Specifications

DEVICES
Systems C.15 Devices 52-1002-5 9/01/2008
EQ2200IDC Series Initiating Device Circuit (IDC)
EQ2200IDC Series Initiating Device Circuit (IDC) (Spec Sheet: 90-1121) consists of a terminal
wiring board and a communication module, mounted inside an explosion-proof, water-tight
enclosure on a plate for mounting in an enclosure. The IDC accepts two dry contact inputs for use
with devices such as relays, pushbuttons, and key switches.
Accepts inputs from standard “contact closure” input devices such as manual call stations, heat
detectors, key-switches, and proof of agent release flow switches
x Provides two ANSI/NFPA 72 Class B Style B supervised input circuits
x Nonvolatile alarm history memory
x Active fault isolation
x Each input programmable for fire, supervisory, trouble, or normal service
DETECTORSCONTROLLERS
Initiating Device
(Manual Pull
Station)
Initiation Device
(Smoke
Detector)
EQ22XXIDC
Initiating
Device Circuit
EQ300X
Controller
= Required
= Option
= Choice Required
KEY: