area fire protection, while monitoring system operation through continuous supervision of its inputs/outputs (I/O) and Local Operating Network/Signaling Line Circuit (LON/SLC) connection to the EQP controller.
DEVICES 8 Channel IPM Module Matrix MODEL EQ3740 DESCRIPTION Intelligent Protection Module (IPM) TYPE MOUNTING OPTION D DIN Rail P Panel TYPE APPROVAL AGENCY W FM/CSA/ATEX/CE Intelligent Protection Module Model EQ3740PW EQ3740DW 9/01/2008 Part Number 008055-002 008055-003 52-1002-5 Material AL AL FM/CSA/ ATEX/CE X X Ship Weight 1.0 lb (0.45 kg) 2.0 lb (0.90 kg) Devices Systems C.
DEVICES EQ3710AIM Analog Input Module EQ3710AIM Analog Input Module (Spec Sheet: 90-1183). The 8 Channel Analog Input Module ® expands the input capability of the Det-Tronics Eagle Quantum Premier System. The unit provides a means of connecting devices with a 4-20 mA output signal to the Eagle Quantum Premier System. Each channel is fully configurable to provide device and alarm information.
DEVICES 8 Channel Analog Input Module Matrix MODEL DESCRIPTION EQ3710 8 Channel Analog Input (AI) Module TYPE MOUNTING OPTION D Din Rail P Panel TYPE APPROVAL AGENCY W FM/CSA/ATEX/CE 8 Channel Analog Input Module Model EQ3710DW EQ3710PW Part Number 007918-003 007918-002 Material AL AL FM/CSA/ ATEX/CE X X Ship Weight 2.0 lb (0.90 kg) 1.0 lb (0.45 kg) HART Interface Module Part Number 008056-001 9/01/2008 Description HART Interface Module 52-1002-5 Devices Systems C.
DEVICES EQ2200DCU Series Digital Communication Unit EQ2200DCU Series Digital Communication Unit (Spec Sheet: 90-1118) is approved for use with a variety of Det-Tronics sensors including PointWatch® IR gas detector and hydrogen sulfide (H2S) electrochemical sensor. It will also accept any sensor/transmitter with a linear 4 to 20 mA output signal and allows for one person non-intrusive calibration. The DCU digitizes the analog signal and transmits the value to the controller.
DEVICES Digital Communication Unit Model Part Number Description Material Thread Ports FM/CSA/ ATEX/CE Ship Weight EQ2207DCU EQ2217DCU EQ2253DCU EQ2263DCU 006607-005 006607-011 006607-017 006607-019 AL SS AL SS M25/M20 M25/M20 3/4 NPT 3/4 NPT 5 5 5 5 X X X X 6 lb (2.7 kg) 10 lb (4.5 kg) 6 lb (2.7 kg) 10 lb (4.5 kg) EQ22EMDCU 000506-005 DCU Assy., Std DCU Assy., Std DCU Assy., Std DCU Assy., Std Full Elect. Module Assy Panel Mount 3 lb (1.
DEVICES EQ2200DCUEX Series Digital Communication Unit EQ2200DCUEX Series Digital Communication Unit (Spec Sheet: 90-1118) is a digital communication unit for catalytic combustible gas sensors (CGS). The DCUEX digitizes the analog signal and transmits the value to the controller.
DEVICES Digital Communication Unit - Combustible Sensor Only Model Part Number Description Material Thread Ports FM/CSA/ ATEX/CE Ship Weight EQ2207DCUEX EQ2217DCUEX EQ2253DCUEX EQ2263DCUEX 006607-006 006607-012 006607-018 006607-020 AL SS AL SS M25/M20 M25/M20 3/4 NPT 3/4 NPT 5 5 5 5 X X X X 6 lb (2.7 kg) 10 lb (4.5 kg) 6 lb (2.7 kg) 10 lb (4.5 kg) EQ22EMDCUEX 000506-006 DCUEX Assy., Std DCUEX Assy., Std DCUEX Assy., Std DCUEX Assy., Std Full Elect.
