Specifications

MULTISPECTRUM INFRARED
Flame A.7 Multispectrum Infrared 52-1002-5 9/01/2008
Table A1 - X3301 Software Part Number Configuration Matrix
Dash Sensitivity Alarm Relay Aux Relay Fault Relay Special
-001 Medium
De-energized
Non-latching
Energized
Non-latching
Energized
Non-latching
None
-002 Very High
De-energized
Non-latching
Energized
Non-latching
Energized
Non-latching
None
-004 Low
De-energized
Non-latching
Energized
Non-latching
Energized
Non-latching
None
-005* Medium
De-energized
Non-latching
De-energized
Non-latching
Energized
Non-latching
Automotive
-006 Medium
De-energized
Latching
De-energized
Latching
Energized
Non-latching
None
-007 Very High
De-energized
Latching
De-energized
Latching
Energized
Non-latching
None
-009 Low
De-energized
Latching
De-energized
Latching
Energized
Non-latching
None
-034 Medium
De-energized
Non-Latching
De-energized
Non-Latching
Energized
Non-latching
Hangar**
-035 Very High
De-energized
Non-Latching
De-energized
Non-Latching
Energized
Non-latching
Hangar**
*Available only on type 21 and 22 (Automotive) outputs.
**Consult factory for recommendations. Hangar mode has delayed response.
Application Recommendations
These are typical industry application settings. They may not be applicable to all installations. Contact factory for application guidance.
General Duty 001
Offshore 001, 004
Turbine 001, 004
Compresso
r
001, 002
Han
g
ar 002, 034 or 035
A
utomotive 005
Note: Latching relays cannot be used in voted systems.