Manual
Mounting Hole
6-32 threaded
Ground Point
Mounting
Bolt
Wall (or other
mounting surface)
Use Spacers to move
the J-Box and Sensor
Assembly away from the
wall at least 0.25-0.5" to
allow access to Sensor
2.125"
detcon inc.
LEL Sensor
MODEL
FP-700
EYS Seal Fitting
Drain
Conduit
"T"
3
4
" NPT Fitting
Mounting Holes
5.5"
5"
12.45"
Typ.
5.25"
3
4
" NPT Fitting
Explosion Proof
Junction-Box
(Detcon's Stainless Steel
Junction-Box Shown)
4.9"
Typ.
7.2"
Typ.
2"
FP-700 Inteligent
Transmitter Module
(ITM)
Housing Bottom
Splash Guard
3
4
" NPT Fitting
Plug unused ports
ITM
Ø0.265"
Ø0.265"
8-32 Threaded
Ground Point
Recommended Electrical
Installation Method
Mounting Hole
Spacer
(+)
mA
(-)
A(+)
B(-)
Wiring to
Sensor Assembly
Wht
Blu
Red
Grn
Blk
Explosion
Proof
Junction Box
(+)
mA
(-)
N/U
A(+)
B(-)
Customer
Supplied Wiring
Transient Protection Module
(TPM) P/N 500-003087-100
Install a 100-250 Ohm
resistor if the 4-20mA
output is not used
Mount TPM in Explosion Proof
Enclosure to ground unit
properly. Mount to bottom of
enclosure using 6-32 screws.
The information and technical data disclosed by
this document may be used and disseminated
only for the purposes and to the extent
specifically authorized by Detcon Incorporated
in writing. Such information and technical data
are proprietary to Detcon Incorporated and may
not be used or disseminated except as provided
in the foregoing sentence.
NA
NA
NA
NA
NA
PROJECT NO.
SERIAL NO.
P.O. NO.
REQ. NO.
PLANT:
REVISION HISTORY
Rev DATE DESCRIPTION
DRAWING NO.
6
R. Hutsko
03/30/06
DWG #
REF. DWGS
APPDDRN CHKD
PROJECT:
NA
FIRST ISSUE:
DRAWN BY:
SUBJECT
CLIENT:
FP-700 Series
Wiring, Dimensional,
and Mounting
SHEET NUM.
SALES ORDER NO.
NANTS
SCALE
NA
SIZE
REV
3168-2
A
3200 Research Forest Dr. A-1 * The Woodlands Texas 77381 * www.detcon.com
NA
_
detcon, inc.
DRAWING NO.
3168-2
REV
6
JOB NO.
NA
SIZE
A
NOTES:
If the Sensor is not mechanically
grounded to the Junction Box, and
external ground strap should be used
to insure proper grounding.
6 11/08/13
Change Splashguard and Housing
RH LU
BM
3168
Correct pinout on TPM11/28/062 BM
EMRH
3168
Updates
TPM Changed04/01/073 BM
EMRH
3168
Updates
Removed yellow wire01/14/084 BM
SFRH
3168
Updates
Updates
Add this drawing for Aluminum Condulet06/25/105 3168BMSFRH Updates