Specifications

SINGLE FREQUENCY INFRARED
Flame B.5 Single Frequency Infrared 52-1002-5 9/01/2008
Table B1 - X9800 Software Part Number Configuration Matrix
Dash
IR
Sensitivity
Alarm Output IR
Qualification
Alarm Relay
Aux Output
Function
Aux Output IR
Qualification
Aux Relay Fault Relay
-001 High TDSA
De-Energized
Non-latching
Follows Alarm TDSA
Energized
Non-latching
Energized
Non-latching
-002 High TDSA or Quick
De-Energized
Non-latching
Follows Alarm TDSA or Quick
Energized
Non-latching
Energized
Non-latching
-003 Very High TDSA or Quick
De-Energized
Non-latching
Follows Alarm TDSA or Quick
Energized
Non-latching
Energized
Non-latching
-004 Very High TDSA
De-Energized
Non-latching
Follows Alarm TDSA
Energized
Non-latching
Energized
Non-latching
-005 High TDSA or Quick
De-Energized
Non-latching
Independent Quick
Energized
Non-latching
Energized
Non-latching
-006 Low TDSA
De-Energized
Non-latching
Follows Alarm TDSA
Energized
Non-latching
Energized
Non-latching
-007 High TDSA
De-Energized
Latching
Follows Alarm TDSA
De-energized
Latching
Energized
Non-latching
-008 High TDSA or Quick
De-Energized
Latching
Follows Alarm TDSA or Quick
De-energized
Latching
Energized
Non-latching
-009 Very High TDSA or Quick
De-Energized
Latching
Follows Alarm TDSA or Quick
De-energized
Latching
Energized
Non-latching
-010 Very High TDSA
De-Energized
Latching
Follows Alarm TDSA
De-energized
Latching
Energized
Non-latching
-011 High TDSA or Quick
De-Energized
Latching
Independent Quick
De-energized
Latching
Energized
Non-latching
-012 Low TDSA
De-Energized
Latching
F
ollows Alarm TDSA
De-energized
Latching
Energized
Non-latching
TDSA = "Time Domain Signal Analysis" patented signal processing algorithm for superior IR false alarm rejection.
Quick = Signal processing for explosive IR events.
Application Recommendations
These are typical industry application settings. They may not be applicable to all installations. Contact factory for application guidance.
General Dut
y
001
Offshore
001
Compresso
r
002
High Speed 003
Hangar 004
A
utomotive 005
Turbine 006
Note: Latching relays cannot be used in voted systems.