Specifications

23 95-85547.2
FALSE ALARM IMMUNITY:
High Sensitivity, TDSA On, Quick Fire Off
High Sensitivity, TDSA On, Quick Fire Off
High Sensitivity, TDSA On, Quick Fire On
FIELD OF VIEW:
Very High Sensitivity, Quick Fire Off
FM Approvals Description and Performance Report – Continued
*Add 2 seconds for EQP Model.
Fuel Size
Distance
feet (m)
Horizontal
(degrees)
Typical Horiz. Response
Time (seconds)*
Vertical
(degrees)
Typical Vert. Response
Time (seconds)*
n-Heptane 1 x 1 foot
42.5
(13)
+45
–45
12
14
+45
–30
10
16
Methane 32 inch plume
30
(9.1)
+45
–45
7
4
+45
–30
6
4
Fuel Size
Distance
feet (m)
Horizontal
(degrees)
Typical Horiz. Response
Time (seconds)*
Vertical
(degrees)
Typical Vert. Response
Time (seconds)*
n-Heptane 1 x 1 foot
25
(7.6)
+45
–45
7
7
+45
–30
6
5
Methane 32 inch plume
17.5
(5.3)
+45
–45
6
3
+45
–30
4
4
Fuel Size
Distance
feet (m)
Horizontal
(degrees)
Typical Horiz. Response
Time (seconds)*
Vertical
(degrees)
Typical Vert. Response
Time (seconds)*
Black Powder 40 Grams
5
(1.5)
+45
–45
0.04
0.03
+45
–30
0.04
0.04
False Alarm Souce
Distance feet
(m)
Modulated Response Unmodulated Response
Sunlight, direct, reflected
No alarm No alarm
Vibration
NA
No alarm No alarm
Arc welding 15 (4.6) No alarm No alarm
70 w sodium vapor lamp 3 (0.9) No alarm No alarm
250 w mercury vapor lamp 3 (0.9) No alarm No alarm
300 w incandescent lamp 3 (0.9) No alarm No alarm
500 w shielded quartz halogen lamp 3 (0.9) No alarm No alarm
1500 w electric radiant heater 10 (3) No alarm No alarm
Two 34 w fluorescent lamps 3 (0.9) No alarm No alarm