Detcon Model 610A-FB detcon inc. Gas Detection System Operator's Instruction Manual September 14, 1999 Document #684 Rev. 1.1 1.0 Introduction 1.1 Description 1.2 Multiple Alarm Relay Circuit 1.3 Alarm Disable 1.4 Remote Reset 1.5 Installation 1.6 Start-up 1.7 Power Supply 1.8 Warranty 1.
MODEL 610A-FB POWER 2 AMP H O U S T O N ALARM DISABLE T detcon inc. E X A S LOCK LOCK LOCK LOCK LOCK LOCK MODEL 10A MODEL 10A MODEL 10A MODEL 10A MODEL 10A MODEL 10A H2S MONITOR ppm H2S MONITOR ppm H2S MONITOR ppm H2S MONITOR ppm H2S MONITOR ppm H2S MONITOR ppm HIGH LOW FAULT ALARM RESET HIGH LOW FAULT ALARM RESET HIGH LOW FAULT ALARM RESET HIGH LOW FAULT ALARM RESET HIGH LOW FAULT HIGH LOW FAULT ALARM RESET ALARM RESET detcon inc. detcon inc. detcon inc. detcon inc.
recording devices, AC power in, DC power in, remote reset as well as relay logic and power terminations for the multiple alarm relay circuit. Form C relay outputs may be discreet, zoned or common by gold plated jumper tabs located on the controller mother board. Form C dry contacts; common, normally open and normally closed, are provided for 3 alarms; High, Low and Fault. Contacts are rated at .6 amp @125 VAC / 2 amp @ 30 VDC.
1.2 MULTIPLE ALARM RELAY CIRCUIT A multiple alarm relay circuit (figure 2) mounted on the controller mother board is provided with each Detcon Model 610A-FB. The alarm circuit consists of 4 interposing relays (contacts are rated 8 amp @ 117 VAC / 5 amp @ 30 VDC) with 24VDC coils as standard. Other coil voltage ratings must be specified at time of order. The alarm circuit can be configured to output Form C dry contacts (common, normally open and normally closed), AC power or DC power.
Figure 3 - Schematic/Wiring Diagram TB2 +DC 16 GA. Red to TB2 Pin 5 5 DC+ 4 DC– 3 2 POWER SUPPLY 1 –DC 16 GA. Black to TB2 Pin 4 POWER SUPPLY BRACKET TB1 L1 L2 GND 3 2 1 L1 - 16 GA.Black to TB1 Pin 3 L2 - 16 GA.White to TB1 Pin 2 GND - 16 GA.Green TB1 Pin 1 GND L2 SWITCH PCB L1 PS L1 PS+ PS16 GA.-BLK COMMON 16 GA.-BLK +IN 16 GA.-RED +OUT 16 GA.-RED DISABLE 16 GA.-BLK POWER ALARM DISABLE 16 GA.-BLK 2 AMP COMMON BUS RESET BUS + POWER BUS DC IN + TYP.
1.4 REMOTE RESET A remote mounted normally open momentary switch may be used to reset all Model 10A controllers. The reset function is effective when the Model 10A's respective alarms have been programmed in the latching position and alarm conditions have passed. Each Model 10A controller has its own alarm reset switch which is discussed further in section 2.0. 1.5 INSTALLATION Step 1. Securely mount the 610A-FB enclosure (see figure 4). Figure 4 - Dimensions/Mounting Detail .31" DIA. MOUNTING HOLE .
Step 5. Refer to installation and wiring detail of remote mount sensor assemblies as detailed in section 3.0. Terminate field wiring from sensors to Model 610A-FB lugless terminal strips located on the controller mother board as shown in figure 1. Note: Based on the application and use of relay contact outputs, complete all wiring terminations prior to application of power. Shut-in controls may be omitted until system test is complete. 1.