Specifications

95-85541611. 1
features
Responds to a fire in the presence of modulated
blackbody radiation (i.e. heaters, ovens, turbines)
without false alarm.
High speed capability — 30 milliseconds.
Built-in data logging / event monitoring, up to 1500
events (up to 1000 general, 500 alarms).
Microprocessor controlled heated optics for
increased resistance to moisture and ice.
Automatic, manual or magnetic o
i
testing.
Easily replaceable o
i
plate.
Fire, fault and auxiliary relays standard.
0 to 20 mA isolated output (optional).
Eagle Quantum Premier LON/SLC output (optional).
HART communication (optional)
A tri-color LED on the detector faceplate indicates
normal condition and notifies personnel of fire alarm
or fault conditions.
Operates under adverse weather conditions.
Mounting arm allows easy sighting.
Integral wiring compartment for ease of installation.
Explosion-proof/flame-proof detector housing. Meets
FM, CSA, ATEX and CE certification requirements.
Class A wiring per NFPA-72.
Meets NFPA-33 response requirement for under
0.5 second (available when model selected).
3 year warranty.
Advanced signal processing (TDSA).
RFI and EMC Directive compliant.
Associated Manuals
List of X9800 related manuals:
specifications
OPERATING VOLTAGE—
24 Vdc nominal (18 Vdc minimum, 30 Vdc maximum).
Maximum ripple is 2 volts peak-to-peak.
POWER CONSUMPTION—
Without heater: 2.1 watts at 24 Vdc nominal;
3.5 watts at 24 Vdc in alarm.
2.2 watts at 30 Vdc nominal;
4.0 watts at 30 Vdc in alarm.
Heater only: 8 watts maximum.
Total power: 16.5 watts at 30 Vdc with EOL resistor
installed and heater on maximum.
EOL resistor must be ceramic, wirewound type, rated
5 watts minimum, with actual power dissipation not to
exceed 2.5 watts.
For HART model, refer to Addendum number 95-8637.
POWER UP TIME—
Fault indication clears after 0.5 second; device is ready
to indicate an alarm condition after 30 seconds.
OUTPUT RELAYS—
Fire Alarm relay, Form C, 5 amperes at 30 Vdc:
The Fire Alarm relay has redundant terminals
and normally open / normally closed contacts,
normally de-energized operation, and latching or
non-latching operation.
Fault Alarm relay, Form A, 5 amperes at 30 Vdc:
The Fault relay has redundant terminals and
normally open contacts, normally energized
operation, and latching or non-latching operation.
Auxiliary relay, Form C, 5 amperes at 30 Vdc:
The auxiliary relay has normally open / normally
closed contacts, normally energized or
de-energized operation, and latching or non-
latching operation.
CURRENT OUTPUT (Optional)—
0 to 20 milliampere (±0.3 mA) dc current, with a
maximum loop resistance of 500 ohms from 18 to
19.9 Vdc and 600 ohms from 20 to 30 Vdc.
LON OUTPUT—
Digital communication, transformer isolated (78.5 kbps).
TEMPERATURE RANGE—
Operating: –40°F to +167°F (–40°C to +75°C).
Storage: –67°F to +185°F (–55°C to +85°C).
Hazardous location ratings from –55°C to +75°C available
on flameproof model.
HUMIDITY RANGE—
0 to 95% relative humidity, can withstand 100%
condensing humidity for short periods of time.
TITLE FORM NUMBER
Pulse 95-8555
EQP 95-8533
SIL 2 (Safety) 95-8672
HART Addendum
95-8637
Q9033 Mounting Arm
and Collar Attachment
95-8686
Inspector Monitor Software for
X-Series Flame Detectors
95-8581