Instructions 95-8554 IR Flame Detector X9800 7.
Table of Contents Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . 14 Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . .
INSTRUCTIONS IR Flame Detector X9800 Important Be sure to read and understand the entire instruction manual before installing or operating the flame detection system. Any deviation from the recommendations in this manual may impair system performance and compromise safety. ATTENTION The X9800 includes the Automatic Optical Integrity (oi ) feature — a calibrated performance test that is automatically performed once per minute to verify complete detector operation capabilities.
The Auxiliary relay has normally open / normally closed contacts, and is configurable for energized or de-energized operation, and latching or non-latching operation. Table 2—Detector Status Indicator Detector Status LED Indicator Power On/Normal Auto oi (no fault or fire alarm) Green 0 to 20 mA Output Power On/Normal Man oi A 0 to 20 mA output is available as an option (in addition to the three relays).
CAUTION These tests require disabling of all extinguishing devices to avoid release resulting from a successful test. integral wiring compartment All external wiring to the device is connected within the integral junction box. The screw terminals accept wiring from 14 to 24 AWG. The detector is furnished with four conduit entries, with either 3/4 inch NPT or 25 mm threads. The magnetic oi test is performed by placing a magnet by the marked location (mag oi) on the outside of the detector.
General APPLICATION INformation FALSE ALARM SOURCES The detector has been designed to ignore steady state infrared sources that do not have a flicker frequency characteristic of a fire, however, it should be noted that if these steady state infrared sources are hot enough to emit adequate amounts of infrared radiation in the response range of the IR sensor and if this radiation becomes interrupted from the view of the detector in a pattern characteristic of a flickering flame, the IR sensor can respond.
IMportant safety notes FACTORS INHIBITING DETECTOR RESPONSE Warning Do not open the detector assembly in a hazardous area when power is applied. The detector contains limited serviceable components and should never be opened. Doing so could disturb critical optical alignment and calibration parameters, possibly causing serious damage. This type of damage could be undetected and could result in failure to see a fire and/or false alarm.
INSTALLATION note The recommended lubricant for threads and O‑rings is a silicone free grease (part number 005003-001) available from Detector Electronics. Under no circumstances should a lubricant containing silicone be used. CENTER AXIS OF DETECTOR FIELD OF VIEW INCORRECT Detector Positioning Detectors should be positioned to provide the best unobstructed view of the area to be protected. The following factors should also be taken into consideration: • Identify all high risk fire ignition sources.
If conduit is used, we recommend installing drains, according to local codes, at water collection points to automatically drain accumulated moisture. It is also recommended to install at least one breather, according to local codes, at upper locations to provide ventilation and allow water vapor to escape. note Refer to“Power Consumption”in the“Specifications” section of this manual. The use of shielded cable is required to protect against interference caused by EMI and RFI.
Relay and 0-20 mA Output Models EOL Resistors (Not Used with EQP Model) Follow the instructions below to install the X9800. To ensure that the insulating material of the wiring terminal block will not be affected by the heat generated by EOL resistors, observe the following guidelines when installing the resistors. 1. Make field connections following local ordinances and guidelines in this manual. Refer to Figures 4 through 12. 2.
X9800 DETECTOR FIRE ALARM PANEL ALARM + 24 VDC – 19 4-20 mA – SPARE 29 18 4-20 mA – REF SPARE 28 COM AUX 27 N.O. AUX 26 N.C. AUX 25 9 4-20 mA + 8 4-20 mA + REF 7 COM FIRE2 COM FIRE 17 6 N.O. FIRE2 N.O. FIRE 16 5 N.C. FIRE2 4 E.O.L. DEVICE4 N.C. FIRE 15 COM FAULT1 COM FAULT 14 RS-485 A 24 3 N.O. FAULT1 N.O.
X9800 DETECTOR X9800 DETECTOR PLC PLC 600 Ω MAX AT 24 VDC 9 4-20 mA + 19 4-20 mA – 29 + 8 4-20 mA + REF 18 28 + – 7 17 27 – 4 TO 20 mA 24 VDC 600 Ω MAX AT 24 VDC 9 + 6 16 26 5 15 25 4 TO 20 mA 24 VDC 13 3 2 24 14 4 – 24 VDC + 12 24 VDC – 11 MAN Oi – 28 17 27 6 16 26 5 15 25 4 14 24 2 24 VDC + 12 1 24 VDC – 11 23 13 MAN Oi 22 C2179 24 VDC – 21 24 VDC – 21 Oi TEST1 24 VDC + – Figure 10—X9800 Detector Wired for Non-Isolated 0 to 20 mA Curren
5. Check all field wiring to be sure that the proper connections have been made. EQP Model 1. Connect external wires to the appropriate terminals inside the device junction box. (See Figure 13 for terminal identification.) 6. Replace the device cover. 2. Connect the shield of the power cable to “earth ground” at the power source. 7. Make the final sighting adjustments and ensure that the mounting bracket hardware is tight. 3. Connect shields for the LON cable as indicated. See Figure 14.