DEVICES EQ2200UVHT and C7050 Detector EQ2200UVHT (95-8570) combined with the C7050 Detector (Manual: 95-8214) on an EQP (or as a replacement on an older EQ system) provides fast, reliable flame detection in a wide variety of applications. The detector has the Automatic Optical Integrity (oi) feature, providing a continuous check of detector optical surfaces, detector sensitivity, and electronic circuitry of the detector/controller system.
DEVICES C7050B Model Matrix MODEL DESCRIPTION C7050B Controller Based UV Flame Detector TYPE MATERIAL A Aluminum S Stainless Steel (316) TYPE 6 1 Port TYPE THREAD TYPE E 1/2" NPT F M20 TYPE OUTPUTS 4 Pulse (Standard) TYPE TUBE MODULE OPTION A DE1888A2 (Standard) K DE1888K2 (High Temp) M DE1888M2 (Remote Surveillance, Hydrogen Fires) N DE1888N2 (High Sensitivity, Special App) T DE1888T2 (Electrostatic App) V DE1888V2 (Internal Reflection) W DE1888W2 (Remote Surveillance, Reduced Sensitivity) X DE1888N (High
DEVICES EQ2200IDC Series Initiating Device Circuit (IDC) EQ2200IDC Series Initiating Device Circuit (IDC) (Spec Sheet: 90-1121) consists of a terminal wiring board and a communication module, mounted inside an explosion-proof, water-tight enclosure on a plate for mounting in an enclosure. The IDC accepts two dry contact inputs for use with devices such as relays, pushbuttons, and key switches.
DEVICES Initiating Device Circuit Assembly Model Part Number EQ2253IDC EQ2263IDC EQ2207IDC EQ2217IDC End-of-line Resistor EQ2207IDCSC EQ2217IDCSC 006608-009 006608-010 006608-013 006608-016 000106-108 007257-001 007257-002 Material Enclosure Thread AL SS AL SS J-Box 3/4" NPT J-Box 3/4" NPT J-Box M25/M20 J-Box M25/M20 10Kohm - 2 required AL J-Box M25/M20 SS J-Box M25/M20 Ports 5 5 5 5 FM/CSA/ ATEX/CE X X X X 5 5 ATEX/CE Ship Weight Only 6 lb (2.7 kg) 10 lb (4.5 kg) 6 lb (2.7 kg) 10 lb (4.
DEVICES Heat Detectors (Explosion-Proof) Part Number Description Heat Detector, Class 1, Division 1, Groups B, C & D, fixed type, rate compensated, N.O.
DEVICES Manual Call Stations Part Number Description Manual Call Station, Class 1, Division 1, Groups C & D, NEMA 4X, push button with lift flap (dual action), surface mount, alloy housing painted red, key for reset & test, 10K Ohm end of line resistor, two 1/2” or 3/4" entries, UL 000115-XXX & CSA approved. Options: European approval, LED indicator, custom engraved labels, DPST, other standard or custom paint colors. Consult factory for option pricing.
DEVICES EQ3720RM Relay Module EQ3720RM Relay Module • (Spec Sheet: 90-1181) The 8 Channel Relay Module is specially ® designed to expand the output capability of the Det-Tronics Eagle Quantum Premier System. The Relay Module provides eight channels of relay output points that are programmed for unsupervised operation. The output relays are rated up to 2 amps per channel at 30 Vdc maximum or 0.5 amps per channel at 120 Vac.
DEVICES 8 Channel Relay Module Matrix MODEL DESCRIPTION EQ3720 8 Channel Relay Module (RM) TYPE MOUNTING OPTION D Din Rail P Panel TYPE APPROVAL AGENCY W FM/CSA/ATEX/CE 8 Channel Relay Module Model EQ3720DW EQ3720PW 9/01/2008 Part Number 007792-003 007792-002 52-1002-5 Material AL AL FM/CSA/ ATEX/CE X X Ship Weight 2.0 lb (0.90 kg) 1.0 lb (0.45 kg) Devices Systems C.
