1 95-855411. 1
IMPORTANT
Be sure to read and understand the entire
instruction manual before installing or operating
the ame detection system. Any deviation from
the recommendations in this manual may impair
system performance and compromise safety.
ATTENTION
The X9800 includes the Automatic
o
i
® (Optical
Integrity) feature — a calibrated performance test
that is automatically performed once per minute
to verify complete detector operation capabilities.
Testing with an external test lamp is not
approved or required.
Description
The X9800 Single Frequency IR Flame Detector meets the
most stringent requirements worldwide with advanced
detection capabilities and immunity to extraneous
sources, combined with a superior mechanical design.
The detector is equipped with both automatic and manual
o
i
test capability.
The detector has Division and Zone
explosion-proof ratings and is suitable for use in indoor
and outdoor applications.
The standard output configuration includes fire, fault and
auxiliary relays. Output options include:
0 to 20 mA output (in addition to the three relays)
Pulse output for compatibility with existing Detector
Electronics Corporation (Det-Tronics
®
) controller
based systems (with fire and fault relays)
Eagle Quantum Premier
®
(EQP) compatible model
(no analog or relay outputs)
HART communication
A tri-color LED on the detector faceplate indicates
normal condition and notifies personnel of fire alarm or
fault conditions.
Microprocessor controlled heated optics increase
resistance to moisture and ice.
The X9800 housing is available in copper-free aluminum
or stainless steel, with NEMA/Type 4X and IP66/IP67
rating.
OUTPUTS
Relays
The standard detector is furnished with fire, fault and
auxiliary relays. All three relays are rated 5 amperes
at 30 Vdc.
The Fire Alarm relay has redundant terminals and
normally open / normally closed contacts, normally
de-energized operation, and latching or non-latching
operation.
The Fault relay has redundant terminals and normally
open contacts, normally energized operation, and
latching or non-latching operation.
INSTRUCTIONS
IR Flame Detector
X9800
©Detector Electronics Corporation 2013 Rev: 6/13