FP-700 Instruction Manual Rev. 3.0 Page 25 of 40
is not employed for a Temperature Fault and AutoSpan Reminder Fault. For all diagnostic faults, the
associated RS-485 Modbus fault register will be flagged to alert the user digitally.
NOTE
: Refer to the Troubleshooting Guide section 6 for guidance on fault conditions.
Zero Fault
If the sensor drifts below –10% LEL, the “Zero Fault” will be declared. A “Zero Fault” will cause a “Fault
Detected” message to scroll once a minute on the ITM display and drop the 4-20mA output to 0mA. The
Modbus fault register bit for Zero Fault will be set and will not clear until the fault condition has been
cleared. The sensor should be considered “Out-of-Service” until a successful AutoZero calibration is
performed.
Range Fault – AutoSpan
If the sensor fails the minimum signal (Section 3.4.2) change criteria during AutoSpan sequence, the “Range
Fault” will be declared. A “Range Fault” will cause a “Fault Detected” message to scroll once a minute on the
ITM display and drop the 4-20mA output to 0mA. The Modbus fault register bit for Range Fault will be set
and will not clear until the fault condition has been cleared. The sensor should be considered “Out-of-Service”
until a successful AutoSpan calibration is performed.
Stability Fault - AutoSpan
If the sensor fails the signal stability criteria (Section 3.4.2) during AutoSpan sequence, the “Stability Fault”
will be declared. A “Stability Fault” will cause a “Fault Detected” message to scroll once a minute on the ITM
display and drop the mA output to 0mA. The Modbus fault register bit for Stability Fault will be set and
will not clear until the fault condition has been cleared. The sensor should be considered as Out-of-Service”
until a successful AutoSpan calibration is performed.
Clearing Fault - AutoSpan
If the sensor fails the clearing criteria (Section 3.4.2) during AutoSpan sequence, the “Clearing Fault will be
declared. A “Clearing Fault” will cause a “Fault Detected” message to scroll once a minute on the ITM
display and drop the milliamp output to 0mA. The Modbus fault register bit for Clearing Fault will be set
and will not clear until the fault condition has been cleared. The sensor should be considered as “Out-of-
Service” until a successful AutoSpan calibration is performed.
Sensor Fault
If either the active or reference detector should fail and become electrically open or the sensor was missing, a
“Sensor Fault” will be declared. A “Sensor Fault” will cause a “Fault Detected” message to scroll once a
minute on the ITM display. The Modbus fault register bit for Sensor Fault will be set and will not clear
until the fault condition has been cleared. If a Sensor Fault occurs, the 4-20mA signal will be set at 0mA until
the fault condition is resolved.
Processor Fault
If the detector has any unrecoverable run-time errors, a “Processor Fault” is declared. A “Processor Fault”
will cause a “Fault Detected” message to scroll once a minute on the ITM display. The Modbus fault
register bit for Processor Fault will be set and will not clear until the fault condition has been cleared. If a
Processor Fault occurs, the 4-20mA signal will be set at 0mA until the fault condition is resolved.
Memory Fault
If the detector has a failure in saving new data to memory, a “Memory Fault is declared. A “Memory Fault”
will cause the “Fault Detected” message to scroll once a minute on the ITM display. The Modbus fault