Specifications
95-8554187.2
CERTIFICATION—
FM
APPROVED
®
For complete FM certification details, refer to Appendix A.
For complete CSA certification details, refer to Appendix B.
FM
APPROVED
®
For complete ATEX certification details, refer to Appendix C.
NOTE
Operational performance veried from -40°C to +75°C.
NOTE
An optional third party addressable module can
only be used within the Ex d ameproof model
unless the addressable module is component
certied as Ex e for use within the Ex d e increased
safety model.
NOTE
Refer to “EOL Resistors” section for installation
details. All cable entry devices and blanking
elements shall be certified to “E-generation” or
“ATEX” standards, in type of explosion protection
increased safety “e” or ameproof enclosure “d” (as
applicable), suitable for the conditions of use and
correctly installed. They shall maintain the degree
of ingress protection IP66 for the apparatus.
Unused apertures shall be closed with suitable
blanking elements.
NOTE
For ATEX installations, the X9800 detector housing
must be electrically connected to earth ground.
IECEx
For complete IECEx certification details, refer to Appendix D.
VdS
Performance per EN54-10,
Certificate of Approval G-203084.
EC-Certificate of Conformity
08 0786 – CPD – 20779
EN54-10 Flame detectors - Point detectors.
For complete VdS certification details, refer to Appendix E.