Specifications

95-855487.2
Relay and 0-20 mA Output Models
Follow the instructions below to install the X9800.
Make field connections following local ordinances 1.
and guidelines in this manual. Refer to Figures 4
through 12.
Check all field wiring to be sure that the proper 2.
connections have been made.
IMPORTANT
Do not test any wiring connected to the detector
with a meg-ohmmeter. Disconnect wiring at
the detector before checking system wiring for
continuity.
Make the final sighting adjustments and ensure that 3.
the mounting bracket hardware is tight.
EOL RESISTORS (Not Used with EQP Model)
To ensure that the insulating material of the wiring terminal
block will not be affected by the heat generated by EOL
resistors, observe the following guidelines when installing
the resistors.
Required EOL resistor power rating must be 5 watts 1.
minimum.
NOTE
EOL resistors must be ceramic, wirewound
type, rated 5 watts minimum, with actual power
dissipation not to exceed 2.5 watts.
This applies
to ATEX/IEC installations only.
Resistor leads should be cut to a length of 2.
approximately 1 1/2 inches (40 mm).
Bend the leads and install the EOL resistor as shown 3.
in Figure 6.
Maintain a 3/8 inch (10 mm) minimum gap between 4.
the resistor body and the terminal block or any other
neighboring parts.
NOTE
The EOL resistor can only be used within the
flameproof terminal compartment. Unused
apertures shall be closed with suitable blanking
elements.
Figure 4—X9800 Terminal Block
9
8
7
6
5
4
3
2
1
19
18
17
16
15
14
13
12
11
4-20 mA +
4-20 mA –
4-20 mA + REF
4-20 mA – REF
COM FIRE
COM FIRE
N.O. FIRE
N.O. FIRE
N.C. FIRE
N.C. FIRE
COM FAULT
COM FAULT
N.O. FAULT
N.O. FAULT
24 VDC +
24 VDC +
24 VDC –
24 VDC –
24 VDC –
29
28
27
26
25
24
23
22
21
SPARE
SPARE
COM AUX
N.O. AUX
N.C. AUX
RS-485 A
RS-485 B
MAN O
i
B2061
Figure 5—Wiring Terminal Identication
1112
13
141516171819
BULKHEAD
3/8 INCH (10 MM) GAP MINIMUM
A2126
Figure 6—EOL Resistor Installation