Manual

21
MP Series
Chart 3.2 • Diagnostic LEDs
LED Color Description Operation
2
Green Power On if power to unit.
3
Green Heat On if call for heat.
4
Green Fan On if fan energized.
5
Green Valve On if valve energized.
6
Red Service Errors (see Chart 3.3).
LED CODE
(Number of Flashes) STATUS / ERROR
1-1 Long Run Time - Actual temperature fails to rise after 4 hours of consecutive running.
1-2 Blower - Fan is on but static pressure is not reading properly.
1-3 Ignition Module Failure - Ignition module failed to initiate sequence of ignition.
1-4 Ignition Soft Lockout - Control will auto reset after 15 minutes. See lockout in diagnostics
section.
2-1 Ignition Hard Lockout - Ignition module will NOT auto reset; unit will not operate unless
there is an interruption by the user.
2-2 Sensor Error - External temperature sensor is shorted or reading open.
2-3 Internal Software Error - Failure with software on modulating controller.
2-4 Model Selection or Setup Error - Invalid model selection DIP Switch configuration
3-2 Error with User Interface - Short was detected in user interface.
Chart 3.3 • Flash Code Status LED (located on Circuit Board)
Each of the following status codes is a two digit number with the first digit determined by the number of
short flashes and the second digit by the number of long flashes.
Figure 3.2 Circuit Board LEDs
LED2
LED3
LED4
LED5
LED6
LED1
LED2
LED3
LED4
LED5
LED6
LED1
LED2
LED3
LED4
LED5
LED6
LED1
Chart 3.1 • Operation LED
LED Color Description Operation
1
Green Relay ON On if relay ON to ignition module.
LED Short Flash: 0.5 Seconds ON, 0.5 Seconds OFF.
LED Long Flash: 1.5 Seconds ON, 1.5 Seconds OFF.
3.0 Operation • Diagnostics