3.16 SOFTWARE FLOW CHART
3.17 REVISION LOG
Revision Date Approval Changes Made
1.3 11/28/07 LU Section 3.6.1a and 3.7.2g flow rate changed from “500-1,000 ml/m” to “200 ml/m”.
1.4 12/2/13 LU Section 3.6.1a and 3.7.2g flow rate changed from “200 ml/m” to “500-1,000 ml/m”
Model IR-522 Combustible Hydrocarbon Sensor PG.19
NORMAL
OPERATION
CALIBRATION
P
GM1 (3) PGM2 (3)
1-ZERO 2-SPAN
LEGEND
PGM1 - program switch location #1
PGM2 - program switch location #2
(
M) - momentary pass of magnet
(3) - 3 second hold of magnet
(30) - 30 second hold of magnet
INC - increase
DEC - decrease
# - numeric value
AUTO ZERO
AUTO SPAN
LEL 0-100 V#.#
PGM1 (3) PGM2 (M)
VIEW PROG STATUS
PGM2 (3)
CAL LEVEL @ ##%
P
GM1 (3) PGM1 (M)
PGM2 (30) PGM2 (M)
OPTICS AT ##%
TEMPERATURE ##°C
PGM1 (M) PGM2 (M)
PGM1 (3)
CAL LEVEL @ ##%
INC
DEC
PGM1 (3) PGM2 (M)
SET CAL LEVEL
PGM2 (3)