7.
ADDRESS SWITCHES SENSOR MODULE REMOVED FROM HOUSING A2191 Figure 15—Location of Address Switches Setting Device network addresses (EQP Models Only) The address number is binary encoded with each switch having a specific binary value with switch 1 being the LSB (Least Significant Bit). (See Figure 16) The device’s LON address is equal to the added value of all closed rocker switches. All “Open” switches are ignored. Overview of Network Addresses Each device on the LON must be assigned a unique address.
STARTUP PROCEDURE Table 3—Current Level Output Troubleshooting Guide When installation of the equipment is complete, perform the “Fire Alarm Test” below. Allow 20 to 30 minutes for the detector’s heated optics to reach equilibrium. Fire Alarm Test 1. Disable any extinguishing connected to the system. equipment that is 2. Apply input power to the system. 4. Repeat this test for all detectors in the system. If a unit fails the test, refer to the “Troubleshooting” section.
MAINTENANCE oi plate Removal 1. Disable any extinguishing equipment that is connected to the unit. IMPORTANT Pe r i o d i c fl a m e p a t h i n s p e c t i o n s a re n o t recommended, since the product is not intended to be serviced and provides proper ingress protection to eliminate potential deterioration of the flamepaths. 2. Loosen the two captive screws, then grasp the oi plate by the visor and remove it from the detector. See Figure 17. 3.
FEATURES SPECIFICATIONS • Responds to a fire in the presence of modulated blackbody radiation (i.e. heaters, ovens, turbines) without false alarm. OPERATING VOLTAGE— 24 Vdc nominal (18 Vdc minimum, 30 Vdc maximum). Maximum ripple is 2 volts peak-to-peak. • High speed capability — 30 milliseconds. • Built-in data logging / event monitoring, up to 1500 events (up to 1000 general, 500 alarms). • Microprocessor controlled heated optics increased resistance to moisture and ice.
ENCLOSURE MATERIAL— Copper-free aluminum (painted) or 316 stainless steel. 100% REPRESENTS THE MAXIMUM DETECTION DISTANCE FOR A GIVEN FIRE. THE SENSITIVITY INCREASES AS THE ANGLE OF INCIDENCE DECREASES. VIEWING ANGLE 15∞ 30∞ 0∞ 100 Vibration— Conformance per FM 3260: 2000, MIL-STD 810C (Curve AW). 15∞ 30∞ 90 DIMENSIONS— See Figure 19. 80 45∞ 45∞ 70 WIRING— Field wiring screw terminals are UL/CSA rated for up to 14 AWG wire, and are DIN/VDE rated for 2.5 mm2 wire.
CERTIFICATION— IECEx For complete IECEx certification details, refer to Appendix D. FM ® APPROVED VdS Performance per EN54-10, Certificate of Approval G-203084. For complete FM certification details, refer to Appendix A. For complete CSA certification details, refer to Appendix B. EC-Certificate of Conformity 08 0786 – CPD – 20779 EN54-10 Flame detectors - Point detectors. ® For complete VdS certification details, refer to Appendix E.
replacement parts ORDERING INFORMATION The detector is not designed to be repaired in the field. If a problem should develop, refer to the Troubleshooting section. If it is determined that the problem is caused by an electronic defect, the device must be returned to the factory for repair. When ordering, please specify: X9800 IR Flame Detector Refer to the X9800 Model Matrix below for details Q9033 mount is required: Q9033A for aluminum detectors only. Q9033B for aluminum and stainless steel detectors.
X9800 MODEL MATRIX MODEL DESCRIPTION X9800 Single Frequency IR Flame Detector TYPE MATERIAL A Aluminum S Stainless Steel (316) TYPE THREAD TYPE 4M 4 PORT, METRIC M25 4N 4 PORT, 3/4" NPT TYPE OUTPUTS 11 Relay 13 Relay and 4-20 mA 14 Eagle Quantum Premier (EQP) 15 Relay and Pulse 16 Addressable Module Only (Third Party Type) 23 HART, Relay and 4-20 mA TYPE W APPROVAL AGENCY FM/CSA/ATEX/CE/IECEx TYPE CLASSIFICATION* 1 Division/Zone Ex d e 2 Division/Zone Ex d *Detectors are alway
APPENDIX A FM Approval and Performance Report THE FOLLOWING ITEMS, FUNCTIONS AND OPTIONS DESCRIBE THE FM APPROVAL: • Explosion-proof for Class I, Div. 1, Groups B, C and D (T5) Hazardous (Classified) Locations per FM 3615. • Dust-ignition proof for Class II/III, Div. 1, Groups E, F and G (T5) Hazardous (Classified) Locations per FM 3615. • Nonincendive for Class I, Div. 2, Groups A, B, C and D (T3) Hazardous (Classified) Locations per FM 3611. • Nonincendive for Class II, Div.
