Specifications

95-8554167.2
fEaTURES
Responds to a fire in the presence of modulated •
blackbody radiation (i.e. heaters, ovens, turbines)
without false alarm.
High speed capability — 30 milliseconds.•
Built-in data logging / event monitoring, up to 1500 •
events (up to 1000 general, 500 alarms).
Microprocessor controlled heated optics for •
increased resistance to moisture and ice.
Automatic, manual or magnetic optical integrity (• o
i
)
testing.
Easily replaceable • o
i
plate.
Fire, fault and auxiliary relays standard.•
0 to 20 mA isolated output (optional).•
Eagle Quantum Premier LON/SLC output (optional).•
Tricolor LED indicates normal operation, fire and fault •
conditions.
Operates under adverse weather conditions.•
Mounting swivel allows easy sighting.•
Integral wiring compartment for ease of installation.•
Explosion-proof/flame-proof detector housing. Meets •
FM, CSA, ATEX and CE certification requirements.
Class A wiring per NFPA-72.•
Meets NFPA-33 response requirement for under •
0.5 second (available when model selected).
3 year warranty.•
Advanced signal processing (TDSA).•
RFI and EMC Directive compliant.•
ASSOCIATED MANUALS
List of X9800 related manuals:
TITLE FORM NUMBER
Pulse 95-8555
EQP 95-8533
HART Addendum
95-8637
SPECIfICaTIONS
OPERATING VOLTAGE—
24 Vdc nominal (18 Vdc minimum, 30 Vdc maximum).
Maximum ripple is 2 volts peak-to-peak.
POWER CONSUMPTION—
Without heater: 2.1 watts at 24 Vdc nominal;
3.5 watts at 24 Vdc in alarm.
2.2 watts at 30 Vdc nominal;
4.0 watts at 30 Vdc in alarm.
Heater only: 8 watts maximum.
Total power: 16.5 watts at 30 Vdc with EOL resistor
installed and heater on maximum.
EOL resistor must be ceramic, wirewound type, rated
5 watts minimum, with actual power dissipation not to
exceed 2.5 watts.
For HART model, refer to Addendum number 95-8637.
POWER UP TIME—
Fault indication clears after 0.5 second; device is ready
to indicate an alarm condition after 30 seconds.
OUTPUT RELAYS—
Fire Alarm relay, Form C, 5 amperes at 30 Vdc:
The Fire Alarm relay has redundant terminals
and normally open / normally closed contacts,
normally de-energized operation, and latching or
non-latching operation.
Fault relay, Form A, 5 amperes at 30 Vdc:
The Fault relay has redundant terminals and
normally open contacts, normally energized
operation, and latching or non-latching operation.
Auxiliary relay, Form C, 5 amperes at 30 Vdc:
The auxiliary relay has normally open / normally
closed contacts, normally energized or de-energized
operation, and latching or non-latching operation.
CURRENT OUTPUT (Optional)—
0 to 20 milliampere (±0.3 mA) dc current, with a
maximum loop resistance of 500 ohms from 18 to
19.9 Vdc and 600 ohms from 20 to 30 Vdc.
LON OUTPUT—
Digital communication, transformer isolated (78.5 kbps).
TEMPERATURE RANGE—
Operating: –40°F to +167°F (–40°C to +75°C).
Storage: –67°F to +185°F (–55°C to +85°C).
Hazardous location ratings from –55°C to +75°C available
on flameproof model.
HUMIDITY RANGE—
0 to 95% relative humidity, can withstand 100%
condensing humidity for short periods of time.