Specifications

DEVICES
Systems C.1 Devices 52-1002-5 9/01/2008
EQ3730EDIO Enhanced Discrete Input/Output Module (EDIO)
EQ3730EDIO Enhanced Discrete Input/Output Module (EDIO) • (Spec Sheet: 90-1189)
The 8 Channel EDIO Module is specially designed to expand the input and output (I/O)
capability of the Det-Tronics Eagle Quantum Premier
®
System. The unit is designed to provide
continuous and automated fire/gas protection while ensuring system operation through
continuous supervision of system I/O and signaling line circuit (SLC). The EDIO module provides
eight channels of configurable input or output points that can be configured as input/output, two-
wire smoke/heat detector, Class A input, Class A output. Each input point can accept fire
detection devices such as heat, smoke, or unitized flame detectors. Each output point can be
configured for dry contacts, signaling, or releasing output operation. Each channel on the
module is provided with individual indicators for active and fault conditions.
x Monitors eight independent I/O channels
x Individual channels are configurable as an input/output/two-wire smoke/heat detectors/
Class A input/Class A output
x A smoke/heat channel can support up to 15 two-wire smoke and heat devices per channel
x For Class A input and output wiring two channels are required per Class A circuit
x Models with SIL 2 certification
x Individual point Style is configurable as a supervised or an unsupervised point
x User configurable supervision for opens and/or shorts
x Individual point Type is configurable for alarm/supervisory/other input styles,
notification/releasing/dry contact output
x Exceeds the requirements of NFPA 72
x Panel or DIN rail mounting
ACCESSORIES
KEY:
= Required
= Option
= Choice Required
INPUTS
CONTROLLER
IDC
Class A or B
Wiring
X-Series
Relay Output
Flame Detector
Initiating Device
Circuit (Manual
Pull Station)
Two Wire
Smoke
Detector
EQ3730
8 Channel
EDIO
24 Vdc Valve
(Pre-action,
Deluge or Agent
Release)
24 Vdc Valve
(Pre-action,
Deluge or Agent
Release)
24 Vdc
Notification
Appliance (Horn
or Strobe/
Beacon)
EQ300X
Controller
Mounting Option
(Panel or DIN
Rail)
NAC
Class A or B
Output
LON Communication Loop
OUTPUTS