DEVICES EQ2500SAM Series Signal Audible Module EQ2500SAM Series Signal Audible Module (Spec Sheet: 90-1129) provides two indicating circuits for controlling UL Listed 24 Vdc polarized audible/visual indicating appliances. The SAM is located on the system LON and is controlled by programmable logic in the Eagle Quantum ® Premier Controller. Each output circuit is independently programmable to allow annunciation of separate events.
DEVICES Signal Audible Module Model Part Number EQ2553SAM EQ2507SAM EQ2563SAM EQ2517SAM EQ25EMSAM EQ25EMSAM6 EQ25EMSAM4 006738-009 006738-013 006738-010 006738-016 000506-007 000505-003 000505-015 Material Thread Ports AL 3/4" NPT 5 AL M25/M20 5 SS 3/4" NPT 5 SS M25/M20 5 FULL Electronic Module ASSY–Panel Mount 3 electronics Modules in Ex d cabinet 2 electronics Modules in Ex d cabinet FM/CSA/ ATEX/CE FM/CSA Only X X X X X X X Ship Weight 6 lb (2.7 kg) 6 lb (2.7 kg) 10 lb (4.5 kg) 10 lb (4.
DEVICES EQ2500ARM Series Agent Release Module EQ2500ARM Series Agent Release Module (Spec Sheet: 90-1128) provides agent release ® capability for the Eagle Quantum System. The ARM is located on the LON and is controlled by programmable logic in the Eagle Quantum Premier Controller. The ARM can be programmed for “Single,” “Cross” or “Counting” Zone Style initiation. Optional time delay, abort, and manual release sequences allow the output to be programmed for use in unique applications.
DEVICES Agent Release Module Model Part Number EQ2553ARM EQ2563ARM EQ2507ARM EQ2517ARM EQ25EMARM 006733-009 006733-010 006733-013 006733-016 000506-009 Material Thread Ports AL 3/4" NPT 5 SS 3/4" NPT 5 AL M25/M20 5 SS M25/M20 5 Full Electronic Module Assy–Panel Mount FM/CSA/ FM/CSA Ship Weight ATEX/CE Only X X X X X 6 lb (2.7 kg) 10 lb (4.5 kg) 6 lb (2.7 kg) 10 lb (4.5 kg) 3 lb (1.
DEVICES Horns and Strobes Horns and Strobes Systems C.
DEVICES Horns and Strobes for Class 1 Division 1 Areas Part Number 000122-XXX Description Horn, Class 1, Division 1, Groups C & D, NEMA 4X, 27 user selectable tones, up to 100 dBA @10 ft., various voltages, surface mount, alloy housing painted red, 10K Ohm end of line resistor, 1/2" or 3/4" entry, UL & CSA approved. Options: European approval, custom engraved labels, standard or custom paint colors. Consult factory for option pricing.
DEVICES EQ2400NE Series Network Extender EQ2400NE Series Network Extender (Spec Sheet: 90-1132) expands the capabilities of the ® Eagle Quantum Premier system by allowing additional nodes as well as additional wiring to be added to the LON communication loop. Without a network extender, the communication network is limited to 60 nodes on a 2,000 meter loop. Each network extender increases the capacity of the loop by 40 nodes and an additional 2,000 meters of wiring.
DEVICES NOTES 9/01/2008 52-1002-5 Devices Systems C.
EAGLE QUANTUM Eagle Quantum System Local Control Unit (LCU) Model EQ2100LCU Part Number 006814-001 FM X CSA CE CEN X X X Ship Weight 20 lb (9.0 kg) Local Control Unit (LCU) Replacement Parts Model EQ2100MR EQ2100LC EQ2100CG EQ2100IM Part Number 006668-001 006566-001 006570-001 006558-001 000505-016 Description CAGE "LCU" STD, GEN. ASSY. LOGIC CONTROLLER, GEN ASSY. QUANTUM GATEWAY, GEN. ASSY. LON ISOLATOR, GEN ASSY. LOGIC CONTROLLER BYPASS KIT Ship Weight 12.2 lb (5.5 kg) 2.6 lb (1.2 kg) 2.6 lb (1.
