Specifications
11 95-85547.2
EQP Model
Connect external wires to the appropriate terminals 1.
inside the device junction box. (See Figure 13 for
terminal identification.)
Connect the shield of the power cable to “earth 2.
ground” at the power source.
Connect shields for the LON cable as indicated. 3.
See Figure 14.
NOTE
DO NOT ground any shields at the detector
housing.
Set the device network address. (See “Setting Device 4.
Network Addresses” section of this manual for switch
setting procedure.)
5.
Check all field wiring to be sure that the proper
connections have been made.
6. Replace the device cover.
7.
Make the final sighting adjustments and ensure that
the mounting bracket hardware is tight.
NOTE
Refer to the Eagle Quantum Premier system manual
(number 95-8533) for information regarding power
and network communication cable requirements.
A2089
COM 2 B
24 VDC
–
24 VDC +
POWER SHIELD
COM SHIELD
COM 2 A
COM 1 B
24 VDC
–
24 VDC +
POWER SHIELD
COM SHIELD
COM 1 A
12
11
13
14
15
16
2
1
3
4
5
6
Figure 13—Wiring Terminal Identication for X9800 EQP Model