Product Overview

7
Adhesives
TECHNICAL GUIDE – ADHESIVES ©2021 DEWALT – REV. F
A
NCHORS & FASTENERS
REFERENCE DATA (ASD)
Allowable Load Capacities for Threaded Rod Installed with AC100+ Gold into Hollow
Concrete Masonry Walls with Stainless Steel and Plastic Screen Tubes
1,2,3,4,5,6,7,8,9,10,11,12,13
Anchor
Diameter
d
inch
Screen Tube
type
Minimum
Embedment
h
nom
inch
(mm)
Critical
Spacing
Distance
s
cr
inch
(mm)
Minimum Edge
Distance
c
min
inch
(mm)
Minimum End
Distance
c
min
inch
(mm)
Allowable Load
Tension Load
lbs
(kN)
Direction of Shear
Loading
Shear Load
lbs
(kN)
1/4
Stainless Steel
1-1/4
(32)
4
(102)
1-1/2
(38)
1-1/2
(38)
280
(1.2)
Towards Edge/End
140
(0.6)
1-1/4
(32)
4
(102)
3
(76)
3
(76)
350
(1.6)
Towards Edge/End
275
(1.2)
1-1/4
(32)
4
(102)
1-1/2
(38)
1-1/2
(38)
280
(1.2)
Away From Edge/End
235
(1.0)
1-1/4
(32)
4
(102)
3
(76)
3
(76)
350
(1.6)
Away From Edge/End
465
(2.1)
Plastic
1-1/4
(32)
1 anchor
per cell
3
(76)
3
(76)
140
(0.6)
Towards Edge/End
235
(1.0)
3/8
Stainless Steel
1-1/4
(32)
6
(152)
1-7/8
(48)
1-7/8
(48)
320
(1.4)
Towards Edge/End
145
(0.6)
1-1/4
(32)
6
(152)
3-3/4
(95)
3-3/4
(95)
400
(1.8)
Towards Edge/End
290
(1.3)
1-1/4
(32)
6
(152)
1-7/8
(48)
1-7/8
(48)
320
(1.4)
Away From Edge/End
245
(1.1)
1-1/4
(32)
6
(152)
3-3/4
(95)
3-3/4
(95.3)
400
(1.8)
Away From Edge/End
490
(2.2)
Plastic
1-1/4
(32)
1 anchor
per cell
3
(76)
3
(76.2)
140
(0.6)
Towards Edge/End
235
(1.0)
1/2
Stainless Steel
1-1/4
(32)
8
(203)
3-3/4
(95)
3-3/4
(95.3)
380
(1.7)
Towards Edge/End
215
(1.0)
1-1/4
(32)
8
(203)
11-1/4
(286)
11-1/4
(286)
400
(1.8)
Towards Edge/End
430
(1.9)
1-1/4
(32)
8
(203)
3-3/4
(95)
3-3/4
(95)
380
(1.7)
Away From Edge/End
365
(1.6)
1-1/4
(32)
8
(203)
11-1/4
(285.8)
11-1/4
(286)
400
(1.8)
Away From Edge/End
730
(3.2)
Plastic
1-1/4
(32)
1 anchor
per cell
3
(76.2)
3
(76)
150
(0.7)
Towards Edge/End
215
(1.0)
5/8
Stainless Steel
1-1/4
(32)
8
(203.2)
3-3/4
(95)
3-3/4
(95)
380
(1.7)
Towards Edge/End
215
(1.0)
1-1/4
(31.8)
8
(203.2)
11-1/4
(286)
11-1/4
(286)
400
(1.8)
Towards Edge/End
430
(1.9)
1-1/4
(31.8)
8
(203.2)
3-3/4
(95)
3-3/4
(95)
380
(1.7)
Away From Edge/End
365
(1.6)
1-1/4
(31.8)
8
(203.2)
11-1/4
(286)
11-1/4
(286)
400
(1.8)
Away From Edge/End
730
(3.2)
Plastic
1-1/4
(31.8)
1 anchor
per cell
3
(76.2)
3
(76)
150
(0.7)
Towards Edge/End
215
(1.0)
3/4 Stainless Steel
1-1/4
(32)
8
(203)
3-3/4
(95)
3-3/4
(95)
380
(1.7)
Towards Edge/End
215
(1.0)
1-1/4
(32)
8
(203)
11-1/4
(286)
11-1/4
(286)
400
(1.8)
Towards Edge/End
430
(1.9)
1-1/4
(32)
8
(203)
3-3/4
(95)
3-3/4
(95)
380
(1.7)
Away From Edge/End
365
(1.6)
1-1/4
(32)
8
(203)
11-1/4
(286)
11-1/4
(286)
400
(1.8)
Away From Edge/End
730
(3.2)
1. Tabulated load values are for anchors installed in hollow concrete masonry with minimum masonry strength, f’m, of 1,500 psi (10.3 MPa). Concrete masonry units must be lightweight,
medium-weight or normal-weight conforming to ASTM C 90. Allowable loads have been calculated using a safety factor of 5.0.
2. Anchors must be installed into the hollow cell; anchors are not permitted to be installed in a mortar joint, flange or web of the concrete masonry unit.
3. A maximum of two anchor may be installed in a single masonry cell in accordance with the spacing and edge distance requirements, except as noted in the table.
4. Embedment is measured from the outside surface of the concrete masonry unit to the embedded end of the anchor.
5. Edge or end distance is measured from anchor centerline to the closest unrestrained edge of the CMU block.
6. The critical spacing, s
cr
, for use with the anchor values shown in this table is 16 anchor diameters, except as noted in the table. The critical spacing, s
cr
, distance is the distance where the full
load values in the table may be used. The minimum spacing distance, s
min
, is the minimum anchor spacing for which values are available and installation is permitted. The spacing may be
reduced to 8 anchor diameters by multiplying the tension load value by a reduction factor of 0.60 and multiplying the shear load value by a reduction factor of 0.45.
7. Spacing distance is measured from the centerline to centerline between two anchors.
8. Linear interpolation of load values between the minimum spacing, s
min
, and critical spacing, s
cr
, distances and between minimum edge or end distance, c
min
, and critical edge or end distance,
c
cr
, is permitted if applicable.
9. Concrete masonry width (wall thickness) may be minimum nominal 6-inch-thick provided the minimum embedment (i.e. face shell thickness) is maintained.
10. The tabulated values are applicable for anchors in the ends of hollow concrete masonry units where minimum face shell thickness, minimum edge and end distances are maintained.
11. Anchors are recognized to resist dead, live and wind tension and shear load applications.
12. Allowable loads must be the lesser of the adjusted masonry or bond values tabulated above and the steel strength values.
13. The tabulated values must be adjusted for increased in-service base material temperatures in accordance with the In-Service Temperature chart, as applicable.