Model 840 Operator Manual Rev. 1.9 Page 1 of 29
1. Description
Housed in a NEMA 4X weatherproof enclosure, the Detcon
Model 840-N4X Gas Detection Alarm System has the
capability to handle eight 4-20mA sensor inputs or eight RS-
485 serial sensor inputs. The remotely mounted gas sensor,
(purchased separately), can include any Detcon 4-20mA or
RS-485 serial input device such as combustible gas, toxic gas,
or oxygen deficiency sensors.
The system displays real time channel information on a
backlit LCD. Configuration inputs are completely field-
programmable and include channel number, gas type, and gas
concentration. It also shows the current Alarm/Fault status
via front panel LED indicators. Standard features include
recorded history of Time Weighted Average (TWA), Peak
readings, and Alarm/Fault/Maintenance Events. Additional
features include one-touch Alarm Reset and Alarm Silence
(Acknowledge) functions.
The Model 840-N4X has a built-in power supply, giving the user a multitude of power options. It can be
powered by either 115/230VAC or 11.5 to 30VDC, and has an optional one-hour battery backup in the
event of temporary power loss.
Each control channel has three field programmable alarm relays and one fault relay. The relays have two
discrete form ā€œCā€ contacts and are rated for 5 Amps at 30VDC and 250VAC. The low, high, and high-high
alarms have individually field adjustable set points for each gas channel and include the provision to
configure the alarm relays in a normally energized (failsafe) or normally de-energized mode of operation.
The low, high, high-high and fault alarm relays may also be configured for latching / non-latching and
silenceable / non-silenceable operation.