SIL 2 CERTIFIED SYSTEM
Systems F.1 SIL Certified 52-1002-5 9/01/2008
SIL 2 Certified Fire and Gas Detection System
Det-Tronics has the capability to offer a third-party approved SIL 2 rated fire and gas detection
system fully certified to IEC61508.
EQ3001 Eagle Quantum Premier Controllers share a common hardware and software platform
with standard EQP Controllers. The SIL rated version of the Controller conducts additional
diagnostic checks and annunciates additional fault conditions. Using Det-Tronics EQP Safety
Controllers in redundant mode will increase their availability, but will have no effect on their ability
to perform a safety-related function. The redundant controller system is certified for use as part of
a SIL 2 system.
EQ3730EDIO Enhanced Discrete Input/Output Module (EDIO) module provides eight channels
of configurable digital input or digital output devices. The EDIO Module is specially designed and
certified to meet the requirements of IEC 61508.
ELS Safety System combines simplex or redundant controller processing with the required I/O
modules to offer a fully functional SIL 2 fire and gas solution certified by TüV. The system
supports the transfers of safety information between controllers using peer-to-peer communication
and supports HART passthrough.
Multi-spectrum Infrared Flame Detector X3301 establishes a new benchmark in multiple-fuel
fire detection performance and false alarm rejection. The detector utilizes advanced signal
processing algorithms supported by an embedded 32-bit microprocessor to provide continuous
protection in the presence of false alarm sources and environments with infrared radiation
present. SIL 2 certified by TüV to IEC-61508 for a 4 to 20 mA and relay output.
PointWatch
®
Eclipse Infrared Gas Detector. Point infrared gas detector providing detection of
flammable hydrocarbon gases in the lower explosion limit (LFL) range. SIL 2 certified by TüV to