FM Approvals Description and Performance Report – Continued RESPONSE CHARACTERISTICS: Very High Sensitivity Fuel Size / Flow Rate Distance feet (m) Typical Response Time (seconds)* TDSA Quick Fire n-Heptane 1 x 1 foot 85 (25.9) 15 On Off Methane 32 inch plume 60 (18.3) 5 On Off Propane Torch 2 (0.6) 0.04 On On High Sensitivity Fuel Size / Flow Rate Distance feet (m) Typical Response Time (seconds)* TDSA Quick Fire n-Heptane 1 x 1 foot 50 (15.
FM Approvals Description and Performance Report – Continued FALSE ALARM IMMUNITY: High Sensitivity, TDSA On, Quick Fire Off Distance feet (m) Modulated Response Unmodulated Response Sunlight, direct, reflected — No alarm No alarm Vibration NA No alarm No alarm Arc welding 15 (4.6) No alarm No alarm 70 w sodium vapor lamp 3 (0.9) No alarm No alarm 250 w mercury vapor lamp 3 (0.9) No alarm No alarm 300 w incandescent lamp 3 (0.
APPENDIX B CSA Certification PRODUCTS CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations Class I, Division 1, Groups B, C, and D (T5); Class II, Division 1, Groups E, F, and G (T5); Class I, Division 2, Groups A, B, C, and D (T3); Class II, Division 2, Groups F and G (T3); Class III; Enclosure Type 4X; Infrared Flame Detector/Controller X9800 series, rated 18-30 Vdc, 2.1 Watts to 16.5 Watts. Relay contacts rated 5 Amps @ 30 Vdc. 7.
APPENDIX C ATEX Approval EC-TYPE EXAMINATION CERTIFICATE DEMKO 02 ATEX 132195X Increased Safety Model Flameproof Model II 2 G Ex d e IIC T5–T6 Gb T6 (Tamb –50°C to +60°C) T5 (Tamb –50°C to +75°C) IP66. II 2 G Ex d IIC T5–T6 Gb T6 (Tamb –55°C to +60°C) T5 (Tamb –55°C to +75°C) IP66. 0539 FM ® 0539 FM ® Compliance with: EN 60079-0: 2009 EN 60079-1: 2007 EN 60079-7: 2007 EN / IEC 60529: 2001.
APPENDIX D IECEx Approval IECEx Certificate of Conformity DEMKO IECEx ULD 06.0018X Ex d e IIC T5-T6 Gb T6 (Tamb =–50°C to +60°C) or T5 (Tamb =–50°C to +75°C) IP66. Ex d IIC T4-T6 Gb T6 (Tamb =–55°C to +60°C) T5 (Tamb =–55°C to +75°C) IP66. Compliance with: IEC 60079-0: 2007 IEC 60079-1: 2007 IEC 60079-7: 2006 EN / IEC 60529: 2001. Installation instructions The field wiring connections in the terminal compartment are suitably certified and accepts wiring diameter from 14 AWG (2.
APPENDIX E VdS Schadenverhütung GmbH Approval VdS Performance per EN54-10, Certificate of Approval G-203084. EC-Certificate of Conformity 08 0786 – CPD – 20779 EN54-10 Flame detectors - Point detectors. SUBJECT MATTER OF THE APPROVAL IR Flame Detector Type X9800 for use in Automatic Fire Detection and Fire Alarm Systems. BASIS OF APPROVAL DIN EN 54, Part 10 (05/02) - Flame Detectors.
95-8554 Detector Electronics Corporation 6901 West 110th Street Your local German DET-TRONICS Distributor: Minneapolis, MN 55438 USA X3301 Multispectrum IR Flame Detector PointWatch Eclipse® IR Combustible Gas Detector FlexVu® Universal Display w/ GT3000 Toxic Gas Detector Eagle Quantum Premier® Safety System d.s.f. GmbH T: 952.941.5665 orSpessartstr. 800.765.3473 11 952.829.8750 D - 63263F:Neu - Isenburg Phone: +49 (0)6102 / 7890 - 0 W: http://www.det-tronics.