Foundation Fieldbus Bridge Table of Contents 1.0 Description................................................................................................................................................ 1 2.0 Installation................................................................................................................................................ 2 2.1 Installation of Foundation Fieldbus Bridge PCA ................................................................................. 2 2.
Foundation Fieldbus Bridge This page left intentionally blank Shipping Address: 3200 A-1 Research Forest Dr., The Woodlands Texas 77381 Mailing Address: P.O. Box 8067, The Woodlands Texas 77387-8067 Phone: 888.367.4286, 281.367.4100 • Fax: 281.292.2860 • www.detcon.com • sales@detcon.
Foundation Fieldbus Bridge 1.0 Description The Foundation Fieldbus Bridge is a bi-directional digital communication interface that provides data communication between the Model 700 sensors and Foundation Fieldbus enabled devices. The open, nonproprietary Foundation Fieldbus architecture provides a communications protocol for control and instrumentation systems in which each device has its' own "intelligence" and communicates via an all-digital, serial, two-way communications system.
Foundation Fieldbus Bridge 2.0 Installation The Foundation Fieldbus Bridge replaces the Transient Protection Assembly in the condulet the Model 700 sensor is attached to. The condulet and the Model 700 sensor should be mounted as prescribed in the sensor’s manual. For units that have been ordered with the Foundation Fieldbus Bridge installed, the section on installing the FF Bridge PCA can be skipped. 2.
Foundation Fieldbus Bridge 3.0 Operation When power is applied to the Foundation Fieldbus Bridge with the Model 700 sensor attached, the FF Bridge will go through a boot up sequence that will last for approximately 10 seconds. After the boot up sequence the FF Bridge will enter normal operation, and communication with the Host will begin. A green LED Labeled “Fieldbus” on the FF Bridge will illuminate when the FF Bridge is communicating with the Foundation Fieldbus Host.
Foundation Fieldbus Bridge Figure 3 Modbus Settings in NI-FBUS Configurator 700 Sensor FF Bridge IM Rev.0.
Foundation Fieldbus Bridge 3.2 Primary Variables The transducer block (TB) in the Foundation Fieldbus Bridge includes four primary variables that indicate the status of the sensor. These variables are described in the table in Figure 4.
Foundation Fieldbus Bridge 4.0 Specifications Input Power 10 to 30VDC (Nominal 24VDC) Power Consumption (per channel) 100mA Maximum (Including Sensor) 3W Maximum (Including Sensor) Operating Temperature –40°C to +85°C Humidity: 10 to 95% Non-condensing Outputs Foundation Fieldbus H1 (31.25 kbits/sec) Foundation Fieldbus ITK Version 5.0 Manufacturer ID 0xA000 Device Type 0x0005 Warranty One year Five year fixed fee service policy 5.0 Warranty All warranties are FOB the Detcon factory.
Foundation Fieldbus Bridge Appendix A Revision History Revision 0.0 Date 6/2/2010 700 Sensor FF Bridge IM Changes made Release Rev. 0.
Foundation Fieldbus Bridge This page left intentionally blank Shipping Address: 3200 A-1 Research Forest Dr., The Woodlands Texas 77381 Mailing Address: P.O. Box 8067, The Woodlands Texas 77387-8067 Phone: 888.367.4286, 281.367.4100 • Fax: 281.292.2860 • www.detcon.com • sales@detcon.com 700 Sensor FF Bridge IM Rev.0.