EAGLE QUANTUM NOTES 9/01/2008 52-1002-5 Eagle Quantum Systems D.
EAGLE LOGIC SYSTEM Eagle Logic Solver (ELS) The Eagle Logic Solver is a point-to-point system that is designed to compliment the EQP system offering. The system has SIL 2 and non-SIL approved modules to allow for a flexible design depending on the certification requirements.
EAGLE LOGIC SYSTEM ELS System Controllers, Controller Carriers, and Accessories Model Part Number Description ELS4521-LC-DT 000650-100 ELS Controller ELS4410-NS-PS 000650-101 ELS Node services power supply monitor ELS4750-CA-NS 000650-102 ELS Controller Carrier, simplex or redundant, power monitoring ELS4521-EB-DT 000650-103 ELS Ethernet BIM Configuration, Workbench, and other Software Model Part Number Description ELS4459-L2-DT 000650-110 ELS Logic Configurator (concurrent licenses after initial) ELS4459-L
SIL 2 CERTIFIED SYSTEM SIL 2 Certified Fire and Gas Detection System Det-Tronics has the capability to offer a third-party approved SIL 2 rated fire and gas detection system fully certified to IEC61508. EQ3001 Eagle Quantum Premier Controllers share a common hardware and software platform with standard EQP Controllers. The SIL rated version of the Controller conducts additional diagnostic checks and annunciates additional fault conditions.
SIL 2 CERTIFIED SYSTEM SIL 2 Certified EQP EQ3001 Controller Model Part Number Mounting EQ3001PNNT EQ3001DNNT EQ3001PCNT EQ3001DCNT EQ3001PNST EQ3001DNST EQ3001PCST EQ3001DCST 007609-072 007609-073 007609-075 007609-076 007609-077 007609-078 007609-079 007609-080 Panel DIN Panel DIN Panel DIN Panel DIN Serial ControlNet Expansion Board SIL/FM/CSA/ ATEX/CE Ship Weight X X X X X X X X 5.0 lb (2.3 kg) 5.0 lb (2.3 kg) 5.0 lb (2.3 kg) 5.0 lb (2.3 kg) 5.0 lb (2.3 kg) 5.0 lb (2.3 kg) 5.0 lb (2.3 kg) 5.
TABLE OF CONTENTS REFERENCES Abbreviations ............................................................................................................................................A.1 Product Life Cycle Definitions ..................................................................................................................A.3 Ordering Information .................................................................................................................................A.4 Ordering Information..
REFERENCES Abbreviations AGC/TE AIM AL amp(s) Arc ARM assy Aux bd(s) cal CE COMM config COV cps Ctrlr CSA dB dBA DCIO DCU DDL DNV e ea EC EDIO EMC EMI Encl EOL EQ EQP EVF FOV FM ft HART Ht IAO ib IEC ID IDC IDCGF Ind IR ISA J-box kg lb LED LEL LFL LON References A.
REFERENCES m mA MOS mm mt N/C NE NEC NEMA No. N.C. N.O.
REFERENCES Product Life Cycle Definitions Active: An active product is one that is being actively promoted, with new versions being released. These products are manufactured on a regular basis and are promoted as the latest technology from Det-Tronics. Retired Product Status (RPS): An RPS product will continue to be manufactured for a maximum of five years after being given this status. No further development work will be done, or new certifications pursued, on RPS products.
REFERENCES Ordering Information Ordering Information If unit required is not listed, it may be possible to order a special model that better fits the requirements. The manufacturer reserves the right to offer a particular model. Consult factory for pricing and availability. Detector Electronics Corporation 6901 West 110th Street Minneapolis, Minnesota 55438 USA The manufacturer reserves the right to make substitutions or changes to products without notice. All prices are in U.S. Dollars. Prices are F.O.B.
