Specifications

ULTRAVIOLET/INFRARED
Flame C.1 Ultraviolet/Infrared 52-1002-5 9/01/2008
X5200 UVIR Flame Detector
X5200 UVIR Flame Detector (Spec Sheet: 90-1156) meets the most stringent requirements
worldwide with advanced high speed detection capabilities and immunity to extraneous sources,
combined with a superior mechanical design. The combination of Arc rejection on the UV sensor
and TDSA/Quick on the IR sensor make this detector the highest false alarm immune UVIR
available. The mounting arrangement allows the UV and IR sensors to monitor the same
hazardous location with a 90-degree cone of vision. When both sensors simultaneously detect the
presence of a flame, an alarm signal is generated. The detector has Division and Zone explosion-
proof ratings and is suitable for use in indoor and outdoor applications.
The standard output configuration includes fire, fault, and auxiliary relays and RS485 Modbus.
Optional 4 to 20 mA or Eagle Quantum Premier output is also available. A model with pulse output
is available for easy retrofitting into existing Det-Tronics controller based systems. A multi-color
LED on the detector faceplate indicates detector status condition.
The X5200 housing is available in aluminum or stainless steel, with NEMA 4X and IP66 rating.
Typical applications include: Hangars, munitions, petrochemical applications, and turbines.
x Eagle Quantum Premier and Eagle Quantum compatible
x Patented signal processing, TDSA, Arc
x A new level of false alarm rejection
x Responds to a fire in the presence of modulated blackbody radiation (i.e., heaters, ovens,
turbines) without false alarm
x High-speed capability
x Microprocessor-controlled heated optics for increased resistance to moisture and ice
x Automatic, manual, or magnetic optical integrity (oi) testing
x Fire, fault, and auxiliary relays standard
x 4 to 20 mA isolated output (optional)
x Pulse output for compatibility with controller-based systems (optional)
x IECEx, FM, CSA, ATEX/CE
x Integral wiring compartment for ease of installation
x Class A wiring per NFPA-72
x EN 54 part 10 certified by VDS
x EMI, RFI, EMC Directive Compliant
x Built-in data logging / event monitoring
x Meets NFPA 33 Response requirement for under 0.5 second (when model selected)
x Models available with integral explosion proof camera option (xWatch)