REFERENCES General Terms and Conditions for Sales Contract All sales by Detector Electronics Corporation (hereinafter called “Detector”) of equipment offered and sold by it shall be subject to the following General Terms and Conditions which shall be deemed incorporated into all orders and offers to purchase submitted to Detector for acceptance and into all of its acceptances and contracts for sale. 1. EXCLUSION OF WARRANTIES.
REFERENCES purpose/use or whether or not occasioned by Detector’s negligence. Detector shall not be liable to the Buyer for any claims, demands, injuries, damages, actions or causes of action whatsoever based on negligence or strict liability.
REFERENCES 7. ACCEPTANCE OF ORDERS. Orders and offers to purchase received by or on behalf of Detector are subject to acceptance only at its office in Minneapolis, Minnesota. No Detector distributor, sales representative, or field agent has authority to accept orders or make contracts of sale on behalf of Detector. 8. CANCELLATION, COUNTERMAND AND RETURN OF GOODS.
REFERENCES 14. LICENSES AND PERMITS. Where Buyer is located in the United States, or has provided a duly executed power of attorney to its agent, Buyer shall be solely responsible for obtaining all export licenses or governmental permits necessary to export the products from the United States. At Buyer’s request, Detector will endeavor to assist Buyer in obtaining such licenses and permits.
REFERENCES Document Charges Approval Certificates Std. Certificate of Origin Std. Calibration Certificate Std. Certificate of Guarantee/Warranty Std. Certificate of Quality Std. Compliance/Conformance Certificate Std. Test and Inspection Certificate Certificate of Origin – Notarized Certificate of Origin – Chamberized Consularized Documents Custom Certificates (Require Part Number and/or Serial Numbers etc) Each No Charge No Charge No Charge No Charge No Charge No Charge No Charge $ 35.00 $180.
REFERENCES Repair Center and Rental Equipment Pricing Available only for active models listed in this price schedule. Before returning equipment for repair, contact Detector Electronics Customer Service Department to obtain a Return Material Identification (RMI) number that will be reserved for your specific return order, and referenced in all documentation. Pack the return shipment carefully to avoid damage in transit.
REFERENCES CLASS 6 (TEST FEES) UV Sensor Module Gas Sensor (all) $300 $300 RENTAL EQUIPMENT RATES Class 3 $350 per day, including day of shipment 009344-001 HART Communicator 275 009345-001 HART Communicator 375 009360-001 W867 EX Lamp Kit NOTE: The rental charges listed above include overnight shipping. They begin on the day the product ships from the factory, apply to both weekdays and weekends, and end the day before the product is received back at the factory.
REFERENCES Repair Center Warranty Policy Repair Center services performed (excluding all gas sensor inspections and software-related repairs) are warranted against defects in material and workmanship for a period of two (2) months from date of shipment from Detector Electronics Corporation (Det-Tronics). This warranty applies only to the material and workmanship directly related to the specific repair services performed, and does not apply to unrelated device or component failures.
REFERENCES 2009 DET-University Field Training Rate Schedule Training Deliverables All courses provide verbal presentation, practical hands-on with applicable equipment or software, course material handouts, and respective product documentation for each participant. Certificates of Completion are issued on request. Factory-Certified Technical Trainer Rates On-Site Per Day Rate (not to exceed 4 persons or 8 hours)............................................................................................
REFERENCES 2009 Field Services Rate Schedule Field Service Engineer and Project/Software Engineer Field Service Engineer $1,400.00 $175.00 $262.00 $350.00 $110.00 Rates On Site Per Day Rate On Site Per Hour Rate Time and One-Half Double Time Travel Per Hour Rate Project/Software Engineer $1600.00 $200.00 $300.50 $400.00 $120.00 1. Time and one-half applies to all work/travel performed after 8 hours per day or on Saturday. 2.